7.3.1. Reading Data from Buffer Mode Ports
To retrieve data from Buffer Mode Ports, you must first determine which port buffers contain data. To check port buffers for stored data, access the Command Mode and type /S [Enter] to display the Port Status Screen.
To retrieve data from buffer memory, go to a free
/C xx [Enter]
Where xx is the number or name of the port buffer to be read.
If the port's buffer is empty, the CMS will send a message which reads "Connected xx, Buffer Empty"; where "xx" is the port number. If the buffer contains data, the CMS will display a prompt that offers four options:
●Next Screen: To scroll through data one screen at a time, press the [Space] bar. Each time the space bar is pressed, the next full screen of data will be sent.
●Scroll All: To send all data without pausing, press [1].
●Skip/Connect: To connect to the buffer port without sending stored data, press [2].
●Erase/Connect: To connect to the buffer port and erase stored data, press [3]. Note that buffered data will be erased immediately and will not be sent.
Note: All four of these options also allow
To clear data from the buffer, use the Erase/Connect option, or go to a free
/E xx [Enter]
Where xx is the number or name of the port buffer to be cleared.
7.3.2. Port Buffers
The Status Screen lists the amount of Buffer Memory currently used by each port. The CMS uses buffer memory in two different ways, depending on the
●
●Buffer Mode Ports: Stores data received from connected devices. The user issues a
file:///C/WEBPAGE/guides/cms/html/rev_b/Cmsguide.htm (43 of 59) [11/15/2000 10:52:03 AM]