GE 2800 manual Features and Benefits

Page 9

Features and Benefits

Standard Physical Dimensions

GE has maintained the same dimensions since 1961 — 42" wide x 16" high x 13-3/4" deep

Replacement of older units is made easy.

Weather-Protected Electrical Components

Vital electrical components are protected from the weather by locating them on the indoor side of the weather barrier.

Weather-Resistant “Superseal”

Properly installed unit in undistorted case keeps air leakage to a minimum.

7 CFM air infiltration with 25 MPH wind on non-ICR units — 10 CFM on units with ICR.

Industry specification is 19 CFM of air infiltration.

Heater Sizes to Meet Room Requirements

All units are equipped with a universal heater — the resistance heat output is determined by power connection kit.

230/208-volt — Line Cord Connected Units — 2.55/2.09 KW with RAK3153 — 15-amp circuit; 3.45/2.82 KW with RAK3203 — 20-amp circuit; 5.0/4.09 KW with RAK3303 — 30-amp circuit.

230/208-volt - Sub-Base Connected Units — 2.55/2.09 KW with RAK204D15P — 15-amp circuit; 3.45/2.82 KW with RAK204D20P — 20-amp circuit; 5.0/4.09 KW with RAK204D30P — 30-amp circuit.

265-volt — 2.55 KW with RAK5172 — 15-amp circuit; 3.45 KW with RAK5202 — 20-amp circuit; 5.0 KW with RAK5302 — 30-amp circuit.

Unit Controls

2800 and 3800 Series — locked-in-place rotary knobs for temperature and operation selection.

5800 Series — touch pad controls with digital readout of temperature set point.

Highly Featured Microprocessor Controls

Microprocessor controls are programmed to interface with the temperature sensors to maximize comfort conditions for the room occupant and provide outstanding features.

Thermistors are used to sense small changes in temperature to give excellent room control and allow the microprocessor to monitor and react to changing conditions.

Electric Resistance Heat Lock-Out

To maximize the savings of the heat pump operation, the Zoneline heat pumps do not utilize the resistance heater when the outdoor temperature is above 46°F during normal operation. The resistance heat is used in the Quick Heat Recovery feature.

Automatic Emergency Heat

Automatically uses electric resistance heat if the heat pump output is not sufficient to maintain selected room temperature.

ge.com

Reverse Cycle Heat Pump Defrost System

Standard on all Zoneline 3800 and 5800 Series heat pumps.

Enables heat pump to operate at lower temperatures when other systems switch to more expensive electric resistance heat.

See pages 18 and 19 for discussion of heat pump operation and defrost systems.

High Temperature Heat Pump Operation Protection

Automatically protects the compressor if heat pump is operated with high outdoor temperatures.

Power to the outdoor fan is turned off if the indoor coil gets too hot during heat pump operation to prevent damage to the compressor.

Quick Heat Recovery – Heat Pump Units

When the unit operation is changed from STOP or COOL to HEAT, the electric resistance heaters are used to warm the room to the thermostat set point. This provides faster room temperature increase for greater guest comfort.

Unit Diagnostics

The 5800 Series has a dip switch that activates each of the various components of the unit to operate briefly. This enables the technician to determine if individual components are functioning properly.

Service Indicator

On the 5800 Series, if the microprocessor detects a compressor malfunction, the digital temperature display will blink. If the malfunction occurs during cooling operation, the indoor fan will continue to operate. If the compressor malfunctions in heating mode, the unit will automatically switch to resistance heat to maintain room temperature set point. GE Service should be called to check the Zoneline.

Fan Motors – Permanently Lubricated

All units have two fan motors for quiet operation and maximum operating efficiency.

Motors are permanently lubricated to reduce maintenance and totally enclosed to keep dirt and water out of the motor windings.

2-Speed Outdoor Fan

The unit automatically selects the most efficient speed for the outdoor fan. The operating sound level is lower when the outdoor fan can operate in low speed yet there are situations where it must operate in high speed. The unit changes the fan speed automatically.

Indoor Fan Speed Selections – HIGH/LOW

Unit may be operated in HIGH HEAT or LOW HEAT or HIGH COOL or LOW COOL.

Image 9
Contents GE Zoneline packaged terminal air conditioners Quick Reference ALL Units Require Power Connection KITPower Connection Kits Zoneline Chassis NomenclatureExample Newest Innovation from GE Deluxe Dry Air 25 ModelsComparison of DRY AIR 25 Dehumidification Cooling With Resistance HeatTable of Contents Introduction Zoneline System Optional Accessories of the Zoneline SystemChassis Room Cabinet Wall Case2800 Zoneline Features5800 .2Features and Benefits Fan-Cycle Switch SmartFan Fan-Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Easy Clean Air Discharge AreaConcealed Manual Vent Control Corrosion Protection OptionalAuxiliary Control Switches Cooling Temperature LimitsHeating Temperature Limits Series models only Heat Sentinel Diagnostics Switch Switches Description Left SwitchesSeries Up resistance heat onlyCDC Terminal Location and Typical Wiring Central Desk ControlImportant CDC Comments all series applicable Remote Thermostat Control Field Wiring TerminalResistance Heat Models RAK806 Universal Control Cover LabelHeat Pump Models Feature Heat Pump Electric Heat24V AC Compressor Heater Common GroundRemote Control Low Voltage Wiring For Use With Mechanical 4-Wire Systems OnlyField-Supplied Relay Specifications Relay DesignationBalance Point Heat Pumps and Energy SavingsZoneline Heat Pump Heat Source Logic Heat Pump Operation Zoneline 3800 and 5800 SeriesHeat pump defrost Zoneline 3800 and 5800 Series Heat pump condensateAir Distribution Application CommentsWall Case with Chassis Installed DimensionsRAB71A Wall Case RAB77 Wall CaseWall Case Sub-BaseChoice of wall cases is available for the Zoneline General Wall Case Installation DataWindow, Curtain and Panel Wall Construction Architectural Window Louver InstallationMasonry Wall Construction Brick, Frame, Stucco Shingle ConstructionCase Angles Preparation of the Wall Case for All Types of ConstructionFraming for Wall Case Fastening Wall CaseBrick Veneer and Frame Construction Wall Section Detailed Side View Frame and Brick Veneer Installation Cord set connectedGasket Caulk around Perimeter Wall case all 22-1/4 Where it joins22-1/4 Four sides 22-3/8All four sides where it Power supply42-1/8 27-1/4 13-1/84 ± 1/4 RAB71/7713-3/4 + D Ge.com TOP View RAB71/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsRAK6052 Ducted Application AZ2800/3800 SeriesRAK601 High WideDucted Detailed Side Views AZ2800/3800 Series Outdoor Grille Exterior GrillesExterior Architectural Treatments Special Outdoor Grilles 230/208-Volt Line-Cord Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Permanently Connected Units 230/208 Volt Sub-Base and Direct Connected UnitsElectrical Wiring Information 2800/3800/5800 Series Replacement of Existing ChassisEssential Elements Ordering Overview Maximum Connected Load 230/208-Volt Line Cord Connected UnitsVolt Units Cooling Performance Data Heat Pump Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Indoor Ambient DB Temperature F 100 Latent System Capacity93.00 Outdoor Design Temperature Difference Formula for Calculating Operating Costs Using Above DataInstalled unit capacity Btuh Watts/KW Normal Yearly Operating DataPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Premium Line 5800 Series Receptacles/Sub-BasesSpecifications RAB71A Complete Accessory ListGeneral Installation Suggestions Ducted Installation Comments Zoneline warrantyReplacement Installations New InstallationsAlphabetical Index Exterior Grille Color SamplesWarm Gray Beige Maple Bittersweet Chocolate GE Company Pub. No -S087 PC48947 Century of quality and innovation