230/208-volt line-cord connected units — order line cord kit.
Electrical Wiring Information – 2800/3800/5800 Series
All Zonelines are
For all installations, the feeder,
Maximum connected load in amperes, including demands for the electric heater and the fan motor, are shown on page
44.Branch circuit ampacity and electrical protective device sizing are shown on page 42 for
More than one unit per branch circuit is not recommended. When in doubt, consult the National Electrical Code. All wiring, including installation of receptacle, must conform to local electrical regulations and codes.
Replacement of Existing Chassis
230/208-Volt and 265-Volt Units
There have been changes to NEC and improvements and modifications to the Zoneline chassis and
Line-Cord Connected Units
The plug configuration of new line cord connected units complies with the current NEC standards. Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuration of the plug on the new line cord. The recommended solution is to change the wall receptacle to conform to current standard plug configuration. See chart on this page for current receptacle configuration.
ge.com
Permanent Connected Units With Sub-Base
If the existing unit is connected to a
If the existing
If the existing
Enclosure cover removed.
RAK4002A
Wiring harness can be ordered separately as RAK4002CW.
Receptacle
Type | Mfg | Part No | Configuration | ||||
|
|
|
|
|
|
|
|
15 AMP | Hubbell | 5661 |
|
|
|
|
|
Typical Line Cord Power Connection Kit RAK3203 shown
58" |
21" |
Inside |
Maximum Cord Extension
Tandem | P&S | 5661 |
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
20 AMP | Hubbell | 5461 |
|
|
|
|
|
|
|
|
|
| |||
Perpendicular |
|
|
|
|
| ||
P&S | 5871 |
|
|
|
|
| |
|
|
|
|
| |||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
30 AMP | Hubbell | 9330 |
|
|
|
|
|
Large Tandem |
|
|
|
|
| ||
P&S | 5930 |
|
|
|
|
| |
|
|
|
|
| |||
|
|
|
|
|
|
|
43