METAL CASE EXTENSION FOR WALLS DEEPER THAN 13-1/8" (11-1/8" WITH SUB-BASE)

Field fabricated – ge recommends the use of one of the deeper RAB71 wall cases offered as special order items.

Zoneline units can be installed in walls of greater depth than the wall case. Where the case recession is less than 3" and where it is possible to waterproof the exposed sides and top of the opening, the suggested procedure is to apply a flashing to the bottom of the wall case as shown on page 31. Where waterproofing is questionable or not possible, or for installations in walls of greater depth, the following is a suggested application procedure. It involves the field fabrication of a case extension. Since the wall case is a water bearing container, the extension likewise must also be water bearing and the connection between the two must be watertight. The case extension must contain splitters to prevent recirculation of the outdoor air circuit.

1.The case extension is field fabricated. The extension depth “D” should allow for a minimum outdoor projection of 1/4". This allows for room cabinet clearance to the finished wall and ample surfaces to apply sealant or caulking for a tight weather seal between the completed wall case/extension assembly and the wall opening. It is recommended that the extension be painted and corner and lap joints be additionally sealed with a quality grade sealant.

2.The wall case and extension should be connected prior to installation in the wall opening. A quality grade sealant should be applied to all four (4) butting flanges. Use bolts and nuts or oversized self tapping screws (driven from the wall case to the extension) to attach the two assemblies. Clean all drain holes of excess sealant. The assembly must be free draining.

3.Install flashing, using a quality grade sealant between the flashing and wall as shown in section A-A below.

4.Install the wall case/extension assembly following procedures described for a standard installation. See diagrams below. The assembly should be sealed or caulked to the wall around all four sides both outdoors and indoors.

NOTE: The wall case/extension assembly should be level.

6-1/4" ± 1/4"

AS REQ'D.

SEALANT - ALL

 

 

D

 

 

 

 

 

 

 

 

 

FOUR (4) FLANGES

 

 

 

 

 

5.Suggested materials for case extension and flashing should be non-ferrous metals. Minimal acceptable material: Galvanized G-90 painted.

 

WALL -

 

ANY

CAULK*

CONSTRUCTION

ROOM

 

RAB71/77

CASE

CABINET

 

 

EXT.

 

 

 

 

 

 

 

 

1/4" MIN.

CAULK*

CAULK*

SPLITTER BETWEEN

AIR INTAKE AND

DISCHARGE

 

 

CUT DRAIN SLOTS

 

1-1/2"

IN BOTH FLANGES

 

(FOUR REQUIRED)

RAB71/77

(4 SIDES)

TO MATCH DRAIN

WALL CASE

EXTENSION

HOLES IN RAB71/77

 

(FIELD

 

 

SUPPLIED)

 

CAULK*

SEE DETAIL

SECTION A-A

*Caulk around perimeter of wall case all four sides where it joins the building - Interior and Exterior.

SECTION A-A

BASEPAN/FLANGE DESIGN

SHOWING SEALANT LOCATIONS.

ALL 4 FLANGES

EXTENSION

 

WALL CASE

 

2" MIN.

FLASHING (FIELD SUPPLIED)

13-3/4" + D"

ALL 4

SIDES

FLANGES AND

DRAIN HOLE

LOCATIONS

SAME AS ON

WALL CASE

1" WIDE

45° DRIP LIP

FLASHING

ALL 4

SIDES

 

WALL

 

Image 30
Contents GE Zoneline packaged terminal air conditioners ALL Units Require Power Connection KIT Quick ReferencePower Connection Kits Zoneline Chassis NomenclatureExample Comparison of DRY AIR 25 Dehumidification Deluxe Dry Air 25 ModelsNewest Innovation from GE Cooling With Resistance HeatTable of Contents Introduction Chassis Room Cabinet Optional Accessories of the Zoneline SystemZoneline System Wall Case5800 Zoneline Features2800 .2Features and Benefits Compressor Restart Delay Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Electronic Temperature LimitingConcealed Manual Vent Control Easy Clean Air Discharge AreaUp-Front Air Filters Corrosion Protection OptionalAuxiliary Control Switches Cooling Temperature LimitsHeating Temperature Limits Series Switches Description Left SwitchesSeries models only Heat Sentinel Diagnostics Switch Up resistance heat onlyCDC Terminal Location and Typical Wiring Central Desk ControlImportant CDC Comments all series applicable Resistance Heat Models Field Wiring TerminalRemote Thermostat Control RAK806 Universal Control Cover Label24V AC Feature Heat Pump Electric HeatHeat Pump Models Compressor Heater Common GroundField-Supplied Relay Specifications For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Relay DesignationHeat Pumps and Energy Savings Balance PointHeat pump defrost Zoneline 3800 and 5800 Series Heat Pump Operation Zoneline 3800 and 5800 SeriesZoneline Heat Pump Heat Source Logic Heat pump condensateApplication Comments Air DistributionRAB71A Wall Case DimensionsWall Case with Chassis Installed RAB77 Wall CaseWall Case Sub-BaseChoice of wall cases is available for the Zoneline Wall Case Installation Data GeneralMasonry Wall Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Brick, Frame, Stucco Shingle ConstructionPreparation of the Wall Case for All Types of Construction Case AnglesFraming for Wall Case Fastening Wall CaseBrick Veneer and Frame Construction Frame and Brick Veneer Installation Cord set connected Wall Section Detailed Side View22-1/4 Four sides 22-1/4 Where it joinsGasket Caulk around Perimeter Wall case all 22-3/842-1/8 Power supplyAll four sides where it 27-1/4 13-1/84 ± 1/4 RAB71/7713-3/4 + D Ge.com TOP View RAK204 Series SUB-BASE Installation and Electrical Data RAB71/77 Wall CaseCondensate Disposal Systems Wall Case with RAD10 Drain KIT External Drain. See page 36 for internal drainInternal Drain. See page 35 for external drain Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsRAK601 Ducted Application AZ2800/3800 SeriesRAK6052 High WideDucted Detailed Side Views AZ2800/3800 Series Exterior Grilles Outdoor GrilleExterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Permanently Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsElectrical Wiring Information 2800/3800/5800 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load 230/208-Volt Line Cord Connected UnitsVolt Units Cooling Performance Data Heat Pump Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Indoor Ambient DB Temperature F 100 Latent System Capacity93.00 Installed unit capacity Btuh Watts/KW Formula for Calculating Operating Costs Using Above DataOutdoor Design Temperature Difference Normal Yearly Operating DataPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Receptacles/Sub-Bases Premium Line 5800 SeriesSpecifications Complete Accessory List RAB71AGeneral Installation Suggestions Replacement Installations Zoneline warrantyDucted Installation Comments New InstallationsAlphabetical Index Exterior Grille Color SamplesWarm Gray Beige Maple Bittersweet Chocolate Century of quality and innovation GE Company Pub. No -S087 PC48947