GE 2800 manual Latent System Capacity, Indoor Ambient DB Temperature F 100, 93.00

Page 46

Latent System Capacity

The total capacity of an air conditioner is made up of the Sensible capacity, the output of the unit used to remove heat from the air in the area being conditioned, and the Latent capacity, the output of the unit used to dehumidify the air in the area being conditioned. For humid climates and applications, the Sensible/Latent capacity split of the unit should be considered. The Sensible capacity listed in the specification charts on page 55 is at a standard rating condition of 95°F dry bulb/75°F wet bulb outdoors; 80°F dry bulb/67°F wet bulb indoors. The Latent system capacity is

1.00minus the Sensible capacity. (If the Sensible capacity is listed at .74 the Latent capacity is .26. This means that 74% of the capacity of the unit is used to remove heat from the air and 26% is used to remove moisture form the air at standard test conditions.)

In some applications information about the Sensible/Latent split, or ratio, at conditions other than the standard rating conditions is needed. The chart below provides data at various indoor conditions.

Cooling Sensible Heat Ratio (SHR) at Various Indoor WB and DB Temperatures

MODEL

Indoor WB

 

 

 

Indoor Ambient DB Temperature (F)

 

 

 

(F)

60

65

70

75

80

85

 

90

95

100

 

 

All 7000 BTUH

59

0.51

0.67

0.83

0.99

1.00

1.00

 

1.00

1.00

1.00

units except

63

 

0.46

0.62

0.77

0.92

1.00

 

1.00

1.00

1.00

Dry Air 25

67

 

 

0.42

0.60

0.75

0.88

 

1.00

1.00

1.00

 

71

 

 

 

0.42

0.54

0.66

 

0.78

0.90

1.00

AZ28E07DAP/EAP

59

0.38

0.49

0.65

0.80

0.95

1.00

 

1.00

1.00

1.00

(Dry Air 25)

63

 

0.38

0.54

0.68

0.80

1.00

 

1.00

1.00

1.00

 

67

 

 

0.35

0.52

0.66

0.79

 

0.92

1.00

1.00

 

71

 

 

 

0.32

0.45

0.58

 

0.73

0.85

1.00

All 9000 BTUH

59

0.42

0.59

0.77

0.93

1.00

1.00

 

1.00

1.00

1.00

units except

63

 

0.40

0.55

0.70

0.83

0.96

 

1.00

1.00

1.00

Dry Air 25

67

 

 

0.42

0.55

0.68

0.81

 

0.93

1.00

1.00

 

71

 

 

 

0.38

0.49

0.60

 

0.71

0.82

0.93

AZ28E09DAP/EAP

59

0.30

0.45

0.60

0.75

0.92

1.00

 

1.00

1.00

1.00

(Dry Air 25)

63

 

0.32

0.42

0.57

0.73

0.90

 

1.00

1.00

1.00

 

67

 

 

0.32

0.45

0.58

0.70

 

0.85

1.00

1.00

 

71

 

 

 

0.30

0.38

0.48

 

0.61

0.74

0.85

All 12000 BTUH

59

0.38

0.54

0.71

0.88

1.00

1.00

 

1.00

1.00

1.00

units except

63

 

0.40

0.54

0.68

0.81

0.93

 

1.00

1.00

1.00

Dry Air 25

67

 

 

0.41

0.54

0.67

0.80

 

0.93

1.00

1.00

 

71

 

 

 

0.36

0.47

0.58

 

0.71

0.82

0.93

AZ28E12DAP/EAP

59

0.30

0.45

0.60

0.75

0.92

1.00

 

1.00

1.00

1.00

(Dry Air 25)

63

 

0.30

0.41

0.56

0.72

0.89

 

1.00

1.00

1.00

 

67

 

 

0.31

0.44

0.57

0.70

 

0.84

0.99

1.00

 

71

 

 

 

0.31

0.40

0.50

 

0.61

0.73

0.84

All 15000 BTUH

59

0.38

0.54

0.71

0.88

1.00

1.00

 

1.00

1.00

1.00

units except

63

 

0.40

0.54

0.68

0.81

93.00

 

1.00

1.00

1.00

Dry Air 25

67

 

 

0.41

0.54

0.67

0.80

 

0.93

1.00

1.00

 

71

 

 

 

0.36

0.47

0.58

 

0.71

0.82

0.93

Capacities are nominal capacity

46

Image 46
Contents GE Zoneline packaged terminal air conditioners ALL Units Require Power Connection KIT Quick ReferenceZoneline Chassis Nomenclature Power Connection KitsExample Comparison of DRY AIR 25 Dehumidification Deluxe Dry Air 25 ModelsNewest Innovation from GE Cooling With Resistance HeatTable of Contents Introduction Chassis Room Cabinet Optional Accessories of the Zoneline SystemZoneline System Wall Case5800 Zoneline Features2800 .2Features and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingConcealed Manual Vent Control Easy Clean Air Discharge AreaUp-Front Air Filters Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits Series Switches Description Left SwitchesSeries models only Heat Sentinel Diagnostics Switch Up resistance heat onlyCentral Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover Label24V AC Feature Heat Pump Electric HeatHeat Pump Models Compressor Heater Common GroundField-Supplied Relay Specifications For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Relay DesignationHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 3800 and 5800 Series Heat Pump Operation Zoneline 3800 and 5800 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateApplication Comments Air DistributionRAB71A Wall Case DimensionsWall Case with Chassis Installed RAB77 Wall CaseSub-Base Wall CaseChoice of wall cases is available for the Zoneline Wall Case Installation Data GeneralMasonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Case AnglesFastening Wall Case Framing for Wall CaseBrick Veneer and Frame Construction Frame and Brick Veneer Installation Cord set connected Wall Section Detailed Side View22-1/4 Four sides 22-1/4 Where it joinsGasket Caulk around Perimeter Wall case all 22-3/842-1/8 Power supplyAll four sides where it 27-1/4 13-1/8RAB71/77 4 ± 1/413-3/4 + D Ge.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsRAK601 Ducted Application AZ2800/3800 SeriesRAK6052 High WideDucted Detailed Side Views AZ2800/3800 Series Exterior Grilles Outdoor GrilleExterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 2800/3800/5800 SeriesEssential Elements Ordering Overview 230/208-Volt Line Cord Connected Units Maximum Connected LoadVolt Units Heat Pump Performance Data Cooling Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Latent System Capacity Indoor Ambient DB Temperature F 10093.00 Installed unit capacity Btuh Watts/KW Formula for Calculating Operating Costs Using Above DataOutdoor Design Temperature Difference Normal Yearly Operating DataPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Receptacles/Sub-Bases Premium Line 5800 SeriesSpecifications Complete Accessory List RAB71AGeneral Installation Suggestions Replacement Installations Zoneline warrantyDucted Installation Comments New InstallationsExterior Grille Color Samples Alphabetical IndexWarm Gray Beige Maple Bittersweet Chocolate Century of quality and innovation GE Company Pub. No -S087 PC48947