Commercial Pool Heaters
INSTALLATION Continued
90° elbow. Subtract 2.5 feet (0.7m) of equivalent length for each 45° elbow.
Masonry Chimney Installation
Do not use a standard masonry chimney to directly vent the combustion products from this pool heater.
To use a masonry chimney, the chimney must use a sealed,
WARNING: Do not vent this pool heater into a masonry chimney without a sealed stainless steel liner system. Any breaks, leaks, or damage to the masonry flue/tile will allow the
IMPORTANT: Check with local code officials to determine code requirements or the advisability of using a masonry chimney with a sealed corrosion- resistant liner system.
Vertical DV Venting Termination
You must use the vent termination recommended by the vent manufacturer for vertical direct vent terminations. Follow all vertical venting termination information for clearances and location under Vertical Vent Termination Clearances and Location, page 10.
Horizontal DV Venting Termination
Horizontal venting (air inlet and flue outlet on the same wall) uses the pool heater’s internal combustion air blowers to force the flue products out of the
You must purchase a horizontal direct vent kit from the pool heater manufacturer to ensure proper operation. See
When installing the vent cap, the wall opening must provide an air space clearance of 2 inches (5.1cm) around the flue pipe. The diameter of the opening for installation of the sidewall cap will be 4 inches (10.2cm) larger (minimum) than the nominal diameter of the installed vent pipe to the horizontal vent cap.
Install the horizontal vent cap from the outside. Mount the vent cap to the wall using four screws or wall anchors. Seal under the screw heads with caulking. Install the sealed,
Horizontal Vent Termination Clearances and Location
Follow all sidewall venting termination information for clearances and location under Sidewall Vent Termination Clearances and Location, page 11.
Direct Vent Kits
Input | Horizontal | Vertical |
Btu/hr | Kit* | Kit* |
500,000 | DVK3004 | VDK3026 |
650,000 | DVK3005 | VDK3027 |
750,000 | DVK3005 | VDK3027 |
990,000 | DVK3000 | VDK3023 |
1,260,000 | DVK3001 | VDK3024 |
1,440,000 | DVK3001 | VDK3024 |
1,800,000 | DVK3002 | VDK3024 |
2,070,000 | DVK3002 | VDK3024 |
|
|
|
*The DVK kit includes a DV box adapter, air inlet cap, and a sidewall vent termination. The VDK kit includes a DV box adapter and an air inlet cap. See note on page 12 concerning DV box adapter.
Flue Pipe Materials
The following manufacturers supply flue materials suitable for these models. All materials are made with
Protech Systems, Inc.
Combustion Air Inlet Piping
The Direct Vent system requires the installation of a pipe to supply combustion air from the outdoors directly to the pool heater. The air inlet piping can either be brought in horizontally from a sidewall or vertically from the rooftop. Make sure the combustion air inlet is in the same pressure zone as the vent terminal.