Lochinvar GAS HEATER FOR COMMERICAL POOL APPLICATIONS Combination Gas Valves, Table-J

Page 28

Commercial Pool Heaters

INSTALLATION Continued

Figure 29 shows a typical pool heater gas train.

The manifold pressure is preset at the factory and adjustment is not usually required. If you must adjust regulator pressure, follow the instructions under Gas Manifold Pressure Adjustment, page 30.

Venting of Combination Gas Valves

The combination gas valve/regulator used on these pool heaters is equipped with an integral vent limiting orifice per ANSI Z21.78. The vent limiter ensures that the volume of gas emitted from the valve in the event of a failed gas diaphragm does not exceed the maximum safe leakage rate allowed by agency requirements. Combination gas valve/regulators equipped with integral vent limiters are not required to have vent or relief lines piped to the outdoors.

Figure 29 – Typical Pool Heater Gas Train Drawing

TABLE-J

Suggested Gas Pipe Size for Single Unit Installations

Btu/hr

 

Distance From Meter (in feet)

Input

0-50

51-100 101-200

201-300

301-500

500,000

 

1 1/2"

 

2"

 

2"

 

2 1/2"

1 1/4"

 

 

 

 

 

 

 

 

 

 

 

 

650,000

1 1/2"

2"

 

2"

 

2 1/2"

 

2 1/2"

 

 

 

 

 

 

 

 

 

750,000

1 1/2"

2"

 

2"

 

2 1/2"

 

3"

 

 

 

 

 

 

 

 

 

990,000

2"

2"

 

2 1/2"

 

2 1/2"

 

3"

 

 

 

 

 

 

 

 

 

1,260,000

2"

2 1/2"

 

2 1/2"

 

3"

 

3"

 

 

 

 

 

 

 

 

 

1,440,000

2 1/2"

2 1/2"

 

3"

 

3"

 

3 1/2"

 

 

 

 

 

 

 

 

 

1,800,000

2 1/2"

3"

 

3"

 

3 1/2"

 

3 1/2"

 

 

 

 

 

 

 

 

 

2,070,000

2 1/2"

3"

 

3"

 

3 1/2"

 

4"

 

 

 

 

 

 

 

 

 

Combination Gas Valves

These pool heaters fire in a single stage of operation.

Note: This pool heater incorporates a “soft start” feature which lights approximately half of the burners before lighting the remaining burners. Each combination valve consists of a gas regulator and two valve seats to meet the requirements for redundant gas valves. The valve has a gas control knob that must remain in the open position at all times when the pool heater is in service. The gas control valve has pressure taps located on the inlet and discharge sides of the valve. Manifold pressure is adjusted using the regulator located on the valve. A manifold gas pressure tap for each burner stick is located on the discharge side of the valve.

Checking Gas Supply Pressure

Use the following procedure to check gas supply pressure.

1.Turn the main power switch to the “OFF” position.

2.Turn gas valve knobs to the “OFF” position.

3.Shut off gas supply at the field-installed manual gas cock in the gas piping to the pool heater. If fuel supply is L.P. gas, shut off gas supply at the tank.

4.Remove the 1/8" hex plug, located on the “inlet” side of any gas valve. You may also use a tapping on the field- installed main manual gas cock or gas piping. Install a fitting in the inlet pressure tapping suitable to connect to a manometer or magnahelic gauge. Range of scale should be 14" w.c. or greater to check inlet pressure.

5.Turn on gas supply at the manual gas cock, turn on L.P. gas at the tank if required.

6.Turn the power switch to the “ON” position.

7.Turn the gas valve knobs to the “ON” position. Set the temperature control to call for heat. See Operating Temperature Control on page 40 for programming instructions.

8.Observe the gas supply pressure as all burners are firing. Ensure that inlet pressure is within the specified range. See Connecting To Gas Supply, page 26 for minimum and maximum gas supply pressures.

9.If gas pressure is out of range, contact gas utility, gas supplier, qualified installer or service agency to determine necessary steps to provide proper gas pressure to the pool heater.

10.If gas supply pressure is within normal range, turn the power switch to the “OFF” position.

11.Turn gas valve knobs to the “OFF” position.

12.Shut off gas supply at the manual gas cock in the gas piping to the pool heater. If fuel supply is L.P. gas, shut off gas supply at the tank.

28

Image 28
Contents GAS Heaters for Commercial Pool Applications Commercial Pool Heaters General Product Information UnpackingCommercial Pool Heaters Product Identification Clearances from Combustible Construction Base for Combustible FloorsFreeze Protection Combustion Air FilterInstallation Combustion Air OptionsExhaust Fans Combustion Air from Interior SpaceVenting Support General InformationVertical Vent Termination Clearances and Location Sidewall Vent Termination Clearances and Location Table BLength of Air Inlet Pipe Combustion Air Inlet PipingSidewall Air Inlet Vertical Rooftop Air Inlet Combined Air Inlet PointsConventional Negative Draft Venting Vent System OptionsNegative Draft Flue Outlet Piping Masonry Chimney InstallationsCommon Venting Systems Vertical DirectAire Venting Inspection of a Masonry ChimneySidewall Venting Vent KitsVenting of Flue Products Sidewall Venting Termination Sidewall FanSidewall Venting Without Fan Masonry Chimney Installation Horizontal DirectAire Venting TABLE-EDirect Venting Flue Pipe Materials Horizontal DV Venting TerminationCombustion Air Inlet Piping Air Inlet Piping Materials Length of Air Inlet PipeSealing Type-B Doublewall Vent Pipe or Galvanized Vent Pipe Combined Combustion Air Inlet Points Vertical Rooftop Air InletOutdoor Installation Venting Outdoor Vent/Air Inlet LocationCombustion Air Fan Adjustment for startup 3-Way Valve Cover InstallationGas Pressure Test Outdoor Vent Cap KitGas Piping Connecting Gas Piping to the Pool HeaterGas Train and Controls Combination Gas Valves Venting of Combination Gas ValvesChecking Gas Supply Pressure TABLE-JMultiple Unit Installations Gas Supply Pipe Sizing Table KGas Manifold Pressure Adjustment Measuring Net Manifold Gas PressureAuxiliary Mixed Water Limit Control Pumped Automatic BypassWay Valve Cover Heater is Within 15 Feet of Pool Piping Heaters are within 15 feet Perpendicular of Pool Piping Relief Valve Water Flow SwitchAutomatic Chlorinator and Chemical Feeders Service Indicator Option Pump Purge Delay OptionWay Automatic Bypass Valve Wiring Terminal Strip Connection Options TABLE-MOperation Lighting InstructionsTo Turn Off Gas To Pool Heater Pre-Start ChecklistStarting the Filter System Operation Programming Mode Error Messages Displayed by the Temperature ControllerDiagnostic Status Indication Hot Surface Igniter and Ignition Control ModuleHot Surface Ignition Control Module Ignition Module Lockout FunctionsTABLE-N Access to Internal Control PanelIgnition and Control Timings Water Chemistry TABLE-OTABLE-P Test Recommended LevelPipe Size Requirements Circulating PumpMinimum Pump Performance Heat ExchangerHigh Water Temperature Limit Control Flue Gas Passageways Cleaning ProceduresAppliance Area Water Circulating PumpBurner Removal and Cleaning Heat Exchanger CleaningElectrical Combustion and Ventilation AirAdjusting Differential Air Pressure Fan CleaningCombustion Air Fan Adjustment Set-Up ProcedureServicing Hot Surface Igniter and Ignition Module Adjustment ProcedureIgnition System Checkout Sequence of Operation Glossary Prepurge Wiring BOX Connections Wiring BOX Connections Ladder Diagram Control BOX Connections Commercial Pool Heaters Appendix a Appendix B View Menu Item Menu Description