CONNECTING THE CONDENSATE WATER DRAIN

Install the condensate drain flexible pipe (Ø 0.825” - 21mm female flexible rubber connection) with a suitable gradient (min. 2.5%).

Discharge condensate from the boiler into the drainage system, either directly or (if required) via a neutralization unit (not supplied).

1. CONDENSATE CONNECTION

The condensate drain of the boiler is equipped with a built-in siphon trap in order to keep flue gases from being discharged via the condensate drain.

The condensate formed both in the condensing boiler and in the flue gas pipe must be discharged into the public sewage system in accordance with all applicable local regulations.

The condensate produced by a gas-fired heating system has a pH value between 3 and 4.

Some local codes may require the use of a separate neutralization unit to treat the aggressive and corrosive condensate.

Raypak offers a Condensate Neutralizer Kit (Z-12 option) for use when managing the condensate is desired or required. Order part number 013141.

With a neutralization unit installed, all condensate from the boiler and the flue gas pipe enters into the neutralization unit where it is treated and released into the public sewage system with a safe pH value of above 6.5.

The use of neutralization granulate (performing the neutralizing process) is dependent on the operation of the heating system. To determine the required refill amount, check granulate level several times during the first year of operation. In some cases one granulate fill may last an entire year.

The condensate discharge outlet to the drainage system connection must be clearly visible. It must be installed with a suitable gradient and provided with a stench trap.

If the condensate outlet of the boiler is lower than the drain, a condensate pump must be used (see electrical wiring to loch out the boiler in the case of failure of the condensate pump - alarm 21). Only corrosion-resistant materials may be used for condensate drainage purposes (e.g. braided hose). Do not use galvanized materials or materials containing copper for piping, couplings etc. Please note that other requirements may apply depending on local regulations and/or project-specific details.

It is advisable to contact your local waterworks office (authority responsible for waste water regulations) well before commencing with the installation of the neutralization unit in order to establish details of local regulations that apply.

NOTICE: Pipe ventilation must take place between the siphon trap and the neutralization unit (if applicable).

7 - ELECTRICAL CONNECTIONS

Devices such as outdoor sensor, 3-way valve, tank sensor, tank thermostat, remote controls are all connected to the external connection board.

The electrical connections to the boiler must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI/NFPA-70.

Installations should also conform with CSA C22.1 Canadian Electrical Code Part 1 if installed in Canada.

1. EXTERNAL CONNECTION BOARD CONNECTIONS

A qualified electrician should connect the electrical supply to the appliance. If controls – external to the appliance – are required, a competent person must undertake the design of any external electrical circuits. ANY EXTERNAL CONTROL OR WIRING MUST BE SERVED FROM THE SAME ISOLATOR AS THAT OF THE APPLIANCE. Wiring to the appliance must be rated for operation in contact with surfaces up to 194°F (90°C).

WARNING: ELECTRICAL SHOCK HAZARD — For your safety, turn off electrical power supply at service entrance panel before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.

AVERTISSEMENT: RISQUE DE CHOC ÉLECTRIQUE — Pour votre sécurité, coupez l'alimentation électrique au niveau du tableau de distribution avant d'effectuer tout raccordement électrique afin d'éviter un risque éventuel de choc électrique. La non-observation du dernier point peut provoquer de graves blessures ou la mort.

NOTICE: Wiring must be N.E.C. Class 1. If original wiring as supplied with heater must be replaced, use only TEW 221°F (105 °C) wire or equivalent. Heater must be electrically grounded as required by National Electrical Code ANSI/ NFPA 70 — latest edition.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

Verify proper operation after servicing.

2. ELECTRICAL SUPPLY

The boiler requires a 120V 60Hz power supply. Ensure the electrical supply is properly polarized.

The boiler must be grounded.

There must only be one common isolator, providing complete electrical isolation for the boiler and any external controls using PVC insulated cable 18 AWG x3C 105 °C /221°F.

All wiring must be installed in accordance with requirements of National Electrical Code and any additional national, state, or local code requirements having jurisdiction. All wiring must be N.E.C. Class 1. The boiler must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA No. 70-latest edition.

In Canada, installation must conform to CSA C22.1 Canadian Electrical Code Part 1 and any local codes.

3. FIELD WIRING

The electrical junction box has a 24 volt terminal compartment and 120 volt terminal compartment. Each terminal connection is clearly marked to ensure correct installation.

Fig. 33

B

 

34

 

Optional devices (24V) terminal block

Fig. 34

Electrical supply (120V)

terminal block

Image 34
Contents Page About these instructions About the XPakContents Following instructions must be observed PAY Attention to These TermsYou must also observe Observe these instructions for space heating water What to do if you smell gasObserve these instructions as general warnings Tools, materials and additional equipmentM E / T E M P E R a T U R E Relationships in Scalds General SafetyBefore Installation Water Time to Produce SeriousRegulations and Guidelines Operating Limits of the boilerIntroduction General layout FigAB C DE Technical Data XPak Recommended Minimum Service ClearancesBoiler Dimensions And Weight Max flues length de-rate less 2%Safety Devices Manual Handling Statement Mode of Operation AT RestXpak Internal Hydraulic Circuit FIG Mode of Operation Principle ComponentsPiping Connections FIG Dimensions and Connections Fig Scope of Delivery Boiler BOX Content Table Pos Parts Quantity PackagingPackaging and Transportation Transporting the BoilerPrepare Xpak Location InstallationPrepare Xpak Xpak Piping Waterside Flow Primary Circuit Procedure SummaryBoiler with DHW Tank Pump DutyXpak Installation Diagrams Key for installation sample diagramsPage Page Gas Pipe Capacity for different pipe sizes Length Gas Volume Capacity Pipe feet Ft 3/hMaking the GAS Connection Equivalent length for pipe fittings in feetBoiler Template Fig All Air from Inside the Building room air All Air from Outdoor sealed combustionFlue GAS System Vent SystemsBoiler Supply Installations1 Canadian Installations2 Minimum Clearances from VENT/AIR Inlet TerminationVertical Coaxial Sealed Combustion Operation TWO Pipes Single Wall Room AIR Dependent Operation Field supplied Stainless steel013102 Description Diagram Drawing TWO Pipes Single Wall = total intake length = Connecting the Condensate Water Drain Electrical ConnectionsConnecting Thermostat External WiringExternal Wiring Limitations Appliance Terminal BlockHigh Terminal Strip DetailsLow Remote Control Connection WAY Valve Wiring ConnectionOutdoor Sensor Connection Wiring Functional Diagram START-UP Procedure Are several steps involved in starting up the boilerCHECK/CONTROL Water Chemistry Freeze Protection When UsedCommissioning Heating SystemCheck Thermostat Circuits Testing for GAS LeaksInitial Lighting and Ignition Safety Shutoff Device Test Initial Flushing of the SystemFinal Checks WarrantyInstructing the User Switching OFF Switching on the ApplianceReset Function START-UP and OperationGreen indicator LED Fig Indicator Leds and FaultsRed indicator LED Fig For AL41 faults For alarm AL91CHECKS, Adjustments and Fault Finding External Faults CHECKING/ADJUSTING the Boiler FAN SpeedsGAS Valve Minimum Pressure Setting Installation FaultsBoiler Configuration Fault FindingReversed Polarity or Supply Fault Electrical ChecksSelecting the offset heating curve Fig Setting the Outdoor Reset Curve with Outdoor SensorProgrammable Timer DAY+NIGHT Type of Heat Request Standard212 194 176 158 140 122 104 Fault Codes Code Cause Alarm Type ActionServicing Instructions Replacement of ComponentsComponent Removal Procedure GeneralReturn Sensor Return Thermistor Fig Water Pressure Switch FigFlow Sensor Primary Thermistor Fig Printed Circuit Board FigBurner Fig Blocked Flue Pressure SWITCH/IGNITION Transformer FigFlue FAN & Mixer Fig Main Heat Exchanger FigCondensate Trap Removal Fig Flue Collector and Flue Thermostat Removal FigPropane GAS GAS Supply InstallationLPG Instructions GAS SupplyTechnical Data LPG Sequence of the Ignition System Exploded Diagrams 56a Xpak Drawing Call OUT Description Important Instructions for the Commonwealth of Massachusetts Limited Warranty Applicable Warranty PeriodsHOW to Make Warranty Claim START-UP Checklist for FAN-ASSISTED Raypak Products Your XPak serial number For future reference

120, 85 specifications

The Raypak 120,85 is a prominent model in the realm of pool and spa heating solutions, designed to deliver unmatched efficiency and performance. Renowned for its robust features and innovative technologies, the Raypak 120,85 stands out as a reliable choice for homeowners seeking to maintain the perfect water temperature in their pools and spas.

One of the primary characteristics of the Raypak 120,85 is its impressive heating capacity. With a total output of 120,000 BTUs, this heater quickly and efficiently warms up water, ensuring that users can enjoy comfortable swimming conditions regardless of the outdoor temperature. The 85 indicates its ability to deliver consistent performance even in cooler climates, making it an adaptable option for various geographical locations.

The Raypak 120,85 is equipped with a state-of-the-art, copper fin tube heat exchanger, which provides superior heat transfer efficiency. This technology enhances the heater's ability to warm water rapidly while maintaining energy efficiency. Additionally, the copper material is known for its durability and resistance to corrosion, ensuring a long lifespan for the heat exchanger.

Another key feature of the Raypak 120,85 is its electronic ignition system. This innovation eliminates the need for a standing pilot light, which not only saves energy but also enhances safety by reducing the risk of gas leaks associated with traditional ignition systems. The electronic ignition provides precise control, ensuring a reliable start each time.

The Raypak 120,85 also boasts a digital display control panel, allowing users to easily monitor and adjust the water temperature settings. This intuitive interface provides accurate readings and simplifies the operation, making it accessible for all users, regardless of their technical expertise.

Furthermore, this heater is designed with a compact footprint, making it suitable for a variety of installation spaces, whether it’s in a pool equipment area or near a spa. Its robust build quality and weather-resistant design ensure that it can withstand the elements, making it a durable and long-lasting investment.

In summary, the Raypak 120,85 combines advanced heating technology, robust construction, and user-friendly features. With its high BTU output, efficient heat exchanger, electronic ignition, and digital controls, it represents a top-tier option for anyone seeking reliable and effective heating solutions for pools and spas. Whether for leisure or relaxation, the Raypak 120,85 promises to deliver an optimal swimming experience, season after season.