ALTERNATE – CASE RECESSION LESS THAN 3" WITH SIDES AND TOP OF WALL OPENING WATERPROOF, FLASHING ON BOTTOM ONLY

For an installation that will provide better protection against water infiltration, GE recommends the use of one of the deeper RAB71 wall cases offered as special order items.

See page 23.

D

A

A

B

C

B

OUTDOOR

GRILLE

CASEFLASHING

CAULK*

1" WIDE 45° DRIP LIP

31

DIMENSIONS:

A. DISTANCE FROM GRILLE OR CASE TO OUTSIDE SURFACE OF WALL PLUS 2" TO 4" (TO INSERT UNDER CASE).

B. 1" DRIP LIP (MINIMUM)

C. 42" PLUS - SUFFICIENT TO FIT SNUGGLY UNDER AND UP AROUND THE CASE. D. 2" MINIMUM

(CAUTION: WHEN CAULKING DO NOT BLOCK DRAIN HOLES IN CASE OR GRILLE.)

IF GRILLE IS TO BE MOUNTED TO WALL SURFACE A SPLITTERS MUST BE USED, SEE PAGE 30.

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

ge.com

Image 31
Contents GE Zoneline packaged terminal air conditioners Quick Reference ALL Units Require Power Connection KITZoneline Chassis Nomenclature Power Connection KitsExample Cooling With Resistance Heat Deluxe Dry Air 25 ModelsNewest Innovation from GE Comparison of DRY AIR 25 DehumidificationTable of Contents Introduction Wall Case Optional Accessories of the Zoneline SystemZoneline System Chassis Room Cabinet.2 Zoneline Features2800 5800Features and Benefits Electronic Temperature Limiting Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Compressor Restart DelayCorrosion Protection Optional Easy Clean Air Discharge AreaUp-Front Air Filters Concealed Manual Vent ControlCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits Up resistance heat only Switches Description Left SwitchesSeries models only Heat Sentinel Diagnostics Switch SeriesCentral Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable RAK806 Universal Control Cover Label Field Wiring TerminalRemote Thermostat Control Resistance Heat ModelsCompressor Heater Common Ground Feature Heat Pump Electric HeatHeat Pump Models 24V ACRelay Designation For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Field-Supplied Relay SpecificationsBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 3800 and 5800 SeriesZoneline Heat Pump Heat Source Logic Heat pump defrost Zoneline 3800 and 5800 SeriesAir Distribution Application CommentsRAB77 Wall Case DimensionsWall Case with Chassis Installed RAB71A Wall CaseSub-Base Wall CaseChoice of wall cases is available for the Zoneline General Wall Case Installation DataBrick, Frame, Stucco Shingle Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Masonry Wall ConstructionCase Angles Preparation of the Wall Case for All Types of ConstructionFastening Wall Case Framing for Wall CaseBrick Veneer and Frame Construction Wall Section Detailed Side View Frame and Brick Veneer Installation Cord set connected22-3/8 22-1/4 Where it joinsGasket Caulk around Perimeter Wall case all 22-1/4 Four sides27-1/4 13-1/8 Power supplyAll four sides where it 42-1/8RAB71/77 4 ± 1/413-3/4 + D Ge.com TOP View RAB71/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsHigh Wide Ducted Application AZ2800/3800 SeriesRAK6052 RAK601Ducted Detailed Side Views AZ2800/3800 Series Outdoor Grille Exterior GrillesExterior Architectural Treatments Special Outdoor Grilles 230/208 Volt Sub-Base and Direct Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208-Volt Permanently Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 2800/3800/5800 SeriesEssential Elements Ordering Overview 230/208-Volt Line Cord Connected Units Maximum Connected LoadVolt Units Heat Pump Performance Data Cooling Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Latent System Capacity Indoor Ambient DB Temperature F 10093.00 Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataOutdoor Design Temperature Difference Installed unit capacity Btuh Watts/KWPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Premium Line 5800 Series Receptacles/Sub-BasesSpecifications RAB71A Complete Accessory ListGeneral Installation Suggestions New Installations Zoneline warrantyDucted Installation Comments Replacement InstallationsExterior Grille Color Samples Alphabetical IndexWarm Gray Beige Maple Bittersweet Chocolate GE Company Pub. No -S087 PC48947 Century of quality and innovation