Raypak 85, 120 manual Making the GAS Connection, Gas Pipe Capacity for different pipe sizes

Page 22

MAKING THE GAS CONNECTION

DANGER: Only carry out work on gas conduits and fittings if you are licensed for such work.

-Determine proper size gas pipe for the installation using Table 3 and Table 4. Do not forget the pipe fitting losses and observe proper size of the fittings.

-Install the furnished 3/4” female gas cock on the gas connection (3/4” male on the boiler) (Fig. 13).

-Connect the gas pipe to the gas cock so that it is free from any strain.

CAUTION: The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).

Fig. 13

 

 

A

A- Manual main gas shutoff

B

C

valve (supplied)

 

B- Coupling (field supplied)

 

C- To gas supply

 

NOTICE: When installing the gas supply connection, it must comply with local regulations or, if such regulations do not exist, with the National Fuel Gas Code, ANSI Z 223.1.

In Canada, the gas supply connection must comply with local regulations or, if such regulations do not exist, with CAN/CSA B149, Natural Gas and Propane Installation Code. A sediment trap must be provided upstream of the gas controls.

Gas Pipe Capacity for different pipe sizes

Tab. 3

Length of

 

Gas Volume Capacity

 

pipe (feet)

 

 

(ft3/h)*

 

 

 

3/4”

 

1”

 

1 1/4”

1 1/2”

10

278

 

520

 

1,060

1,600

20

190

 

350

 

730

1,100

30

152

 

285

 

590

890

40

130

 

245

 

500

760

50

115

 

215

 

440

670

75

93

 

175

 

360

545

100

79

 

160

 

305

480

150

64

 

120

 

250

380

*Maximum pipe capacity in ft3/hr, based on a specific gravity of 60 (42 mbar) and a inlet gas pressure of 14 inches W.C. (35 mbar) or less and a pressure drop of 0.3 inches W.C. (20 mbar)

Equivalent length for pipe fittings in feet

Tab. 4

Steel pipe

Equivalent length for Pipe Fittings in feet

diameter

 

 

 

 

 

Type of pipe fitting

 

in inches

90° Elbow

Tee

Gate valve

 

Gas cocks

 

 

 

(flow thru

 

 

 

 

 

 

branch)

 

 

 

 

 

 

Equivalent

length in feet

 

 

3/4

 

2.1

4.1

0.5

 

1.25

1

 

2.6

5.2

0.6

 

1.60

1 1/4

 

3.5

6.9

0.8

 

2.15

1 1/2

 

4.0

8.0

0.9

 

2.50

NOTICE: The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).

Open

position

Fig. 14

Closed position

22

Image 22
Contents Page About these instructions About the XPakContents Following instructions must be observed PAY Attention to These TermsYou must also observe Observe these instructions for space heating water What to do if you smell gasObserve these instructions as general warnings Tools, materials and additional equipmentM E / T E M P E R a T U R E Relationships in Scalds General SafetyBefore Installation Water Time to Produce SeriousRegulations and Guidelines Operating Limits of the boilerIntroduction General layout FigAB C DE Technical Data XPak Recommended Minimum Service ClearancesBoiler Dimensions And Weight Max flues length de-rate less 2%Safety Devices Manual Handling Statement Mode of Operation AT RestXpak Internal Hydraulic Circuit FIG Mode of Operation Principle ComponentsPiping Connections FIG Dimensions and Connections Fig Scope of Delivery Boiler BOX Content Table Pos Parts Quantity PackagingPackaging and Transportation Transporting the BoilerPrepare Xpak Location InstallationPrepare Xpak Xpak Piping Waterside Flow Primary Circuit Procedure SummaryBoiler with DHW Tank Pump DutyXpak Installation Diagrams Key for installation sample diagramsPage Page Gas Pipe Capacity for different pipe sizes Length Gas Volume Capacity Pipe feet Ft 3/hMaking the GAS Connection Equivalent length for pipe fittings in feetBoiler Template Fig All Air from Inside the Building room air All Air from Outdoor sealed combustionFlue GAS System Vent SystemsBoiler Supply Installations1 Canadian Installations2 Minimum Clearances from VENT/AIR Inlet TerminationVertical Coaxial Sealed Combustion Operation TWO Pipes Single Wall Room AIR Dependent Operation Field supplied Stainless steel013102 Description Diagram Drawing TWO Pipes Single Wall = total intake length = Connecting the Condensate Water Drain Electrical ConnectionsConnecting Thermostat External WiringExternal Wiring Limitations Appliance Terminal BlockHigh Terminal Strip DetailsLow Remote Control Connection WAY Valve Wiring ConnectionOutdoor Sensor Connection Wiring Functional Diagram START-UP Procedure Are several steps involved in starting up the boilerCHECK/CONTROL Water Chemistry Freeze Protection When UsedCommissioning Heating SystemCheck Thermostat Circuits Testing for GAS LeaksInitial Lighting and Ignition Safety Shutoff Device Test Initial Flushing of the SystemFinal Checks WarrantyInstructing the User Switching OFF Switching on the ApplianceReset Function START-UP and OperationGreen indicator LED Fig Indicator Leds and FaultsRed indicator LED Fig For AL41 faults For alarm AL91CHECKS, Adjustments and Fault Finding External Faults CHECKING/ADJUSTING the Boiler FAN SpeedsGAS Valve Minimum Pressure Setting Installation FaultsBoiler Configuration Fault FindingReversed Polarity or Supply Fault Electrical ChecksSelecting the offset heating curve Fig Setting the Outdoor Reset Curve with Outdoor SensorProgrammable Timer DAY+NIGHT Type of Heat Request Standard212 194 176 158 140 122 104 Fault Codes Code Cause Alarm Type ActionServicing Instructions Replacement of ComponentsComponent Removal Procedure GeneralReturn Sensor Return Thermistor Fig Water Pressure Switch FigFlow Sensor Primary Thermistor Fig Printed Circuit Board FigBurner Fig Blocked Flue Pressure SWITCH/IGNITION Transformer FigFlue FAN & Mixer Fig Main Heat Exchanger FigCondensate Trap Removal Fig Flue Collector and Flue Thermostat Removal FigPropane GAS GAS Supply InstallationLPG Instructions GAS SupplyTechnical Data LPG Sequence of the Ignition System Exploded Diagrams 56a Xpak Drawing Call OUT Description Important Instructions for the Commonwealth of Massachusetts Limited Warranty Applicable Warranty PeriodsHOW to Make Warranty Claim START-UP Checklist for FAN-ASSISTED Raypak Products Your XPak serial number For future reference

120, 85 specifications

The Raypak 120,85 is a prominent model in the realm of pool and spa heating solutions, designed to deliver unmatched efficiency and performance. Renowned for its robust features and innovative technologies, the Raypak 120,85 stands out as a reliable choice for homeowners seeking to maintain the perfect water temperature in their pools and spas.

One of the primary characteristics of the Raypak 120,85 is its impressive heating capacity. With a total output of 120,000 BTUs, this heater quickly and efficiently warms up water, ensuring that users can enjoy comfortable swimming conditions regardless of the outdoor temperature. The 85 indicates its ability to deliver consistent performance even in cooler climates, making it an adaptable option for various geographical locations.

The Raypak 120,85 is equipped with a state-of-the-art, copper fin tube heat exchanger, which provides superior heat transfer efficiency. This technology enhances the heater's ability to warm water rapidly while maintaining energy efficiency. Additionally, the copper material is known for its durability and resistance to corrosion, ensuring a long lifespan for the heat exchanger.

Another key feature of the Raypak 120,85 is its electronic ignition system. This innovation eliminates the need for a standing pilot light, which not only saves energy but also enhances safety by reducing the risk of gas leaks associated with traditional ignition systems. The electronic ignition provides precise control, ensuring a reliable start each time.

The Raypak 120,85 also boasts a digital display control panel, allowing users to easily monitor and adjust the water temperature settings. This intuitive interface provides accurate readings and simplifies the operation, making it accessible for all users, regardless of their technical expertise.

Furthermore, this heater is designed with a compact footprint, making it suitable for a variety of installation spaces, whether it’s in a pool equipment area or near a spa. Its robust build quality and weather-resistant design ensure that it can withstand the elements, making it a durable and long-lasting investment.

In summary, the Raypak 120,85 combines advanced heating technology, robust construction, and user-friendly features. With its high BTU output, efficient heat exchanger, electronic ignition, and digital controls, it represents a top-tier option for anyone seeking reliable and effective heating solutions for pools and spas. Whether for leisure or relaxation, the Raypak 120,85 promises to deliver an optimal swimming experience, season after season.