Installation and Service Manual
Figure 14 – Sidewall Combustion Air Inlet
Figure 15 – Air Inlet Cap for Sidewall Termination
To prevent recirculation of flue products from an adjacent vent cap into the combustion air inlet, follow all applicable clearance requirements in the latest edition of the National Fuel Gas Code and/or
You must install the combustion air inlet cap at least one foot (0.30m) above ground level and above normal snow levels.
The point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (powered vent cap) if it is located within 10 feet (3.05m) of the flue outlet from the powered vent cap. Make sure to properly install the air inlet cap assembly on the air inlet pipe.
You must install the combustion air inlet cap and the powered vent cap on the same wall and in the same pressure zone. Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an
Vertical Rooftop Air Inlet
Use the vertical air inlet terminations available from the pool heater manufacturer, recommended and/or supplied by the vent manufacturer, or use two 90° elbows as described on page 24.
Figure 16 – Roof Top Combustion Air Inlet
Clearances
You must locate the air inlet termination elbow at least 12" (30cm) above the roof or above normal snow levels.
If the air inlet cap is within a 10 foot (3.05m) radius of the flue outlet, the point of termination for the combustion air inlet cap must be at least 3 feet (0.91m) below the point of flue gas termination (vent cap).
Do not install the combustion air inlet cap closer than 10 feet (3.05m) from an inside corner of an
Combined Air Inlet Points
The air inlet pipes from multiple pool heaters can be combined to a single common connection if the common air inlet pipe has a cross sectional area equal to or larger than the total area of all air inlet pipes connected to the common air inlet pipe.
Example: Two 10" air inlet pipes (78.5 in2 area each) have a total area of 157 in2 and will require a 15" (176.7 in2 area) common air inlet pipe.
The air inlet point for multiple pool heater air inlets must be provided with an exterior opening which has a free area equal to or greater than the total area of all air inlet pipes connected
13