GE 2800 manual Wall Case, Sub-Base, Choice of wall cases is available for the Zoneline

Page 22

Wall Case

A choice of wall cases is available for the Zoneline.®

RAB71A — This insulated case is constructed of heavy-gauge galvanized steel and finished with a protective baked-enamel finish for protection and appearance. Design of the case provides for support of the chassis and free draining of any water entering the wall case. A petroleum microcrystalline wax is applied at critical points of fabrication to seal against moisture. The dimensions of the RAB71 wall case are: 42" wide by 16" high by 13-3/4" deep, the same dimensions as the original wall case for GE Zonelines built in 1961. The RAB71 wall case is also available in depths other than the standard depth. It is available on special order as: RAB7116 – 16" deep; RAB7124 – 24" deep; RAB7128 – 28" deep; and RAB7131 – 31" deep. All of these special-order deep wall cases are insulated and have sheet metal dividers, or splitters, to prevent the recirculation of condenser discharge air.

RAB77 — This non-insulated wall case is molded from fiberglass-reinforced polyester compound. This SMC (Sheet-Molded Compound) wall case offers outstanding strength, durability, color retention, water integrity and corrosion resistance. The dimensions of the RAB77 wall case are: 42-1/8" wide by 16-1/4" high by 13-7/8" deep.

Both wall cases are of universal design, accepting all Zoneline chassis of current design as well as all GE Zoneline chassis produced since 1961.

Drain holes are provided in the rear of the wall case to permit excessive cooling condensate water, heat pump condensate or precipitation entering the wall case to drain freely. A drain kit may be connected to the wall case to control any water draining from the wall case. See page 34 for information on RAD10 Drain Kit.

RAK901L — For installations where the wall case extends into room, RAK901L is an insulation kit that can be used with the RAB77 or any existing non-insulated wall case to minimize the possibility of condensation forming on the indoor side of the case during the winter.

Sub-Base

The sub-base is an optional accessory for the Zoneline and is presented with the wall case information since the decision to use or not to use a sub-base in the installation is a factor in the location of the wall opening for the unit. National Electrical Code® requires that air conditioning units connected to voltages in excess of 250 volts be “permanently connected.” There are also some installations where units connected to voltage sources under 250 volts may also need to be “permanently connected.” If you are in doubt about the requirements for a particular installation, consult Article 440 of the NEC or the local electrical inspector. These requirements are designed to protect personal safety and should be strictly followed. Although NEC is cited here as a reference, all electrical wiring and installations must conform to any and all local electrical codes and regulations.

“Permanent Connection” generally means wiring to the unit must be contained in an enclosed “chaseway,” where access to the wiring connections is more restrictive than a normal line cord plugged into a receptacle. NEC requirements may be met by using flexible or rigid conduit to contain the wiring between the unit and a junction box that contains the wiring connections. The conduit is connected to the unit and to the junction box with connectors to hold the conduit in place. The junction box may be located in the floor or the wall of the structure but only approved connectors may be used outside the unit or the junction box. The sub-base is UL® listed as a junction box for permanent connection of a Zoneline.

Using a sub-base in an installation requiring permanent connection provides a convenient, consistent location for unit wiring to be connected to building wiring. The use of a sub-base is not required, but the convenience and the improved aesthetics it offers makes the use of a sub-base a viable means of permanent connection.

RAK204U — The RAK204U Series of sub-bases provides a variety of designs that fit the site needs and are available for use with Zoneline PTAC/PTHP units. The RAK204U will most likely be used for support of the wall case and unit.

The RAK204U is the same physically as the other sub-bases except there is no receptacle installed. Receptacles and wiring can be field installed and, by using the RAK205CW chaseway and the RAK4002 junction box perform the same function as any of the other sub-base kits by selecting the correct receptacle and installing it in the interior mounting plate inside the RAK204U.

208/230-volt receptacles can also be mounted in the cover plate for easy access when direct connect wiring is not required. 265-volt units are to be “Permanently (or Direct) Connected” and the external receptacle (when wiring is not enclosed in a chaseway) does not meet this requirement.

A knockout for a fuseholder or a disconnect is also provided in the cover plate.

RAK204U — No receptacle, no wiring, will accept any

15-, 20-, 30-amp receptacle and wiring. No chaseway is included. RAK205CW chaseway must be ordered separately.

The 230/208-volt sub-bases below include a short, sub-base power connection kit. Since sub-base connected units are not considered to be line-cord connected, a Leakage Current Detection and Interruption or Arc Fault Current Interrupter device is not necessary.

The junction box (RAK4002A for 2800 and 3800 Series units; RAK4002B for 5800 Series units) that mounts on the chassis of 230/208-volt sub-base connected units must be purchased separately.

RAK204D15P 208/230-volt 15-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included.

RAK204D20P 208/230-volt 20-amp receptacle. Receptacle is NEMA6-20R with 18" of #12AWG wires attached to the receptacle. Short power connection kit included. Chaseway included.

22

Image 22
Contents GE Zoneline packaged terminal air conditioners ALL Units Require Power Connection KIT Quick ReferenceZoneline Chassis Nomenclature Power Connection KitsExample Comparison of DRY AIR 25 Dehumidification Deluxe Dry Air 25 ModelsNewest Innovation from GE Cooling With Resistance HeatTable of Contents Introduction Chassis Room Cabinet Optional Accessories of the Zoneline SystemZoneline System Wall Case5800 Zoneline Features2800 .2Features and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingConcealed Manual Vent Control Easy Clean Air Discharge AreaUp-Front Air Filters Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits Series Switches Description Left SwitchesSeries models only Heat Sentinel Diagnostics Switch Up resistance heat onlyCentral Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover Label24V AC Feature Heat Pump Electric HeatHeat Pump Models Compressor Heater Common GroundField-Supplied Relay Specifications For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Relay DesignationHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 3800 and 5800 Series Heat Pump Operation Zoneline 3800 and 5800 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateApplication Comments Air DistributionRAB71A Wall Case DimensionsWall Case with Chassis Installed RAB77 Wall CaseSub-Base Wall CaseChoice of wall cases is available for the Zoneline Wall Case Installation Data GeneralMasonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Case AnglesFastening Wall Case Framing for Wall CaseBrick Veneer and Frame Construction Frame and Brick Veneer Installation Cord set connected Wall Section Detailed Side View22-1/4 Four sides 22-1/4 Where it joinsGasket Caulk around Perimeter Wall case all 22-3/842-1/8 Power supplyAll four sides where it 27-1/4 13-1/8RAB71/77 4 ± 1/413-3/4 + D Ge.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsRAK601 Ducted Application AZ2800/3800 SeriesRAK6052 High WideDucted Detailed Side Views AZ2800/3800 Series Exterior Grilles Outdoor GrilleExterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 2800/3800/5800 SeriesEssential Elements Ordering Overview 230/208-Volt Line Cord Connected Units Maximum Connected LoadVolt Units Heat Pump Performance Data Cooling Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Latent System Capacity Indoor Ambient DB Temperature F 10093.00 Installed unit capacity Btuh Watts/KW Formula for Calculating Operating Costs Using Above DataOutdoor Design Temperature Difference Normal Yearly Operating DataPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Receptacles/Sub-Bases Premium Line 5800 SeriesSpecifications Complete Accessory List RAB71AGeneral Installation Suggestions Replacement Installations Zoneline warrantyDucted Installation Comments New InstallationsExterior Grille Color Samples Alphabetical IndexWarm Gray Beige Maple Bittersweet Chocolate Century of quality and innovation GE Company Pub. No -S087 PC48947