Raypak 85, 120 Boiler with DHW Tank, Waterside Flow Primary Circuit, Pump Duty, Procedure Summary

Page 18

8. BOILER WITH DHW TANK

-Connect the external hot-water tank according to the Installation instructions of the hot-water tank and fittings concerned.

Domestic Hot Water Production via DHW Storage Tank XPak boilers can be used in conjunction with the stand-alone DHW storage tanks.

The boiler can control the DHW tank temperature directly from the boiler control panel. In case a tank sensor is installed (see boiler configuration jumpers Fig. 61) adjust the tank temperature via the DHW selector. The display shows the tank temperature if main selector in proper position.

Boiler can accept also a DHW tank controlled by a thermostat (see boiler configuration jumpers Fig. 61), in this case the DHW set point can not be adjusted on the control panel but only on the tank thermostat (field supplied).

Both cases the supplied water temperature to the tank is 176°F (80°C) and it goes ahead with priority over heating until the tank request is satisfied (either the sensor or the termostat open).

The boiler can control a 3-way valve directly from the boiler control panel (see 3-way installations Fig. 38).

Refer to electrical connections for 3-way valve installation. Size and select the DHW storage tank based on the forecast DHW consumption of the building in question.

If different method of DHW production are used, the boiler flow temperature is set as heating mode (see boiler configuration jumpers Fig. 61).

9. WATERSIDE FLOW (PRIMARY CIRCUIT)

The boiler is designed only for closed loop, forced circulation hot water heating systems.

XPak is equipped with an internal 3 speed pump.

PUMP DUTY

Fig. 6 below shows the flow-rate available – after allowing for pressure loss through the appliance – for system requirements. When using this graph, apply only the pressure loss of the system. The graph is based on a 36°F (20°C) temperature differential.

CAUTION: The XPak should not be operated as a potable Hot Water Boiler. The XPak should not be operated in a open system.

10. PROCEDURE SUMMARY

1.Connect the system return marked “In”.

2.Connect the system supply marked “Out”.

3.Install a Back Flow preventor on the Cold Feed Make-Up Water line.

4.Install a Pressure Reducing Valve if required on the Cold Feed Make-Up Water line, 15 PSI (1 bar) nominal on the system return. Check Pressure Gauge which should read minimum pressure of 12 PSI (0.8 bar)

5.Install an Expansion Tank on the system supply. Consult the tank manufacturer’s instruction for specific information relating to expansion tank installation. Size the expansion tank for the

required system volume and capacity, no valve is to be placed between the boiler and the expansion tank.

6.Install an Air Elimination Device on the system supply if required, the boiler has two auto air vents built in.

7.Install a drain valve at the lowest point of the system. Note: The XPak has a proper internal drain valve. (see Fig. 42a)

8.The Safety Relief Valve is installed at the factory. Pipe the discharge of the safety relief valve to prevent injury in the event of pressure relief. Pipe the discharge to a maximum of 6” (152 mm) above the floor to a drain. Provide piping that is the same size as the safety relief valve outlet. Never block the outlet of a safety relief valve.

11. FILL AND PURGE HEATING SYSTEM

CAUTION: For installation that incorporates standing Iron Radiation and systems with manual vents at the high points. Follow above section and starting with the nearest manual air vent, open vent until water flows out, then close vent. Repeat procedure, working your way toward furthest air vent. It may be necessary to install a basket strainer in an older system where larger amounts of sediment may be present. Annual cleaning of the strainer may be necessary.

WARNING: Use only inhibited propylene glycol solutions which are specially formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems. Glycol mixtures should not exceed 40%.

1.Glycol in hydronic applications which is specially formulated for this purpose includes inhibitors that prevent the glycol from attacking metallic system components. Make certain that the system fluid is checked for the correct glycol concentration and inhibitor level.

2.The glycol solution should be tested at least once a year and as recommended by the glycol manufacturer.

3.Anti-freeze solutions expand more than water. Allowances must be made for this expansion in the system design.

CAUTION: It is highly recommended that you carefully follow the glycol manufacturer’s recommended concentrations, expansion requirements and maintenance recommendations (pH additive breakdown, inhibitor reduction, etc.). You must carefully calculate the additional friction loss in the system as well as the reduction in heat transfer co-efficients; pH must be maintained between 6-8.

 

16

 

 

 

 

 

XPak 85

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

XPak 120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

3rd

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

3rd

 

 

 

 

 

 

(ftwc)

 

 

 

 

 

 

 

 

 

 

 

speed

 

 

 

 

(ftwc)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

2nd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

head

9

 

 

 

 

 

 

speed

 

 

 

 

 

 

 

 

head

9

 

 

 

 

 

 

speed

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st

 

 

 

 

 

 

 

 

 

 

 

Residual

6

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

Residual

6

 

 

 

speed

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

20

41

61

81

102

122

142

163

183

203

224

244

264

285

305

 

0

20

41

61

81

102

122

142

163

183

203

224

244

264

285

305

 

 

 

 

 

 

Flow rate (gph)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flow rate (gph)

 

 

 

 

 

Fig. 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 18
Contents Page About these instructions About the XPakContents PAY Attention to These Terms Following instructions must be observedYou must also observe Observe these instructions for space heating water What to do if you smell gasObserve these instructions as general warnings Tools, materials and additional equipmentM E / T E M P E R a T U R E Relationships in Scalds General SafetyBefore Installation Water Time to Produce SeriousRegulations and Guidelines Operating Limits of the boilerIntroduction General layout FigAB C DE Technical Data XPak Recommended Minimum Service ClearancesBoiler Dimensions And Weight Max flues length de-rate less 2%Safety Devices Manual Handling Statement Mode of Operation AT RestXpak Internal Hydraulic Circuit FIG Mode of Operation Principle ComponentsPiping Connections FIG Dimensions and Connections Fig Scope of Delivery Boiler BOX Content Table Pos Parts Quantity PackagingPackaging and Transportation Transporting the BoilerInstallation Prepare Xpak LocationPrepare Xpak Xpak Piping Waterside Flow Primary Circuit Procedure SummaryBoiler with DHW Tank Pump DutyXpak Installation Diagrams Key for installation sample diagramsPage Page Gas Pipe Capacity for different pipe sizes Length Gas Volume Capacity Pipe feet Ft 3/hMaking the GAS Connection Equivalent length for pipe fittings in feetBoiler Template Fig All Air from Inside the Building room air All Air from Outdoor sealed combustionVent Systems Flue GAS SystemBoiler Supply Installations1 Canadian Installations2 Minimum Clearances from VENT/AIR Inlet TerminationVertical Coaxial Sealed Combustion Operation TWO Pipes Single Wall Room AIR Dependent Operation Stainless steel Field supplied013102 Description Diagram Drawing TWO Pipes Single Wall = total intake length = Connecting the Condensate Water Drain Electrical ConnectionsConnecting Thermostat External WiringExternal Wiring Limitations Appliance Terminal BlockTerminal Strip Details HighLow WAY Valve Wiring Connection Remote Control ConnectionOutdoor Sensor Connection Wiring Functional Diagram START-UP Procedure Are several steps involved in starting up the boilerCHECK/CONTROL Water Chemistry Freeze Protection When UsedCommissioning Heating SystemCheck Thermostat Circuits Testing for GAS LeaksInitial Lighting and Ignition Safety Shutoff Device Test Initial Flushing of the SystemWarranty Final ChecksInstructing the User Switching OFF Switching on the ApplianceReset Function START-UP and OperationIndicator Leds and Faults Green indicator LED FigRed indicator LED Fig For AL41 faults For alarm AL91CHECKS, Adjustments and Fault Finding External Faults CHECKING/ADJUSTING the Boiler FAN SpeedsGAS Valve Minimum Pressure Setting Installation FaultsBoiler Configuration Fault FindingReversed Polarity or Supply Fault Electrical ChecksSelecting the offset heating curve Fig Setting the Outdoor Reset Curve with Outdoor SensorProgrammable Timer DAY+NIGHT Type of Heat Request Standard212 194 176 158 140 122 104 Fault Codes Code Cause Alarm Type ActionServicing Instructions Replacement of ComponentsComponent Removal Procedure GeneralReturn Sensor Return Thermistor Fig Water Pressure Switch FigFlow Sensor Primary Thermistor Fig Printed Circuit Board FigBurner Fig Blocked Flue Pressure SWITCH/IGNITION Transformer FigFlue FAN & Mixer Fig Main Heat Exchanger FigCondensate Trap Removal Fig Flue Collector and Flue Thermostat Removal FigPropane GAS GAS Supply InstallationLPG Instructions GAS SupplyTechnical Data LPG Sequence of the Ignition System Exploded Diagrams 56a Xpak Drawing Call OUT Description Important Instructions for the Commonwealth of Massachusetts Limited Warranty Applicable Warranty PeriodsHOW to Make Warranty Claim START-UP Checklist for FAN-ASSISTED Raypak Products Your XPak serial number For future reference

120, 85 specifications

The Raypak 120,85 is a prominent model in the realm of pool and spa heating solutions, designed to deliver unmatched efficiency and performance. Renowned for its robust features and innovative technologies, the Raypak 120,85 stands out as a reliable choice for homeowners seeking to maintain the perfect water temperature in their pools and spas.

One of the primary characteristics of the Raypak 120,85 is its impressive heating capacity. With a total output of 120,000 BTUs, this heater quickly and efficiently warms up water, ensuring that users can enjoy comfortable swimming conditions regardless of the outdoor temperature. The 85 indicates its ability to deliver consistent performance even in cooler climates, making it an adaptable option for various geographical locations.

The Raypak 120,85 is equipped with a state-of-the-art, copper fin tube heat exchanger, which provides superior heat transfer efficiency. This technology enhances the heater's ability to warm water rapidly while maintaining energy efficiency. Additionally, the copper material is known for its durability and resistance to corrosion, ensuring a long lifespan for the heat exchanger.

Another key feature of the Raypak 120,85 is its electronic ignition system. This innovation eliminates the need for a standing pilot light, which not only saves energy but also enhances safety by reducing the risk of gas leaks associated with traditional ignition systems. The electronic ignition provides precise control, ensuring a reliable start each time.

The Raypak 120,85 also boasts a digital display control panel, allowing users to easily monitor and adjust the water temperature settings. This intuitive interface provides accurate readings and simplifies the operation, making it accessible for all users, regardless of their technical expertise.

Furthermore, this heater is designed with a compact footprint, making it suitable for a variety of installation spaces, whether it’s in a pool equipment area or near a spa. Its robust build quality and weather-resistant design ensure that it can withstand the elements, making it a durable and long-lasting investment.

In summary, the Raypak 120,85 combines advanced heating technology, robust construction, and user-friendly features. With its high BTU output, efficient heat exchanger, electronic ignition, and digital controls, it represents a top-tier option for anyone seeking reliable and effective heating solutions for pools and spas. Whether for leisure or relaxation, the Raypak 120,85 promises to deliver an optimal swimming experience, season after season.