GE 2800 manual Up-Front Air Filters, Easy Clean Air Discharge Area, Concealed Manual Vent Control

Page 11

Features and Benefits

Up-Front Air Filters

Two interchangeable up-front filters, easy to remove and reinstall, may be cleaned without opening or removing the room front.

Clean filters by brushing, vacuuming or back- flushing under faucet or shower head.

Easy Clean Air Discharge Area

2800 and 3800 Series units have an out-of-sight vertical protective screen over the indoor fan. This allows easy cleaning of air discharge area by simply removing room front and wiping clean.

There is no screen directly below discharge louver to trap unsightly dirt and debris where it may be seen by room occupant.

Concealed Manual

Vent Control

The 3-position manual vent door control may be closed, partially open or fully open.

Vent CFM High Speed

Unit

Full Open

Partial Open

  7000

50

40

  9000

70

45

12000

75

45

15000

75

45

CFM ratings at 230 volts and 265 volts.

Greater amounts of air will be introduced if the room has an exhaust fan.

An open vent door brings unconditioned outdoor air into the room, increasing heating and cooling costs.

Positive vent door closure prevents accidental opening and unwanted air infiltration.

ge.com

Corrosion Protection (Optional)

2800 and 3800 Series units may be ordered with special protection to better withstand damage from salt air and salt water in seacoast areas.

Corrosion protection is standard on the 5800 Series and on Dry Air 25 models.

Heat Pump units with ICR are not available with corrosion protection and should not be installed in seacoast or corrosive environments.

Units installed in corrosive areas should be examined and cleaned more frequently than normal installations.

Internal Condensate Removal (ICR)

See page 34 for a discussion of the Internal Condensate Removal system available on 3800 and 5800 Series heat pumps.

Enhanced Dehumidification

Moisture removal is an important function of an air conditioner. People are more comfortable at higher temperatures when the humidity level is relatively low. Air conditioners operate with less energy consumption when the room temperatures are set higher.

The GE Zoneline® 2800 Series with the Dry Air 25 heat pipe application removes 25% more moisture than the base 2800 Series unit.

The GE Zoneline Dry Air 25 chassis is the only PTAC available with the application of the patented Dinh® Dehumidifier Heat Pipe under license from Heat Pipe Technology, Inc.

Customers who are using the Dry Air 25 report a fresher- smelling room as a result of the lower humidity levels, as well as lower operating costs.

Locking Door Kit

RAK8023 — A door with a lock that replaces the standard control cover door to prevent unauthorized changing of control setting is offered as an accessory.

11

Image 11
Contents GE Zoneline packaged terminal air conditioners Quick Reference ALL Units Require Power Connection KITExample Power Connection KitsZoneline Chassis Nomenclature Cooling With Resistance Heat Deluxe Dry Air 25 ModelsNewest Innovation from GE Comparison of DRY AIR 25 DehumidificationTable of Contents Introduction Wall Case Optional Accessories of the Zoneline SystemZoneline System Chassis Room Cabinet.2 Zoneline Features2800 5800Features and Benefits Electronic Temperature Limiting Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Compressor Restart DelayCorrosion Protection Optional Easy Clean Air Discharge AreaUp-Front Air Filters Concealed Manual Vent ControlHeating Temperature Limits Auxiliary Control SwitchesCooling Temperature Limits Up resistance heat only Switches Description Left SwitchesSeries models only Heat Sentinel Diagnostics Switch SeriesImportant CDC Comments all series applicable CDC Terminal Location and Typical WiringCentral Desk Control RAK806 Universal Control Cover Label Field Wiring TerminalRemote Thermostat Control Resistance Heat ModelsCompressor Heater Common Ground Feature Heat Pump Electric HeatHeat Pump Models 24V ACRelay Designation For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Field-Supplied Relay SpecificationsBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 3800 and 5800 SeriesZoneline Heat Pump Heat Source Logic Heat pump defrost Zoneline 3800 and 5800 SeriesAir Distribution Application CommentsRAB77 Wall Case DimensionsWall Case with Chassis Installed RAB71A Wall CaseChoice of wall cases is available for the Zoneline Wall CaseSub-Base General Wall Case Installation DataBrick, Frame, Stucco Shingle Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Masonry Wall ConstructionCase Angles Preparation of the Wall Case for All Types of ConstructionBrick Veneer and Frame Construction Framing for Wall CaseFastening Wall Case Wall Section Detailed Side View Frame and Brick Veneer Installation Cord set connected22-3/8 22-1/4 Where it joinsGasket Caulk around Perimeter Wall case all 22-1/4 Four sides27-1/4 13-1/8 Power supplyAll four sides where it 42-1/813-3/4 + D 4 ± 1/4RAB71/77 Ge.com TOP View RAB71/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsHigh Wide Ducted Application AZ2800/3800 SeriesRAK6052 RAK601Ducted Detailed Side Views AZ2800/3800 Series Outdoor Grille Exterior GrillesExterior Architectural Treatments Special Outdoor Grilles 230/208 Volt Sub-Base and Direct Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208-Volt Permanently Connected UnitsEssential Elements Ordering Overview Electrical Wiring Information 2800/3800/5800 SeriesReplacement of Existing Chassis Volt Units Maximum Connected Load230/208-Volt Line Cord Connected Units Total Capacity Btuh Btuh at 80º F D.B. 67º F W.B Cooling Performance DataHeat Pump Performance Data 93.00 Indoor Ambient DB Temperature F 100Latent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataOutdoor Design Temperature Difference Installed unit capacity Btuh Watts/KWPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Premium Line 5800 Series Receptacles/Sub-BasesSpecifications RAB71A Complete Accessory ListGeneral Installation Suggestions New Installations Zoneline warrantyDucted Installation Comments Replacement InstallationsWarm Gray Beige Maple Bittersweet Chocolate Alphabetical IndexExterior Grille Color Samples GE Company Pub. No -S087 PC48947 Century of quality and innovation