APC ACPA4000 manual Accessories, Temperature/humidity sensor

Page 20
Accessories

Accessories

Temperature/humidity sensor

The Remote Temperature/humidity sensor (AP9512TH) monitors the room temperature and relative humidity. This remote sensor monitors the environment surrounding the cooling equipment to ensure that the conditioned air is cooling the desired area.

Note: The equipment cannot be controlled based on the temperature measured by the sensor.

To install the sensor:

1.Determine a location that allows you to neatly route and secure the 3.66-m (12-ft) cord near the heat source you want to control.

Note: Avoid locating the sensor in areas that could give you an inaccurate reading such as near air ducts, other heat sources, windows, direct sunlight, or room entrances.

2. Attach the sensor to a wall or other surface with the provided hook-and-loop fasteners.

3. Neatly route and secure the 3.66-m

(12-ft) cord with wire tie or cable clips.

4. Connect the sensor to the controller board at the rear of the equipment.

na0174a

12

NetworkAIR ACPA4000

Image 20
Contents NetworkAIR Portable Air Conditioning Unit ACPA4000Installation, Operation, and Maintenance Page American Power Conversion Legal Disclaimer Page Contents InstallationGeneral Information Operation Maintenance and Troubleshooting Page General Information OverviewManual updates About the NetworkAIR ACPA4000Safety symbols that may be used in this manual Cross-referencesymbol used in this manualStoring the Equipment Before Installation Inspecting the EquipmentSafety Filing a claimThe equipment ships with the items shown below Tools RequiredInventory Rear view Component IdentificationFront view Dimensions and Weights Dimensions are shown in mm inNet Weight Shipping WeightLock the rolling casters InstallationWhere to locate the equipment Assemble the ceiling adapter Intake and Exhaust VentsHose connections Install the adapter in a drop ceiling NetworkAIR ACPA4000Assemble the ducts Attach the drain line. Attach Drain LineConnect the fitting to the drain line Accessories Temperature/humidity sensorOutput relays Relays and ContactsOverview To connect an input contact Input contactsTo connect an output relay How to apply power to the equipment Start-UpStart-upchecklist Display interface identification OperationOverview Scrolling status screens How to Use the InterfaceTurn on the equipment Main menu screen Navigating the interfaceDate 18-Jun-2007 Time Date 18-Jun-2007 TimeTurn off the equipment Change settingsPassword entry Set Environmental Controls Default scheduleOperating schedules Schedule 1 ofSchedule On/Off ModeSet the alarm delay Set Up AlarmsTemperature and humidity alarms Set Up the Display Password and time-outSet the date and time Display interface optionsDevice settings Resetting to default settingsPath Main Menu Setup System Device Path Main Menu Setup Factory DefaultsHow to download firmware Set Up Contacts and Relays Input contactsUser input contacts User outputsChecking Equipment Status Default schedule statusScrolling status screens System and environmental status screensViewing alarm status Manufacturer dataResponding to Alarms Silencing the alarm beeperSilence Active Alarm Warning or alarm LEDResolving alarm conditions Active alarm screenAlarm and event log Action Required Alarm messagesAlarm Message Remote temperature Alarm MessageAction Required Display Interface Reference Charts SetupScrolling status screens Monitoring informationProgrammable settings SetupStatus Control EnvironmentSetup SystemReplace the air filter Maintenance and TroubleshootingMaintenance Update the main control board firmware Clean the condenser filter and test the LCDI plugClean the cabinet Troubleshooting ProblemPossible cause Corrective actionOne-YearFactory Warranty Terms of warrantyNon-transferablewarranty ExclusionsWarranty claims Parts Warranty ProceduresClaims Specifications ElectricalPhysical Component TypePage 990-0412D APC Worldwide Customer Support990-0412D 03/2008