GE Essential Elements Ordering Overview, Electrical Wiring Information 2800/3800/5800 Series

Page 43

Essential Elements Ordering Overview

230/208-volt line-cord connected units — order line cord kit.

230/208-volt sub-base connected units — order sub-base (includes power connection kit) and junction box for chassis.

265-volt units — order sub-base and power connection kit separately.

Electrical Wiring Information – 2800/3800/5800 Series

All Zonelines are single-phase 60 hertz units.

For all installations, the feeder, sub-feeder, branch circuit and electrical protective devices and selection must conform to the National Electrical Code and to local codes.

Maximum connected load in amperes, including demands for the electric heater and the fan motor, are shown on page

44.Branch circuit ampacity and electrical protective device sizing are shown on page 42 for 230/208-volt units and on this page for 265-volt units.

More than one unit per branch circuit is not recommended. When in doubt, consult the National Electrical Code. All wiring, including installation of receptacle, must conform to local electrical regulations and codes.

Replacement of Existing Chassis

230/208-Volt and 265-Volt Units

There have been changes to NEC and improvements and modifications to the Zoneline chassis and sub-bases since the unit was first introduced. Some of these changes require alterations to be made when replacing an older unit with a new chassis.

Line-Cord Connected Units

The plug configuration of new line cord connected units complies with the current NEC standards. Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuration of the plug on the new line cord. The recommended solution is to change the wall receptacle to conform to current standard plug configuration. See chart on this page for current receptacle configuration.

ge.com

Permanent Connected Units With Sub-Base

If the existing unit is connected to a sub-base the installation of the new unit may involve modifying the existing installation slightly. It is recommended these modifications be made by a qualified electrician.

If the existing sub-base is the full width of the wall case, RAK201 sub-base access plate may be ordered and used to replace the cover on the old sub-base. Field-supplied wiring, conduit and conduit connectors should be used to make a connection between the new chassis and the center knockout of the RAK201. The wiring connections should be made inside the sub-base and the RAK201 attached to the sub-base with the two screws provided.

If the existing sub-base is not the full width of the wall case, the electrician will have to modify the existing cover plate to allow field-supplied wiring, conduit and conduit connectors to be run from the permanent connection kit to the sub-base.

Enclosure cover removed.

RAK4002A

Wiring harness can be ordered separately as RAK4002CW.

Receptacle

Type

Mfg

Part No

Configuration

 

 

 

 

 

 

 

 

15 AMP

Hubbell

5661

 

 

 

 

 

Typical Line Cord Power Connection Kit RAK3203 shown

58"

21"

Inside

Maximum Cord Extension

Tandem

P&S

5661

 

 

 

 

 

NEMA6-15R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 AMP

Hubbell

5461

 

 

 

 

 

 

 

 

 

 

Perpendicular

 

 

 

 

 

P&S

5871

 

 

 

 

 

NEMA6-20R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 AMP

Hubbell

9330

 

 

 

 

 

Large Tandem

 

 

 

 

 

P&S

5930

 

 

 

 

 

NEMA6-30R

 

 

 

 

 

 

 

 

 

 

 

 

43

Image 43
Contents GE Zoneline packaged terminal air conditioners Quick Reference ALL Units Require Power Connection KITZoneline Chassis Nomenclature Power Connection KitsExample Cooling With Resistance Heat Deluxe Dry Air 25 ModelsNewest Innovation from GE Comparison of DRY AIR 25 DehumidificationTable of Contents Introduction Wall Case Optional Accessories of the Zoneline SystemZoneline System Chassis Room Cabinet.2 Zoneline Features2800 5800Features and Benefits Electronic Temperature Limiting Fan-Only Setting HIGH/LOWFan-Cycle Switch SmartFan Compressor Restart DelayCorrosion Protection Optional Easy Clean Air Discharge AreaUp-Front Air Filters Concealed Manual Vent ControlCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits Up resistance heat only Switches Description Left SwitchesSeries models only Heat Sentinel Diagnostics Switch SeriesCentral Desk Control CDC Terminal Location and Typical WiringImportant CDC Comments all series applicable RAK806 Universal Control Cover Label Field Wiring TerminalRemote Thermostat Control Resistance Heat ModelsCompressor Heater Common Ground Feature Heat Pump Electric HeatHeat Pump Models 24V ACRelay Designation For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Field-Supplied Relay SpecificationsBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 3800 and 5800 SeriesZoneline Heat Pump Heat Source Logic Heat pump defrost Zoneline 3800 and 5800 SeriesAir Distribution Application CommentsRAB77 Wall Case DimensionsWall Case with Chassis Installed RAB71A Wall CaseSub-Base Wall CaseChoice of wall cases is available for the Zoneline General Wall Case Installation DataBrick, Frame, Stucco Shingle Construction Architectural Window Louver InstallationWindow, Curtain and Panel Wall Construction Masonry Wall ConstructionCase Angles Preparation of the Wall Case for All Types of ConstructionFastening Wall Case Framing for Wall CaseBrick Veneer and Frame Construction Wall Section Detailed Side View Frame and Brick Veneer Installation Cord set connected22-3/8 22-1/4 Where it joinsGasket Caulk around Perimeter Wall case all 22-1/4 Four sides27-1/4 13-1/8 Power supplyAll four sides where it 42-1/8RAB71/77 4 ± 1/413-3/4 + D Ge.com TOP View RAB71/77 Wall Case RAK204 Series SUB-BASE Installation and Electrical DataCondensate Disposal Systems External Drain. See page 36 for internal drain Wall Case with RAD10 Drain KITInternal Drain. See page 35 for external drain Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsHigh Wide Ducted Application AZ2800/3800 SeriesRAK6052 RAK601Ducted Detailed Side Views AZ2800/3800 Series Outdoor Grille Exterior GrillesExterior Architectural Treatments Special Outdoor Grilles 230/208 Volt Sub-Base and Direct Connected Units Or 277-Volt Unit Installation Permanently Connected Units230/208-Volt Line-Cord Connected Units 230/208-Volt Permanently Connected UnitsReplacement of Existing Chassis Electrical Wiring Information 2800/3800/5800 SeriesEssential Elements Ordering Overview 230/208-Volt Line Cord Connected Units Maximum Connected LoadVolt Units Heat Pump Performance Data Cooling Performance DataTotal Capacity Btuh Btuh at 80º F D.B. 67º F W.B Latent System Capacity Indoor Ambient DB Temperature F 10093.00 Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataOutdoor Design Temperature Difference Installed unit capacity Btuh Watts/KWPage Ge.com Typical 5800 Series Schematic Diagram Suggested Bid Form Specifications Suggested Bid Form Specifications Suggested Bid Form Specifications Premium Line 5800 Series Receptacles/Sub-BasesSpecifications RAB71A Complete Accessory ListGeneral Installation Suggestions New Installations Zoneline warrantyDucted Installation Comments Replacement InstallationsExterior Grille Color Samples Alphabetical IndexWarm Gray Beige Maple Bittersweet Chocolate GE Company Pub. No -S087 PC48947 Century of quality and innovation