Fig. 6: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations

 

 

U.S. Installations1

Canadian Installations2

A

Clearance above grade, veranda, porch,

1 ft (30 cm)

1 ft (30 cm)

deck, or balcony

 

 

 

 

 

 

 

 

Clearance to window or door that may be

4 ft (1.2m) below or to side

 

B

of opening; 1 foot (30 cm)

3 ft (91 cm)

opened

 

above opening

 

 

 

 

 

 

 

 

C

Clearance to permanently closed window

*

*

 

 

 

 

 

Vertical clearance to ventilated soffit located

 

 

D

above the terminal within a horizontal dis-

5 ft (1.5m)

*

tance of 2 ft (61cm) from the centerline of the

 

 

 

 

terminal

 

 

 

 

 

 

E

Clearance to unventilated soffit

*

*

 

 

 

 

F

Clearance to outside corner

*

*

 

 

 

 

G

Clearance to inside corner

6 ft (1.83m)

*

 

 

 

 

 

Clearance to each side of center line ex-

 

3 ft (91 cm) within a height

H

*

15 ft above the me-

tended above meter/regulator assembly

 

 

ter/regulator assembly

 

 

 

 

 

 

 

I

Clearance to service regulator vent outlet

*

6 ft (1.83m)

 

 

 

 

 

Clearance to non-mechanical air supply inlet

4 ft (1.2m) below or to side

 

J

to building or the combustion air inlet to any

of opening; 1 ft (30 cm)

3 ft (91 cm)

 

other appliance

above opening

 

 

 

 

 

K

Clearance to mechanical air supply inlet

3 ft (91 cm) above if within

6 ft (1.83m)

10 ft (3m) horizontally

 

 

 

 

 

 

 

L

Clearance above paved sidewalk or paved

7 ft (2.13m)

7 ft (2.13m) t

driveway located on public property

 

 

 

 

 

 

 

M

Clearance under veranda, porch, deck or

*

12 in. (30 cm) TT

balcony

 

 

 

 

 

 

 

1In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code

2In accordance with the current CAN/CGA-B149 Installation Codes

t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves both dwellings

TTPermitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and

underside of veranda, porch, deck or balcony is greater than 1 ft (30cm)

*Clearances in accordance with local installation codes and the requirements of the gas supplier

Table E: Vent/Air Inlet Termination Clearances

10

Image 10
Contents Installation & Operating Instructions Page Contents Pay Attention to These Terms Product Receipt Before InstallationInstallations at Elevation Model IdentificationGas Vent Size Conn Input Component LocationsGeneral Information Max MinTime/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Indoor Installations InstallationInstallation Codes Equipment BaseIndoor Units Outdoor InstallationsCombustion and Ventilation Air Heater Min. Clearance Minimum From CombustibleTable E Vent/Air Inlet Termination Clearances Combustion Air Filter Direct VentTruSeal Combustion Air Remove the Debris ScreenConventional Combustion Air Supply InstallationsCanadian Installations All Air from Inside the BuildingWater Piping Relief Valve Installation and PipingTemperature & Pressure Gauge GeneralHydronic Heating Domestic Hot Water Fitting Type Equivalent Length ft 2 NPTPool Heating Combined Potable Water and Space HeatingAutomatic Chlorinators and Chemical Feeders Pool/Spa Water Chemistry Winterizing Your HeaterGas Supply Connection Gas SupplyWater Hardness Electrical Power Connections Gas Supply PressureCheck the Power Source Making the Electrical ConnectionsSupport of Vent Stack Field Wiring ConnectionAppliance Categories Installations Vent Terminal LocationCanadian Installations Venting Installation TipsVenting Configurations InstallationLength CertifiedTotal Effective Combustion Air Air Inlet Max. Length* ftModel Vent Size Volume Flue Products Common VentingHorizontal Through-the-Wall and Direct Venting Category Horizontal Through-the-Wall VentingDirect Vent-Vertical Direct Vent VerticalOutdoor Installation Outdoor VentingFreeze Protection CleaningPVC vent assembly instructions PVC Venting OptionPVC Vent Adapter Termination using Adapter Thimble ControlsOperating Modes Differential GraphBoil Target 78F Boil Max 86F Boil Min 70F ‘Burner’ Delay 10 VDC 20 mA Modes Default Setting Range10 VDC 20 mA Boiler Target Definitions Operation Number Field Type Fault DescriptionRank Heater Sequence of Operation Ignition ModuleFlow Switch High Limit-Manual ResetHigh Limit-Auto Reset Optional Code ConditionHigh & Low Gas Pressure Switches Optional Modulating Temperature ControlLow Water Cut-Off Optional Blocked Vent Switch Air Pressure SwitchUDB Diagnostic Board Condensate Float SwitchWiring Diagrams Models 1005 Model Pre Start-up START-UPPre Start-up Check Start-Up Initial Start-upPreparation Required toolsBlower Check Model No Net Blower Suction Setting In. WCModel No Amp Draw Setting Manifold CheckFinishing Safety InspectionLeak Test Procedure Dual-Seat Gas Valve Follow-UpPost Start-Up Check GASLighting Instructions OperationTo Turn Off Gas To Appliance Troubleshooting StepUDB Fault History MaintenanceSuggested Minimum Maintenance Schedule Weekly Preventive Maintenance SchedulePeriodically Semi-AnnuallyInside Air Contamination AppendixAs Required Important Instructions for the Commonwealth of Massachusetts Limited Parts Warranty Xtherm Types H and WH ModelsLimited Parts Warranty Xtherm Types WHP START-UP Checklist for FAN-ASSISTED Raypak Products Page
Related manuals
Manual 12 pages 19.26 Kb

1005 specifications

Raypak is a prominent name in the heating industry, known for its innovative and efficient heating solutions for residential and commercial applications. The models 2005, 1005, and 1505 are notable offerings from Raypak, each designed to provide reliable performance, energy efficiency, and user-friendly operation.

The Raypak 2005 model stands out for its robust construction and high efficiency. It utilizes advanced technology to ensure consistent heating and reliability. With a high-capacity output, the 2005 is ideal for larger pools and spa applications, efficiently maintaining desired temperatures even during colder months. Its digital control system allows for precise temperature settings, enabling users to customize their heating needs effectively.

The 1005 model is an excellent choice for medium-sized pools and spas, offering a perfect balance of power and energy efficiency. One of its key features is the ability to operate quietly, making it suitable for residential areas where noise can be a concern. The 1005 employs a reliable gas burning system that maximizes fuel efficiency and provides fast heating. Its compact design also makes it easy to install, saving space while delivering exceptional performance.

The Raypak 1505 model is designed for versatility, catering to a wide range of heating requirements. One of its standout characteristics is its corrosion-resistant heat exchanger, which ensures long-lasting performance even in harsh environments. The 1505 also incorporates a user-friendly digital interface, allowing for easy operation and monitoring of temperature settings. It supports both natural gas and propane, providing flexibility to users based on their energy source preferences.

All three models—the 2005, 1005, and 1505—benefit from Raypak's commitment to energy efficiency. They are designed to meet stringent environmental standards while minimizing operational costs for the user. Additionally, their reliable safety features, such as pressure switches and safety valves, ensure safe operation across various conditions.

In summary, Raypak's 2005, 1005, and 1505 models exhibit a combination of efficiency, durability, and user-friendliness. With their advanced technologies and adaptable designs, these heaters are suitable for a wide array of heating applications, providing users with reliable solutions for their heating needs. Whether for residential or commercial use, Raypak's commitment to quality and innovation makes these models excellent choices for anyone seeking dependable heating solutions.