Alarm messages

Alarm Message

Action Required

 

 

High head pressure

Ensure condenser exhaust air diverter is not blocked, facing a wall, or

 

pointed at the condenser air inlet.

 

Check the area above the ceiling where the condenser air is circulating

 

for excessive heat buildup. Additional ventilation may be required.

 

Check the condenser inlet filter for cleanliness.

 

 

Supply temperature

Alarm setpoint may be too low. Alarm should normally be set to 10° (C

high

or F) above the cool setpoint plus the dead band.

 

Check that the unit is in cool mode and the compressor is running.

 

 

Supply temperature

Alarm setpoint may be too high.

low

Front airflow may be obstructed. Check the return air filter for

 

cleanliness. Check the front discharge air grille for free air movement.

 

Cooling setpoint may be too low to allow for at least an 11°C (20°F)

 

temperature differential between return and supply temperatures.

 

Example: A setpoint of 21.1°C (70°F) could have a supply temperature

 

as low as 10°C (50°F).

 

 

Return temperature

Alarm setpoint may be too low.

high

Check that the unit is in cool mode and the compressor is running.

 

 

Equipment capacity may be too small for room load.

 

Ensure that return air (air coming back to the equipment) is not from a

 

direct heat source, equipment discharge fan, or room supply duct.

 

Alarm delay may be too short. Sufficient time must be allowed to let the

 

equipment bring the temperature in the space under control. This is

 

especially true at equipment start-up.

 

 

Return temperature

Alarm setpoint may be too high.

low

Verify that the return air is not coming from a cold air supply source such

 

 

as a room discharge duct.

 

There should not be any obstructions near the grill front that could divert

 

supply air back to the return air grill.

 

 

NetworkAIR ACPA4000

31

Image 39
Contents ACPA4000 Installation, Operation, and MaintenanceNetworkAIR Portable Air Conditioning Unit Page American Power Conversion Legal Disclaimer Page Installation General InformationContents Operation Maintenance and Troubleshooting Page About the NetworkAIR ACPA4000 General InformationOverview Manual updatesCross-referencesymbol used in this manual Safety symbols that may be used in this manualFiling a claim Storing the Equipment Before InstallationInspecting the Equipment SafetyTools Required InventoryThe equipment ships with the items shown below Component Identification Front viewRear view Shipping Weight Dimensions and WeightsDimensions are shown in mm in Net WeightInstallation Where to locate the equipmentLock the rolling casters Intake and Exhaust Vents Hose connectionsAssemble the ceiling adapter NetworkAIR ACPA4000 Install the adapter in a drop ceilingAssemble the ducts Drain Line Connect the fitting to the drain lineAttach the drain line. Attach Temperature/humidity sensor AccessoriesRelays and Contacts OverviewOutput relays Input contacts To connect an output relayTo connect an input contact Start-Up Start-upchecklistHow to apply power to the equipment Operation OverviewDisplay interface identification How to Use the Interface Turn on the equipmentScrolling status screens Date 18-Jun-2007 Time Main menu screenNavigating the interface Date 18-Jun-2007 TimeChange settings Password entryTurn off the equipment Default schedule Set Environmental ControlsMode Operating schedulesSchedule 1 of Schedule On/OffSet Up Alarms Temperature and humidity alarmsSet the alarm delay Display interface options Set Up the DisplayPassword and time-out Set the date and timePath Main Menu Setup Factory Defaults Device settingsResetting to default settings Path Main Menu Setup System DeviceHow to download firmware User outputs Set Up Contacts and RelaysInput contacts User input contactsSystem and environmental status screens Checking Equipment StatusDefault schedule status Scrolling status screensManufacturer data Viewing alarm statusWarning or alarm LED Responding to AlarmsSilencing the alarm beeper Silence Active AlarmActive alarm screen Alarm and event logResolving alarm conditions Alarm messages Alarm MessageAction Required Alarm Message Action RequiredRemote temperature Monitoring information Display Interface Reference ChartsSetup Scrolling status screensControl Environment Programmable settingsSetup StatusSystem SetupMaintenance and Troubleshooting MaintenanceReplace the air filter Clean the condenser filter and test the LCDI plug Clean the cabinetUpdate the main control board firmware Corrective action TroubleshootingProblem Possible causeExclusions One-YearFactory WarrantyTerms of warranty Non-transferablewarrantyWarranty claims Warranty Procedures ClaimsParts Component Type SpecificationsElectrical PhysicalPage 03/2008 990-0412DAPC Worldwide Customer Support 990-0412D