Raypak 120 START-UP and Operation, Switching on the Appliance, Working the Boiler, Reset Function

Page 43

10 - START-UP AND OPERATION

XPak wall-mounted condensing boiler is designed for the production of heating and domestic hot water if a storage tank is connected.

The control panel contains the main boiler control and manage- ment functions.

1. SWITCHING ON THE APPLIANCE

Switch on the boiler as follows:

-Open the gas tap under the boiler by turning it counterclockwise (Fig. 46)

-Turn on the general switch of the system and then, after

lowering the flap, turn the function selector to summer ,

winter or winter tank temperature F (Fig. 54) depending on the chosen operating mode.

Pump cycle mode: when power is restored to the boiler and/ or the boiler is powered for the first time, the boiler will enter a 2- minute purge cycle whereby only the pump will run for 15-seconds then off for 15-seconds and will not “fire” until this period has elapsed. To interrupt the purge cycling remove the knob of the main selector switch and press the CO button (Fig. 59).

Off/reset - Select this position when the boiler needs to be reset or switched off.

Summer mode - The domestic hot water function provided by the water tank is activated. The display indicates the storage tank temperature (only with the external water tank connected with a sensor).

Winter mode - The boiler produces hot water for heating and, if connected to an external water tank, it provides domestic hot water. The display indicates the boiler flow temperature.

Winter mode tank temperature F - The boiler produces hot water for heating and, if connected to an external water tank with a sensor, it provides domestic hot water.The display indicates the storage tank temperature.

2.HOW TO READ THE DISPLAY TEMPERATURE ● (dot in the middle)= means hundred (Fig.43)

● (dot on RIGHT side)= means DHW mode (Fig. 44) example:

Fig. 43

 

 

 

 

 

 

Heating mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60°F

 

 

 

 

 

 

 

 

 

 

160°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 44

 

 

 

 

 

DHW mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40°F

140°F

NOTICE:

For temperature over 199°F (93°C) the display shows .

Adjusting heating water temperature

To adjust the heating water temperature turn the knob marked

(Fig. 50) clockwise to increase and counterclockwise to decrease.

When turning the knob, the required temperature automatically appears on the digital display.

NOTICE: Depending on the type of system, it is possible to pre-select the suitable temperature range:

-standard systems 104-176°F (40-80°C)

-floor systems 68-113°F (20-45°C).

For further details, consult the “Boiler configuration” (Fig. 61)

3.ADJUSTING HEATING WATER TEMPERATURE WITH AN OUTDOOR PROBE CONNECTED

When an outdoor probe is connected, the value of the delivery temperature is automatically chosen by the system which rapidly adjusts ambient temperature to the changes in outdoor tempe-

rature. To increase or decrease the temperature with respect to the value automatically calculated by the PCB, turn the heating water selector (Fig. 50) clockwise to increase and counterclockwise to decrease.

Adjustment settings range from comfort levels - 5 to + 5 which are indicated on the digital display when the knob is turned.

4.ADJUSTING DOMESTIC HOT WATER TEMPERATURE (IF A STORAGE TANK WITH SENSOR AND 3-WAY VALVE IS INSTALLED)

When turning the knob, the required temperature automatically appears on the digital display. The domestic hot water adjustment ranges lies between 95°F (35°C) and 140°F (60°C). When choosing the temperature, both for heating and domestic hot water, the display shows the value being selected. About 4 seconds after the selection has been made, the modification is recorded and the display returns to the delivery or domestic hot water temperature read by the probe. Priority is always given to DHW production.

The boiler setting depends from the jumper JP position (Fig. 63).

-CASE A (factory set) heating only + external water tank with thermostat adjustment inapplicable - jumper in position 3

-CASE B heating only + external water tank with sensor - to adjust the temperature of the domestic hot water in the water tank, turn the temperature selector clockwise to increase and counterclockwise to decrease - jumper in position 2.

5.WORKING THE BOILER

If a programmable timer or ambient thermostat are mounted, these must be switched on and adjusted to higher than ambient temperature in order to allow the boiler to start.

The boiler remains on standby until the burner ignites as a result of a demand for heat.The green indicator LED (B, Fig. 52), located on the left-hand side of the panel, lights up to indicate the flame is present. The boiler continues to work until the selected temperatures have been reached. It then returns to “stand-by” while displaying delivery temperature.

In the event of a starting or operating fault, the boiler performs a “SAFETY STOP”: the green indicator LED on the control panel goes out, a fault code flashes on the display (Fig. 53) and a red indicator LED (D) lights up in the event of a shutdown. To identify the fault codes and reset the boiler, consult the “Indicator LEDs and faults” section.

6. RESET FUNCTION

To reset the boiler, turned the function selector to (Fig. 54) then move it to the required position and check that the red indicator LED has gone out.

At this point, the boiler starts automatically if correct operating conditions have been restored; when the burner ignites, the green indicator led lights up and the digital display indicates the instantaneous operating temperature.

NOTICE: Simply turning the selector to does not reset the boiler.

If the boiler continues not to work, call your local Service Technician.

In normal operating conditions, when the function selector is turned to , the digital display indicates “- -” (Fig. 55) unless the anti-freeze phase (AF - Fig. 56) is in progress or the combustion analysis function is activated (CO - Fig. 58).

7. SWITCHING OFF

For short absences (weekends, brief journeys, etc.) turn the function selector to OFF/RESET.

As the boiler remains powered with the gas tap open, it is protected by the following systems:

-Freeze protection: Heating

The function starts if the temperature measured by the flow sensor falls below 43°F (6°C). In this mode, a heat demand is generated and the burner ignites at minimum power. This is maintained until the temperature of the water flow reaches 95°F (35°C).

43

Image 43
Contents Page About the XPak About these instructionsContents Following instructions must be observed PAY Attention to These TermsYou must also observe Tools, materials and additional equipment What to do if you smell gasObserve these instructions as general warnings Observe these instructions for space heating waterWater Time to Produce Serious General SafetyBefore Installation M E / T E M P E R a T U R E Relationships in ScaldsOperating Limits of the boiler Regulations and GuidelinesGeneral layout Fig IntroductionAB C DE Technical Data Max flues length de-rate less 2% Recommended Minimum Service ClearancesBoiler Dimensions And Weight XPakPrinciple Components Manual Handling Statement Mode of Operation AT RestXpak Internal Hydraulic Circuit FIG Mode of Operation Safety DevicesPiping Connections FIG Dimensions and Connections Fig Transporting the Boiler Boiler BOX Content Table Pos Parts Quantity PackagingPackaging and Transportation Scope of DeliveryPrepare Xpak Location InstallationPrepare Xpak Xpak Piping Pump Duty Procedure SummaryBoiler with DHW Tank Waterside Flow Primary CircuitKey for installation sample diagrams Xpak Installation DiagramsPage Page Equivalent length for pipe fittings in feet Length Gas Volume Capacity Pipe feet Ft 3/hMaking the GAS Connection Gas Pipe Capacity for different pipe sizesBoiler Template Fig All Air from Outdoor sealed combustion All Air from Inside the Building room airFlue GAS System Vent SystemsBoiler Supply Minimum Clearances from VENT/AIR Inlet Termination Installations1 Canadian Installations2Vertical Coaxial Sealed Combustion Operation TWO Pipes Single Wall Room AIR Dependent Operation Field supplied Stainless steel013102 Description Diagram Drawing TWO Pipes Single Wall = total intake length = Electrical Connections Connecting the Condensate Water DrainAppliance Terminal Block External WiringExternal Wiring Limitations Connecting ThermostatHigh Terminal Strip DetailsLow Remote Control Connection WAY Valve Wiring ConnectionOutdoor Sensor Connection Wiring Functional Diagram Are several steps involved in starting up the boiler START-UP ProcedureHeating System Freeze Protection When UsedCommissioning CHECK/CONTROL Water ChemistryInitial Flushing of the System Testing for GAS LeaksInitial Lighting and Ignition Safety Shutoff Device Test Check Thermostat CircuitsFinal Checks WarrantyInstructing the User START-UP and Operation Switching on the ApplianceReset Function Switching OFFGreen indicator LED Fig Indicator Leds and FaultsRed indicator LED Fig For alarm AL91 For AL41 faultsCHECKS, Adjustments and Fault Finding Installation Faults CHECKING/ADJUSTING the Boiler FAN SpeedsGAS Valve Minimum Pressure Setting External FaultsElectrical Checks Fault FindingReversed Polarity or Supply Fault Boiler ConfigurationType of Heat Request Standard Setting the Outdoor Reset Curve with Outdoor SensorProgrammable Timer DAY+NIGHT Selecting the offset heating curve Fig212 194 176 158 140 122 104 Code Cause Alarm Type Action Fault CodesGeneral Replacement of ComponentsComponent Removal Procedure Servicing InstructionsPrinted Circuit Board Fig Water Pressure Switch FigFlow Sensor Primary Thermistor Fig Return Sensor Return Thermistor FigMain Heat Exchanger Fig Blocked Flue Pressure SWITCH/IGNITION Transformer FigFlue FAN & Mixer Fig Burner FigFlue Collector and Flue Thermostat Removal Fig Condensate Trap Removal FigGAS Supply GAS Supply InstallationLPG Instructions Propane GASTechnical Data LPG Sequence of the Ignition System Exploded Diagrams 56a Xpak Drawing Call OUT Description Important Instructions for the Commonwealth of Massachusetts Applicable Warranty Periods Limited WarrantyHOW to Make Warranty Claim START-UP Checklist for FAN-ASSISTED Raypak Products Your XPak serial number For future reference

120, 85 specifications

The Raypak 120,85 is a prominent model in the realm of pool and spa heating solutions, designed to deliver unmatched efficiency and performance. Renowned for its robust features and innovative technologies, the Raypak 120,85 stands out as a reliable choice for homeowners seeking to maintain the perfect water temperature in their pools and spas.

One of the primary characteristics of the Raypak 120,85 is its impressive heating capacity. With a total output of 120,000 BTUs, this heater quickly and efficiently warms up water, ensuring that users can enjoy comfortable swimming conditions regardless of the outdoor temperature. The 85 indicates its ability to deliver consistent performance even in cooler climates, making it an adaptable option for various geographical locations.

The Raypak 120,85 is equipped with a state-of-the-art, copper fin tube heat exchanger, which provides superior heat transfer efficiency. This technology enhances the heater's ability to warm water rapidly while maintaining energy efficiency. Additionally, the copper material is known for its durability and resistance to corrosion, ensuring a long lifespan for the heat exchanger.

Another key feature of the Raypak 120,85 is its electronic ignition system. This innovation eliminates the need for a standing pilot light, which not only saves energy but also enhances safety by reducing the risk of gas leaks associated with traditional ignition systems. The electronic ignition provides precise control, ensuring a reliable start each time.

The Raypak 120,85 also boasts a digital display control panel, allowing users to easily monitor and adjust the water temperature settings. This intuitive interface provides accurate readings and simplifies the operation, making it accessible for all users, regardless of their technical expertise.

Furthermore, this heater is designed with a compact footprint, making it suitable for a variety of installation spaces, whether it’s in a pool equipment area or near a spa. Its robust build quality and weather-resistant design ensure that it can withstand the elements, making it a durable and long-lasting investment.

In summary, the Raypak 120,85 combines advanced heating technology, robust construction, and user-friendly features. With its high BTU output, efficient heat exchanger, electronic ignition, and digital controls, it represents a top-tier option for anyone seeking reliable and effective heating solutions for pools and spas. Whether for leisure or relaxation, the Raypak 120,85 promises to deliver an optimal swimming experience, season after season.