Raypak 120, 85 manual Technical Data LPG

Page 57

TECHNICAL DATA - LPG

Gas pressure

 

XPak 85

XPak 120

Input - (0 - 2000 ft / 0 - 610 m)

Btu/hr

25,600 - 87,000

27,300 - 119,500

 

kW

7.5 - 25.5

8.0 - 35.0

Input - (2000 - 4500 ft / 610 - 1375 m)

Btu/hr

25,600 - 82,900

27,300 - 114,300

 

kW

7.5 - 24.3

8.0 - 33.5

Gas supply pressure LPG

in w. c.

11

11

 

kPa

2.75

2.75

Min. gas supply pressure LPG

in w. c.

8

8

 

kPa

1.99

1.99

Max. gas supply pressure LPG

in w. c.

13

13

 

kPa

3.24

3.24

Burner pressure (max-min)

in w. c.

1.92-0.24

2.00-0.16

 

kPa

0.48-0.06

0.50-0.04

 

 

 

 

Rate

 

 

 

Gas Rate max LPG

lbs/hr

4.02

5.55

 

kg/hr

1.82

2.52

Gas Rate min LPG

lbs/hr

1.20

1.28

 

kg/hr

0.54

0.58

Emissions

 

 

 

CO2 setting

%

10.0%

10.0%

NOx @ max

ppm

< 20

< 20

NOx @ min

ppm

< 15

< 20

CO @ max without air

ppm

< 200

< 200

CO @ min without air

ppm

< 40

< 35

Injector size

 

 

 

Injector LPG (E) - black coated

Ø

0.15 inch (3.9 mm)

0.19 inch (5.0 mm)

 

 

 

 

HTG

 

CO

IGN

TMR

MIN

MAX

 

Fig. 2

Fig. 3

B (flue)

A (air)

BOILER FAN SPEEDS

The boiler fan speeds require to be checked and/or adjusted prior to making any adjustments to the gas valve or if the main PCB has been replaced.

ATTENTION

Gas type and boiler fan speed (output) must be set according to the specific appliance specification. Raypak accepts no responsibility if the gas type and/or fan speed is not correctly adjusted according to the respective specification as detailed on the boiler data badge.

ADJUSTING GAS PRESSURE

The gas pressure can not be adjusted as the boiler is equipped with a pneumatic gas valve.

CHECKING/ADJUSTING THE APPLIANCE FAN SPEEDS Move the selector switch to the OFF position and remove the 3-selector knobs.

ABSOLUTE MAX FAN SPEED

Locate the MAX trim pot (Fig. 2) and gently adjust clockwise or counter clockwise to achieve the correct fan speed (see table below).

NOTE

ThedisplayshowsthefanRPMinmultiplesof1000,i.e. 2.5=2500RPM.

ABSOLUTE MIN FAN SPEED

Locate the MIN trim pot (Fig. 2) and gently adjust clockwise or counter clockwise to achieve the correct fan speed (see table below).

NOTE

The display shows the fan RPM in multiples of 1000, i.e. 2.5 = 2500RPM.

IGNITION FAN SPEED ATTENTION

Do this operation only after the adjusting of absolute max and min fan speed.

Locate the IGN trim pot (Fig. 2) and gently adjust clockwise or counter clockwise to achieve the correct fan speed (see table below).

NOTE

The display shows the fan RPM in multiples of 1000, i.e. 2.5 = 2500RPM.

HEATING FAN SPEED

Locate the HTG trim pot (Fig. 2) and gently adjust clockwise or counter clockwise to achieve the correct fan speed (see table below).

NOTE

The display shows the fan RPM in multiples of 1000, i.e. 2.5 = 2500RPM.

FAN SPEED (rpm)TABLE

MODEL

MAX

MIN

HTG

IGN

XPak85

5,700

1,900

5,700

3,700

XPak120

5,400

1,400

5,400

3,700

 

 

 

 

 

ADJUSTING THE GAS VALVE

THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH THE AID OF A PROPERLY CALIBRATED FLUE GAS ANALYZER.

CHECKING THE CO2 AND ADJUSTING THE GAS VALVE THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH THE AID OF A PROPERLY CALIBRATED FLUE GAS ANALYZER. Isolate the boiler from the electrical supply and remove the appliance casing. Set the flue gas analyzer to read CO2 and insert the probe into the flue analysis test point (A-air, B-flue Fig. 3). Restore the electrical supply to the boiler and switch the boiler to the OFF mode. To adjust the gas valve you must first ensure that the fan speed potentiometers (trim pots) have been set correctly. Remove the 3-selector knobs, locate and press the CO button). The appliance will now operate in CO mode for approximately 15- minutes.

GAS VALVE MAXIMUM SETTING

Locate and gently turn the HTG trim pots until the maximum value (max fan speed) is obtained and check that it corresponds with the appropriate CO2 value (Maximum) for the respective boiler. If the CO2 reading is correct, proceed to gas valve minimum setting. However, If the CO2 reading is incorrect, the maximum gas pressure must be adjusted as follows:

-Using a suitable screwdriver, very slowly turn the maximum adjustment screw (Fig. 4) – clockwise to decrease, counter clockwise to increase – until the correct value is displayed on the CO2 analyzer (allow time for the analyzer to stabilize).

GAS VALVE MINIMUM SETTING

Locate and gently turn the HTG trim pot until the minimum value (min fan speed) is obtained and check that it corresponds with the appropriate CO2 value (Minimum) for the respective appliance. If the CO2 reading is correct, rotate the HTG trim pot until the correct value is obtained for the respective appliance (see fan speed table) and proceed.

However, If the CO2 reading is incorrect, the minimum gas pressure must be adjusted as follows:

-Using a suitable screwdriver, very slowly turn the minimum adjustment screw (Fig. 4) – clockwise to increase, counter clockwise to decrease - until the correct value is displayed on the CO2 analyzer (allow time for the analyzer to stabilize).

INSTALLATIONS AT ELEVATION

Rated inputs are suitable for up to 4,500 ft elevation (see technical data table). Consult the factory for installations at altitudes over 4,500 ft above sea level. No hardware changes are required to the boilers for installations up to 10,000 ft (adjustments may be required).

COMPLETION

On completion of the combustion analysis check and/or any gas valve adjustment, set the HTG trim pot to the corresponding value as detailed in the fan speed table. Reattach the 3-selector knobs. Remove the test probe from the test point and reattach the sealing screws and/or cap.

57

Image 57
Contents Page About the XPak About these instructionsContents PAY Attention to These Terms Following instructions must be observedYou must also observe Observe these instructions as general warnings What to do if you smell gasObserve these instructions for space heating water Tools, materials and additional equipmentBefore Installation General SafetyM E / T E M P E R a T U R E Relationships in Scalds Water Time to Produce SeriousOperating Limits of the boiler Regulations and GuidelinesGeneral layout Fig IntroductionAB C DE Technical Data Boiler Dimensions And Weight Recommended Minimum Service ClearancesXPak Max flues length de-rate less 2%Xpak Internal Hydraulic Circuit FIG Mode of Operation Manual Handling Statement Mode of Operation AT RestSafety Devices Principle ComponentsPiping Connections FIG Dimensions and Connections Fig Packaging and Transportation Boiler BOX Content Table Pos Parts Quantity PackagingScope of Delivery Transporting the BoilerInstallation Prepare Xpak LocationPrepare Xpak Xpak Piping Boiler with DHW Tank Procedure SummaryWaterside Flow Primary Circuit Pump DutyKey for installation sample diagrams Xpak Installation DiagramsPage Page Making the GAS Connection Length Gas Volume Capacity Pipe feet Ft 3/hGas Pipe Capacity for different pipe sizes Equivalent length for pipe fittings in feetBoiler Template Fig All Air from Outdoor sealed combustion All Air from Inside the Building room airVent Systems Flue GAS SystemBoiler Supply Minimum Clearances from VENT/AIR Inlet Termination Installations1 Canadian Installations2Vertical Coaxial Sealed Combustion Operation TWO Pipes Single Wall Room AIR Dependent Operation Stainless steel Field supplied013102 Description Diagram Drawing TWO Pipes Single Wall = total intake length = Electrical Connections Connecting the Condensate Water DrainExternal Wiring Limitations External WiringConnecting Thermostat Appliance Terminal BlockTerminal Strip Details HighLow WAY Valve Wiring Connection Remote Control ConnectionOutdoor Sensor Connection Wiring Functional Diagram Are several steps involved in starting up the boiler START-UP ProcedureCommissioning Freeze Protection When UsedCHECK/CONTROL Water Chemistry Heating SystemInitial Lighting and Ignition Safety Shutoff Device Test Testing for GAS LeaksCheck Thermostat Circuits Initial Flushing of the SystemWarranty Final ChecksInstructing the User Reset Function Switching on the ApplianceSwitching OFF START-UP and OperationIndicator Leds and Faults Green indicator LED FigRed indicator LED Fig For alarm AL91 For AL41 faultsCHECKS, Adjustments and Fault Finding GAS Valve Minimum Pressure Setting CHECKING/ADJUSTING the Boiler FAN SpeedsExternal Faults Installation FaultsReversed Polarity or Supply Fault Fault FindingBoiler Configuration Electrical ChecksProgrammable Timer DAY+NIGHT Setting the Outdoor Reset Curve with Outdoor SensorSelecting the offset heating curve Fig Type of Heat Request Standard212 194 176 158 140 122 104 Code Cause Alarm Type Action Fault CodesComponent Removal Procedure Replacement of ComponentsServicing Instructions GeneralFlow Sensor Primary Thermistor Fig Water Pressure Switch FigReturn Sensor Return Thermistor Fig Printed Circuit Board FigFlue FAN & Mixer Fig Blocked Flue Pressure SWITCH/IGNITION Transformer FigBurner Fig Main Heat Exchanger FigFlue Collector and Flue Thermostat Removal Fig Condensate Trap Removal FigLPG Instructions GAS Supply InstallationPropane GAS GAS SupplyTechnical Data LPG Sequence of the Ignition System Exploded Diagrams 56a Xpak Drawing Call OUT Description Important Instructions for the Commonwealth of Massachusetts Applicable Warranty Periods Limited WarrantyHOW to Make Warranty Claim START-UP Checklist for FAN-ASSISTED Raypak Products Your XPak serial number For future reference

120, 85 specifications

The Raypak 120,85 is a prominent model in the realm of pool and spa heating solutions, designed to deliver unmatched efficiency and performance. Renowned for its robust features and innovative technologies, the Raypak 120,85 stands out as a reliable choice for homeowners seeking to maintain the perfect water temperature in their pools and spas.

One of the primary characteristics of the Raypak 120,85 is its impressive heating capacity. With a total output of 120,000 BTUs, this heater quickly and efficiently warms up water, ensuring that users can enjoy comfortable swimming conditions regardless of the outdoor temperature. The 85 indicates its ability to deliver consistent performance even in cooler climates, making it an adaptable option for various geographical locations.

The Raypak 120,85 is equipped with a state-of-the-art, copper fin tube heat exchanger, which provides superior heat transfer efficiency. This technology enhances the heater's ability to warm water rapidly while maintaining energy efficiency. Additionally, the copper material is known for its durability and resistance to corrosion, ensuring a long lifespan for the heat exchanger.

Another key feature of the Raypak 120,85 is its electronic ignition system. This innovation eliminates the need for a standing pilot light, which not only saves energy but also enhances safety by reducing the risk of gas leaks associated with traditional ignition systems. The electronic ignition provides precise control, ensuring a reliable start each time.

The Raypak 120,85 also boasts a digital display control panel, allowing users to easily monitor and adjust the water temperature settings. This intuitive interface provides accurate readings and simplifies the operation, making it accessible for all users, regardless of their technical expertise.

Furthermore, this heater is designed with a compact footprint, making it suitable for a variety of installation spaces, whether it’s in a pool equipment area or near a spa. Its robust build quality and weather-resistant design ensure that it can withstand the elements, making it a durable and long-lasting investment.

In summary, the Raypak 120,85 combines advanced heating technology, robust construction, and user-friendly features. With its high BTU output, efficient heat exchanger, electronic ignition, and digital controls, it represents a top-tier option for anyone seeking reliable and effective heating solutions for pools and spas. Whether for leisure or relaxation, the Raypak 120,85 promises to deliver an optimal swimming experience, season after season.