Lochinvar GAS HEATER FOR COMMERICAL POOL APPLICATIONS General Information, Venting Support

Page 10

Commercial Pool Heaters

INSTALLATION Continued

VENTING

General Information

You must supply adequate combustion and ventilation air to this pool heater. You must provide minimum clearances for the vent terminal from adjacent buildings, windows that open, and building openings. Follow all requirements set forth in the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment or applicable local building codes. Vent installations for connection to gas vents or chimneys must be in accordance with Part 7, “Venting of Equipment” of the above-mentioned standards.

IMPORTANT: Examine the venting system at least once each year. Check all joints and vent pipe connections for tightness. Also check for corrosion or deterioration. If you find any problems, correct them at once.

Venting Support

Support horizontal portions of the venting system to prevent sagging. Provide an upward slope of at least 1/4 inch per foot (21mm/m) on all horizontal runs from the pool heater to the vertical flue run or to the vent terminal on sidewall venting installations.

Do not use an existing chimney as a raceway if another appliance or fireplace is vented through the chimney. The weight of the venting system must not rest on the pool heater. Provide adequate support of the venting system. Follow all local and applicable codes. Secure and seal all vent connections. Follow the installation instructions from the vent material manufacturer.

Vertical Vent Termination Clearances and Location

The vent terminal should be vertical and exhaust outside the building at least 2 feet (0.61m) above the highest point of the roof within a 10 foot (3.05m) radius of the termination.

The vertical termination must be a minimum of 3 feet (0.91m) above the point of exit.

A vertical termination less than 10 feet (3.05m) from a parapet wall must be a minimum of 2 feet (0.61m) higher than the parapet wall.

You must locate the air inlet termination elbow at least 12" (30cm) above the roof or above normal snow levels.

Keep the vent cap clear of snow, ice, leaves, and debris to avoid blocking the flue.

Figure 10 – Vent Termination from Peaked Roof - 10' or Less From Ridge

IMPORTANT: Vent terminations are not shown in Figures 10, 11, 12, and 13. Make sure all vertical vents are installed with vent terminations recommended by the vent manufacturer.

Figure 11 – Vent Termination from Peaked Roof More Than 10' From Ridge

10

Image 10
Contents GAS Heaters for Commercial Pool Applications Commercial Pool Heaters General Product Information UnpackingCommercial Pool Heaters Product Identification Clearances from Combustible Construction Base for Combustible FloorsFreeze Protection Combustion Air FilterInstallation Combustion Air OptionsExhaust Fans Combustion Air from Interior SpaceVenting Support General InformationVertical Vent Termination Clearances and Location Sidewall Vent Termination Clearances and Location Table BLength of Air Inlet Pipe Combustion Air Inlet PipingSidewall Air Inlet Vertical Rooftop Air Inlet Combined Air Inlet PointsConventional Negative Draft Venting Vent System OptionsNegative Draft Flue Outlet Piping Masonry Chimney InstallationsCommon Venting Systems Vertical DirectAire Venting Inspection of a Masonry ChimneySidewall Venting Vent KitsVenting of Flue Products Sidewall Venting Termination Sidewall FanSidewall Venting Without Fan Masonry Chimney Installation Horizontal DirectAire Venting TABLE-EDirect Venting Flue Pipe Materials Horizontal DV Venting TerminationCombustion Air Inlet Piping Air Inlet Piping Materials Length of Air Inlet PipeSealing Type-B Doublewall Vent Pipe or Galvanized Vent Pipe Combined Combustion Air Inlet Points Vertical Rooftop Air InletOutdoor Installation Venting Outdoor Vent/Air Inlet LocationGas Pressure Test Combustion Air Fan Adjustment for startup3-Way Valve Cover Installation Outdoor Vent Cap KitGas Piping Connecting Gas Piping to the Pool HeaterGas Train and Controls Checking Gas Supply Pressure Combination Gas ValvesVenting of Combination Gas Valves TABLE-JMultiple Unit Installations Gas Supply Pipe Sizing Table KGas Manifold Pressure Adjustment Measuring Net Manifold Gas PressureAuxiliary Mixed Water Limit Control Pumped Automatic BypassWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Relief Valve Water Flow SwitchAutomatic Chlorinator and Chemical Feeders Service Indicator Option Pump Purge Delay OptionWay Automatic Bypass Valve Wiring Terminal Strip Connection Options TABLE-MOperation Lighting InstructionsTo Turn Off Gas To Pool Heater Pre-Start ChecklistStarting the Filter System Operation Programming Mode Error Messages Displayed by the Temperature ControllerHot Surface Ignition Control Module Diagnostic Status IndicationHot Surface Igniter and Ignition Control Module Ignition Module Lockout FunctionsTABLE-N Access to Internal Control PanelIgnition and Control Timings Water Chemistry TABLE-OTABLE-P Test Recommended LevelMinimum Pump Performance Pipe Size RequirementsCirculating Pump Heat ExchangerAppliance Area High Water Temperature Limit ControlFlue Gas Passageways Cleaning Procedures Water Circulating PumpElectrical Burner Removal and CleaningHeat Exchanger Cleaning Combustion and Ventilation AirCombustion Air Fan Adjustment Adjusting Differential Air PressureFan Cleaning Set-Up ProcedureServicing Hot Surface Igniter and Ignition Module Adjustment ProcedureIgnition System Checkout Sequence of Operation Glossary Prepurge Wiring BOX Connections Wiring BOX Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B View Menu Item Menu Description