GE 2800 manual Heat Pumps and Energy Savings, Balance Point

Page 18

Heat Pumps and Energy Savings

GE Zoneline® Heat Pumps are designed to provide cost-efficient heat pump operation while monitoring room conditions to maintain comfort.

The units employ a logic system monitoring both outdoor and indoor temperatures to determine the heat source, thus increasing energy savings by operating longer in the heat pump mode.

Heat pumps save energy and cost less to operate than

units with electric resistance heaters as the only heat source. Just as the EER of an air conditioner is an indication of the efficiency of the unit, COP (Coefficient of Performance) is the indication of the efficiency of the heat pump. This relative efficiency of a heat pump compares the unit to electric resistance heat. If a unit has a COP of 3.0, it means the

unit will produce three times as much heat at rating conditions for the same electrical input wattage used for electric resistance heat.

The compressor is used in heat pump operation just as in air conditioning operation. In heat pump operation, the hot refrigerant gas is directed to the indoor coil rather than to the outdoor coil. Room air that circulates over the indoor coil gains heat from the coil rather than losing heat to the coil as during cooling operation.

As the outdoor temperature falls, the heat pump is able to extract less heat from the outdoor air to raise the temperature of the indoor air. For this reason, all packaged terminal heat pumps also have electric resistance heaters as backup to heat pump operation. At some point, the heat pump is unable to provide sufficient heat to adequately warm the room. Many Packaged Terminal Heat Pumps cease heat pump operation and change to more expensive resistance heat at some pre-determined outdoor temperature to compensate for the inability of the heat pump to maintain room temperature. This point, called the “switchover point,” is usually at an outdoor temperature where savings from heat pump operation may still be realized, if the unit is designed to maintain room comfort at the lower outdoor temperatures.

Balance Point

An important consideration of the selection of a heat pump unit is the “balance point” of the installation. Virtually every room is unique — with different insulation — different sizes and types of windows — different types of construction

different directional exposures. All of these variables, as well as geographical location, must be considered in order to determine the balance point, the point at which the heat pump is unable to produce enough heat to compensate for the heat loss of the room or area being heated. For these reasons a consulting engineer should be engaged to calculate the heat loss and specify the heat pump unit required.

GE offers two series of Zoneline Heat Pump units — the 3800 Series with Standard Microprocessor controls and the 5800 Series with Highly Featured Microprocessor controls

and both series react to the indoor temperature as well as the outdoor temperature in determining the heat source to provide comfortable room conditions and energy savings. This determination of the heat source based on the indoor temperature helps provide a more comfortable room.

18

Image 18
Contents GE Zoneline packaged terminal air conditioners ALL Units Require Power Connection KIT Quick ReferencePower Connection Kits Zoneline Chassis NomenclatureExample Comparison of DRY AIR 25 Dehumidification Deluxe Dry Air 25 ModelsNewest Innovation from GE Cooling With Resistance HeatTable of Contents Introduction Chassis Room Cabinet Optional Accessories of the Zoneline SystemZoneline System Wall Case5800 Zoneline Features2800 .2Features and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingConcealed Manual Vent Control Easy Clean Air Discharge AreaUp-Front Air Filters Corrosion Protection OptionalAuxiliary Control Switches Cooling Temperature LimitsHeating Temperature Limits Series Switches Description Left SwitchesSeries models only Heat Sentinel Diagnostics Switch Up resistance heat onlyCDC Terminal Location and Typical Wiring Central Desk ControlImportant CDC Comments all series applicable Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover Label24V AC Feature Heat Pump Electric HeatHeat Pump Models Compressor Heater Common GroundField-Supplied Relay Specifications For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Relay DesignationHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 3800 and 5800 Series Heat Pump Operation Zoneline 3800 and 5800 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateApplication Comments Air DistributionRAB71A Wall Case DimensionsWall Case with Chassis Installed RAB77 Wall CaseWall Case Sub-BaseChoice of wall cases is available for the Zoneline Wall Case Installation Data GeneralMasonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Case AnglesFraming for Wall Case Fastening Wall CaseBrick Veneer and Frame Construction Frame and Brick Veneer Installation Cord set connected Wall Section Detailed Side View22-1/4 Four sides 22-1/4 Where it joinsGasket Caulk around Perimeter Wall case all 22-3/842-1/8 Power supplyAll four sides where it 27-1/4 13-1/84 ± 1/4 RAB71/7713-3/4 + D Ge.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsRAK601 Ducted Application AZ2800/3800 SeriesRAK6052 High WideDucted Detailed Side Views AZ2800/3800 Series Exterior Grilles Outdoor GrilleExterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsElectrical Wiring Information 2800/3800/5800 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load 230/208-Volt Line Cord Connected UnitsVolt Units Cooling Performance Data Heat Pump Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Indoor Ambient DB Temperature F 100 Latent System Capacity93.00 Installed unit capacity Btuh Watts/KW Formula for Calculating Operating Costs Using Above DataOutdoor Design Temperature Difference Normal Yearly Operating DataPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Receptacles/Sub-Bases Premium Line 5800 SeriesSpecifications Complete Accessory List RAB71AGeneral Installation Suggestions Replacement Installations Zoneline warrantyDucted Installation Comments New InstallationsAlphabetical Index Exterior Grille Color SamplesWarm Gray Beige Maple Bittersweet Chocolate Century of quality and innovation GE Company Pub. No -S087 PC48947