Maximum Connected Load

The maximum connected load of a Zoneline® unit occurs when the unit is in resistance heating operation. The maximum amperage shown in the tables below is the combined total of the resistance heater and the indoor fan motor.

230/208-Volt Line Cord Connected Units

 

 

 

 

 

 

Power Connector Kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAK3153

 

RAK3203

 

 

RAK3303

 

 

 

rak4157

 

RAK4207

 

 

RAK4307

 

 

rak204d15p

 

RAK204D20P

 

 

RAK204D30P

MODEL

 

230 V

 

208 V

 

230 V

 

208 V

230 V

 

208 V

NUMBER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AZ28E07DA*

 

11.5

 

10.5

 

15.5

 

14.1

N/A

 

N/A

AZ28E09DA*

 

11.5

 

10.5

 

15.5

 

14.1

22.3

 

20.3

AZ28E12DA*

 

11.6

 

10.6

 

15.5

 

14.1

22.3

 

20.3

AZ28E15DA*

 

11.6

 

10.6

 

15.6

 

14.2

22.4

 

20.4

AZ38H07DA*

 

11.5

 

10.5

 

15.5

 

14.1

N/A

 

N/A

AZ38H09DA*

 

11.5

 

10.5

 

15.5

 

14.1

22.3

 

20.3

AZ38H12DA*

 

11.6

 

10.6

 

15.5

 

14.1

22.3

 

20.3

AZ38H15DA*

 

11.6

 

10.6

 

15.6

 

14.2

22.4

 

20.4

AZ58H07DA*

 

11.5

 

10.5

 

15.5

 

14.1

N/A

 

N/A

AZ58H09DA*

 

11.5

 

10.5

 

15.5

 

14.1

22.3

 

20.3

AZ58H12DA*

 

11.6

 

10.6

 

15.5

 

14.1

22.3

 

20.3

AZ58H15DA*

 

11.6

 

10.6

 

15.6

 

14.2

22.4

 

20.4

*All versions

 

 

 

 

 

 

 

 

 

 

Electric Heat Amps include electric heater and fan motor current draw.

 

 

 

 

 

 

Values shown in table above are also the total connected loads for units installed with sub-bases.

 

 

 

 

RAK204D15P — same as RAK3153

 

 

 

 

 

 

 

 

 

 

RAK204D20P — same as RAK3203

 

 

 

 

 

 

 

 

 

 

RAK204D30P — same as RAK3303

 

 

 

 

 

 

 

 

 

 

265-Volt Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub-Base/Power Connector Kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAK204E15

 

RAK204E20

 

RAK204E30

 

 

 

 

 

 

RAK5172

 

RAK5202

 

RAK5302

 

 

 

 

 

 

RAK5157

 

RAK5207

 

RAK5307

 

 

 

 

 

MODEL

 

265 V

 

265 V

 

265 V

 

 

 

 

NUMBER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AZ28E07EA

 

10.2

 

13.7

 

N/A

 

 

 

 

AZ28E09EA*

 

10.2

 

13.7

 

19.6

 

 

 

 

 

AZ28E12EA*

 

10.3

 

13.7

 

19.6

 

 

 

 

 

AZ28E15EA*

 

10.3

 

13.7

 

19.6

 

 

 

 

 

AZ38H07EA*

 

10.2

 

13.7

 

N/A

 

 

 

 

AZ38H09EA*

 

10.2

 

13.7

 

19.6

 

 

 

 

 

AZ38H12EA*

 

10.3

 

13.7

 

19.6

 

 

 

 

 

AZ38H15EA*

 

10.3

 

13.7

 

19.6

 

 

 

 

 

AZ58H07EA*

 

10.2

 

13.7

 

N/A

 

 

 

 

AZ58H09EA*

 

10.2

 

13.7

 

19.6

 

 

 

 

 

AZ58H12EA*

 

10.3

 

13.7

 

19.6

 

 

 

 

 

AZ58H15DA*

 

10.3

 

13.7

 

19.6

 

 

 

 

 

*All versions

Electric Heat Amps include electric heater and fan motor current draw.

44

Image 44
Contents GE Zoneline packaged terminal air conditioners ALL Units Require Power Connection KIT Quick ReferenceExample Power Connection KitsZoneline Chassis Nomenclature Deluxe Dry Air 25 Models Newest Innovation from GEComparison of DRY AIR 25 Dehumidification Cooling With Resistance HeatTable of Contents Introduction Optional Accessories of the Zoneline System Zoneline SystemChassis Room Cabinet Wall CaseZoneline Features 28005800 .2Features and Benefits Fan-Only Setting HIGH/LOW Fan-Cycle Switch SmartFanCompressor Restart Delay Electronic Temperature LimitingEasy Clean Air Discharge Area Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalHeating Temperature Limits Auxiliary Control SwitchesCooling Temperature Limits Switches Description Left Switches Series models only Heat Sentinel Diagnostics SwitchSeries Up resistance heat onlyImportant CDC Comments all series applicable CDC Terminal Location and Typical WiringCentral Desk Control Field Wiring Terminal Remote Thermostat ControlResistance Heat Models RAK806 Universal Control Cover LabelFeature Heat Pump Electric Heat Heat Pump Models24V AC Compressor Heater Common GroundFor Use With Mechanical 4-Wire Systems Only Remote Control Low Voltage WiringField-Supplied Relay Specifications Relay DesignationHeat Pumps and Energy Savings Balance PointHeat Pump Operation Zoneline 3800 and 5800 Series Zoneline Heat Pump Heat Source LogicHeat pump defrost Zoneline 3800 and 5800 Series Heat pump condensateApplication Comments Air DistributionDimensions Wall Case with Chassis InstalledRAB71A Wall Case RAB77 Wall CaseChoice of wall cases is available for the Zoneline Wall CaseSub-Base Wall Case Installation Data GeneralArchitectural Window Louver Installation Window, Curtain and Panel Wall ConstructionMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Case AnglesBrick Veneer and Frame Construction Framing for Wall CaseFastening Wall Case Frame and Brick Veneer Installation Cord set connected Wall Section Detailed Side View22-1/4 Where it joins Gasket Caulk around Perimeter Wall case all22-1/4 Four sides 22-3/8Power supply All four sides where it42-1/8 27-1/4 13-1/813-3/4 + D 4 ± 1/4RAB71/77 Ge.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Ducted Installations New Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDucted Application AZ2800/3800 Series RAK6052RAK601 High WideDucted Detailed Side Views AZ2800/3800 Series Exterior Grilles Outdoor GrilleExterior Architectural Treatments Special Outdoor Grilles Or 277-Volt Unit Installation Permanently Connected Units 230/208-Volt Line-Cord Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsEssential Elements Ordering Overview Electrical Wiring Information 2800/3800/5800 SeriesReplacement of Existing Chassis Volt Units Maximum Connected Load230/208-Volt Line Cord Connected Units Total Capacity Btuh Btuh at 80º F D.B. 67º F W.B Cooling Performance DataHeat Pump Performance Data 93.00 Indoor Ambient DB Temperature F 100Latent System Capacity Formula for Calculating Operating Costs Using Above Data Outdoor Design Temperature DifferenceInstalled unit capacity Btuh Watts/KW Normal Yearly Operating DataPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Receptacles/Sub-Bases Premium Line 5800 SeriesSpecifications Complete Accessory List RAB71AGeneral Installation Suggestions Zoneline warranty Ducted Installation CommentsReplacement Installations New InstallationsWarm Gray Beige Maple Bittersweet Chocolate Alphabetical IndexExterior Grille Color Samples Century of quality and innovation GE Company Pub. No -S087 PC48947