Installation

Installation

Where to locate the equipment

When deciding where to locate the equipment, consider your cooling needs, air flow, the location of the electrical outlet (no more than 2.4 m (8 ft) from the equipment), and access for the condenser intake and exhaust.

Cooling needs. Position the equipment as close as possible to the main source of heat that requires cooling.

Air flow. Position the equipment so that its rear is at least 200 mm (8 in) away from a wall or other equipment.

Location of electrical outlet. Place the equipment no farther than 2.4 m (8 ft) from a dedicated 115V, 60Hz, 20A branch circuit receptacle.

na0143a

Dimensions are shown in mm (in).

Electrical Hazard: Do not use extension cords with this equipment. Using an extention cord reduces circuit protection and voids the warranty.

Caution: To help avoid loss of cooling, only connect this equipment to a single-outlet dedicated circuit.

Lock the rolling casters

To prevent the equipment from rolling, press down on the locking tabs on the two front casters.

na0176a

NetworkAIR ACPA4000

7

Image 15
Contents ACPA4000 Installation, Operation, and MaintenanceNetworkAIR Portable Air Conditioning Unit Page American Power Conversion Legal Disclaimer Page Installation General InformationContents Operation Maintenance and Troubleshooting Page About the NetworkAIR ACPA4000 General InformationOverview Manual updatesCross-referencesymbol used in this manual Safety symbols that may be used in this manualFiling a claim Storing the Equipment Before InstallationInspecting the Equipment SafetyTools Required InventoryThe equipment ships with the items shown below Component Identification Front viewRear view Shipping Weight Dimensions and WeightsDimensions are shown in mm in Net WeightInstallation Where to locate the equipmentLock the rolling casters Intake and Exhaust Vents Hose connectionsAssemble the ceiling adapter NetworkAIR ACPA4000 Install the adapter in a drop ceilingAssemble the ducts Drain Line Connect the fitting to the drain lineAttach the drain line. Attach Temperature/humidity sensor AccessoriesRelays and Contacts OverviewOutput relays Input contacts To connect an output relayTo connect an input contact Start-Up Start-upchecklistHow to apply power to the equipment Operation OverviewDisplay interface identification How to Use the Interface Turn on the equipmentScrolling status screens Date 18-Jun-2007 Time Main menu screenNavigating the interface Date 18-Jun-2007 TimeChange settings Password entryTurn off the equipment Default schedule Set Environmental ControlsMode Operating schedulesSchedule 1 of Schedule On/OffSet Up Alarms Temperature and humidity alarmsSet the alarm delay Display interface options Set Up the DisplayPassword and time-out Set the date and timePath Main Menu Setup Factory Defaults Device settingsResetting to default settings Path Main Menu Setup System DeviceHow to download firmware User outputs Set Up Contacts and RelaysInput contacts User input contactsSystem and environmental status screens Checking Equipment StatusDefault schedule status Scrolling status screensManufacturer data Viewing alarm statusWarning or alarm LED Responding to AlarmsSilencing the alarm beeper Silence Active AlarmActive alarm screen Alarm and event logResolving alarm conditions Alarm messages Alarm MessageAction Required Alarm Message Action RequiredRemote temperature Monitoring information Display Interface Reference ChartsSetup Scrolling status screensControl Environment Programmable settingsSetup StatusSystem SetupMaintenance and Troubleshooting MaintenanceReplace the air filter Clean the condenser filter and test the LCDI plug Clean the cabinetUpdate the main control board firmware Corrective action TroubleshootingProblem Possible causeExclusions One-YearFactory WarrantyTerms of warranty Non-transferablewarrantyWarranty claims Warranty Procedures ClaimsParts Component Type SpecificationsElectrical PhysicalPage 03/2008 990-0412DAPC Worldwide Customer Support 990-0412D