OPERATION Continued
HOT SURFACE IGNITION SYSTEM
Hot Surface Igniter and Ignition Control Module
This unit has one ignition module and one hot surface igniter.
CAUTION: The igniter is extremely fragile, be very careful when removing. A faulty or damaged hot surface igniter MUST BE replaced with a Lochinvar PLT3400 igniter. DO NOT use general purpose field replacement igniters.
Figure 47 – Hot Surface Igniter
Figure 48 – Hot Surface Ignition Control Module
Hot Surface Ignition Control Module
Ignition Module Lockout Functions
The ignition module may lockout in either a
The ignition module will go into a soft lockout in conditions of low air, low voltage or low hot surface igniter current. A soft- lockout condition will operate the combustion air fans for the post purge cycle and then the ignition module will pause for approximately five minutes. At the end of this timed pause, the ignition module will attempt a new trial for ignition sequence. If the
Diagnostic Status Indication
The ignition module has an LED which indicates the status of the safety circuits. A remote Ignition Module Status indicating light is wired from the ignition module Status LED and mounted on the front control panel. The flashing operation of this light/LED indicates the diagnostic status of the ignition control module. The status LED, mounted on the ignition module, flashes a code sequence from the Ignition Module to indicate the status of the ignition process. See TABLE– N, on page 43 for the flashing diagnostic status codes as signaled by the ignition module.