GE 2800 manual Series, Switches Description Left Switches, Up resistance heat only

Page 13

ge.com

Auxiliary Control Switches

These switches are located behind the room cabinet under the control panel.

5800 Series

Switches

Description

 

Left Switches

 

 

(1)

ALL I2R

Heat pump override —

 

 

Down — Normal heat pump operation

 

 

Up — resistance heat only

(2)

C: FAN

Fan control for cooling operation —

 

 

Down — Fan Continuous

 

 

Up — Fan Cycle

(3)

H: FAN

Fan control for heating operation —

 

 

Down — Fan Cycle

 

 

Up — Fan Continuous

(4)

CLASS 2

Remote Thermostat Mode —

 

 

Down — Unit Control

 

 

Up — Remote Thermostat

(5)

LOAD SHED

Load Shedding when connected to Central Desk Control System —

 

 

Down — Fan shuts off with unit

 

 

Up — fan under “Smart Fan” settings

(6)

FREEZ S

Freeze Sentinel Override —

 

 

Down — Freeze Sentinel ON

 

 

Up — Freeze Sentinel OFF

(7)

CONST FAN

Constant Fan —

 

 

Down — Fan runs normally

 

 

Up — fan runs when unit is in STOP position

(8)

OCCUPIED

Occupancy Sensor Mode —

 

 

Down — Unit Control

 

 

Up — Occupancy Sensor Connected

Right Switches

 

TL1 – TL3

 

Cooling temperature limiting (See table at bottom of page)

TL4 – TL6

 

Heating temperature limiting (See table at bottom of page)

(7)

 

Diagnostics Switch

(8)

 

Heat Sentinel switch —

 

 

Down — Heat Sentinel OFF

 

 

Up — Heat Sentinel ON

(9)

 

Heat Boost —

 

 

Down — Heat Boost OFF

 

 

Up — Heat Boost ON

5800 Series shown UP

DOWN

ALLI2R (All Electric Heat) (5800 Series models only)

C:FAN CN (Cooling–Smart Fan)

H:FAN CY (Heating–Smart Fan) CLASS 2 (Remote Thermostat)

LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel)

CONST FAN (Constant ON Fan)

OCCUPIED (Occupancy Sensor)

1

2

3

4

5

6

7

8

 

 

 

HIGH

 

 

 

 

UP

 

 

 

COOL

 

 

 

 

DOWN

1

2

3

4

5

6

7

8

9

 

HEAT BOOST

(5800 Series models only) Heat Sentinel Diagnostics Switch

TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)

TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool)

Cooling and Heating temperature limits are set independently, temperature limiting switches are in factory-set down position, except as noted.

Cooling Temperature Limits

Switches Up

 

NONE

1

1, 2

2

2, 3

1, 2, 3

1, 3

3

 

 

 

 

 

 

 

 

 

 

 

 

60

64

66

68

70

72

74

76

 

 

 

 

 

 

 

 

 

 

 

Heating Temperature Limits

 

 

 

 

Switches Up

 

6

4, 6

4, 5, 6

5, 6

5

4, 5

4

NONE

 

 

 

 

 

 

 

 

 

 

 

 

65

70

72

74

76

78

80

85

 

 

 

 

 

 

 

 

 

 

13

Image 13
Contents GE Zoneline packaged terminal air conditioners Quick Reference ALL Units Require Power Connection KITZoneline Chassis Nomenclature Power Connection KitsExample Newest Innovation from GE Deluxe Dry Air 25 ModelsComparison of DRY AIR 25 Dehumidification Cooling With Resistance HeatTable of Contents Introduction Zoneline System Optional Accessories of the Zoneline SystemChassis Room Cabinet Wall Case2800 Zoneline Features5800 .2Features and Benefits Fan-Cycle Switch SmartFan Fan-Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Easy Clean Air Discharge AreaConcealed Manual Vent Control Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits Series models only Heat Sentinel Diagnostics Switch Switches Description Left SwitchesSeries Up resistance heat onlyCentral Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable Remote Thermostat Control Field Wiring TerminalResistance Heat Models RAK806 Universal Control Cover LabelHeat Pump Models Feature Heat Pump Electric Heat24V AC Compressor Heater Common GroundRemote Control Low Voltage Wiring For Use With Mechanical 4-Wire Systems OnlyField-Supplied Relay Specifications Relay DesignationBalance Point Heat Pumps and Energy SavingsZoneline Heat Pump Heat Source Logic Heat Pump Operation Zoneline 3800 and 5800 SeriesHeat pump defrost Zoneline 3800 and 5800 Series Heat pump condensateAir Distribution Application CommentsWall Case with Chassis Installed DimensionsRAB71A Wall Case RAB77 Wall CaseSub-Base Wall CaseChoice of wall cases is available for the Zoneline General Wall Case Installation DataWindow, Curtain and Panel Wall Construction Architectural Window Louver InstallationMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionCase Angles Preparation of the Wall Case for All Types of ConstructionFastening Wall Case Framing for Wall CaseBrick Veneer and Frame Construction Wall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedGasket Caulk around Perimeter Wall case all 22-1/4 Where it joins22-1/4 Four sides 22-3/8All four sides where it Power supply42-1/8 27-1/4 13-1/8RAB71/77 4 ± 1/413-3/4 + D Ge.com TOP View RAB71/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsRAK6052 Ducted Application AZ2800/3800 SeriesRAK601 High WideDucted Detailed Side Views AZ2800/3800 Series Outdoor Grille Exterior GrillesExterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Line-Cord Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 2800/3800/5800 SeriesEssential Elements Ordering Overview 230/208-Volt Line Cord Connected Units Maximum Connected LoadVolt Units Heat Pump Performance Data Cooling Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Latent System Capacity Indoor Ambient DB Temperature F 10093.00 Outdoor Design Temperature Difference Formula for Calculating Operating Costs Using Above DataInstalled unit capacity Btuh Watts/KW Normal Yearly Operating DataPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Premium Line 5800 Series Receptacles/Sub-BasesSpecifications RAB71A Complete Accessory ListGeneral Installation Suggestions Ducted Installation Comments Zoneline warrantyReplacement Installations New InstallationsExterior Grille Color Samples Alphabetical IndexWarm Gray Beige Maple Bittersweet Chocolate GE Company Pub. No -S087 PC48947 Century of quality and innovation