Commercial Pool Heaters
INSTALLATION Continued
TABLE-H
Outdoor Vent Cap Kits
Input | Outdoor Vent Kit* |
Btu/hr |
|
500,000 | ODK3075 |
650,000 | ODK3076 |
750,000 | ODK3076 |
990,000 | ODK3077 |
1,260,000 | ODK3078 |
1,440,000 | ODK3079 |
|
|
1,800,000 | ODK3080 |
2,070,000 | ODK3080 |
|
|
* These kits include an outdoor vent cap and gasket.
Flue gas condensate can freeze on exterior walls or on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition. Some discoloration to exterior building or pool heater surfaces can be expected. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.
The Outdoor Vent Cap Kit
The optional outdoor vent cap kit is available from the pool heater manufacturer. The outdoor cap part numbers are listed by input size. See
Install the outdoor vent cap on the rear of the pool heater, see Figure 27.
The air filter bracket will need to be rotated as shown in Figure 27 to allow proper access to the filters with the outdoor vent cap in place.
The 3-Way Valve Cover Installation
The
Combustion Air Fan Adjustment (for startup)
For startup, the combustion air fan shutter may require adjustment. Should the combustion air fan shutter need adjusting refer to the Adjusting Differential Air Pressure instructions located under the Cleaning and Maintenance section on page 49 of this manual.
Note: The manifold gas pressure can affect the differential air pressure. Once the combustion air fan shutter has been adjusted, confirm manifold gas pressure as described in the Gas Manifold Pressure Adjustment section on page 30 of this manual.
Figure 27 – Outdoor Vent Cap Installed on Rear of Pool Heater
CONNECTING TO GAS SUPPLY
Only supply gas type specified on the pool heater’s rating plate. This pool heater is orificed for operation up to 2000 feet altitude. If installing above 2000 feet elevation, consult the pool heater manufacturer.
INLET PRESSURE: Measure inlet pressure at the inlet pressure tap located upstream of the combination gas valve(s).
See
|
|
| |
| Inlet Pressure |
| |
| Max. | Min. | |
| Inlet Pressure | ||
|
|
| |
Nat. Gas | 10.5" w.c. | 4.5" w.c. |
|
LP Gas | 13" w.c. | 8" w.c. |
|
|
|
|
|
MANIFOLD PRESSURE: Measure manifold pressure at the pressure tap on the downstream side of the combination gas valves. The gas regulator on the pool heater’s combination gas valves is preset at the factory to supply proper manifold pressure for normal operation. See
If you must adjust regulator pressure, follow the instructions under Gas Manifold Pressure Adjustment, page 30. Do not increase regulator pressure beyond specified pressure setting.
Gas Pressure Test
1.Disconnect the unit from the gas supply piping system during any piping system pressure testing greater than 1/2 PSIG (3.5kPa).
26