Operating schedules

Operating schedules

Path: Main Menu > Setup > Operating Schedule. Program up to eight sets of environmental controls that run according to the time and day.

Scheduling: on/off. Select Off to use the default schedule, or On to use the programmed schedules.

Reset schedules. Turn all schedules off and reset them to their factory default settings.

Edit schedules. Set the cooling options for up to eight time periods.

Schedule: 1 of 8

Select a schedule to modify.

Schedule: On/Off

Activate or deactivate this schedule.

Mode

Choose Cool, Vent Only, or System Off. See “Mode” on page 20.

Set Point

Set the target temperature for the room. See “Set Point” on

 

page 20.

Blower

Set the speed of the blower to High or Low. Use the Low blower

 

speed to remove humidity from the room air.

Day

Choose the days for this schedule to run. Options include: Every

 

day, Weekdays, Weekends, Sun, Mon, Tue, Wed, Thu, Fri, and

 

Sat.

Start Time

Set the time when this schedule becomes active. Times are entered

 

using a 24-hour clock.

Stop Time

Set the time when this schedule becomes inactive. Times are

 

entered using a 24-hour clock.

Note: If schedules overlap, the schedule with the highest day-priority runs. The priority is:

• Highest: Sun, Mon, Tue, Wed, Thu, Fri, Sat

Next Highest: Weekdays, Weekends

Lowest: Every Day

NetworkAIR ACPA4000

21

Image 29
Contents NetworkAIR Portable Air Conditioning Unit ACPA4000Installation, Operation, and Maintenance Page American Power Conversion Legal Disclaimer Page Contents InstallationGeneral Information Operation Maintenance and Troubleshooting Page Overview General InformationManual updates About the NetworkAIR ACPA4000Cross-referencesymbol used in this manual Safety symbols that may be used in this manualInspecting the Equipment Storing the Equipment Before InstallationSafety Filing a claimThe equipment ships with the items shown below Tools RequiredInventory Rear view Component IdentificationFront view Dimensions are shown in mm in Dimensions and WeightsNet Weight Shipping WeightLock the rolling casters InstallationWhere to locate the equipment Assemble the ceiling adapter Intake and Exhaust VentsHose connections NetworkAIR ACPA4000 Install the adapter in a drop ceilingAssemble the ducts Attach the drain line. Attach Drain LineConnect the fitting to the drain line Temperature/humidity sensor AccessoriesOutput relays Relays and ContactsOverview To connect an input contact Input contactsTo connect an output relay How to apply power to the equipment Start-UpStart-upchecklist Display interface identification OperationOverview Scrolling status screens How to Use the InterfaceTurn on the equipment Navigating the interface Main menu screenDate 18-Jun-2007 Time Date 18-Jun-2007 TimeTurn off the equipment Change settingsPassword entry Default schedule Set Environmental ControlsSchedule 1 of Operating schedulesSchedule On/Off ModeSet the alarm delay Set Up AlarmsTemperature and humidity alarms Password and time-out Set Up the DisplaySet the date and time Display interface optionsResetting to default settings Device settingsPath Main Menu Setup System Device Path Main Menu Setup Factory DefaultsHow to download firmware Input contacts Set Up Contacts and RelaysUser input contacts User outputsDefault schedule status Checking Equipment StatusScrolling status screens System and environmental status screensManufacturer data Viewing alarm statusSilencing the alarm beeper Responding to AlarmsSilence Active Alarm Warning or alarm LEDResolving alarm conditions Active alarm screenAlarm and event log Action Required Alarm messagesAlarm Message Remote temperature Alarm MessageAction Required Setup Display Interface Reference ChartsScrolling status screens Monitoring informationSetup Programmable settingsStatus Control EnvironmentSystem SetupReplace the air filter Maintenance and TroubleshootingMaintenance Update the main control board firmware Clean the condenser filter and test the LCDI plugClean the cabinet Problem TroubleshootingPossible cause Corrective actionTerms of warranty One-YearFactory WarrantyNon-transferablewarranty ExclusionsWarranty claims Parts Warranty ProceduresClaims Electrical SpecificationsPhysical Component TypePage APC Worldwide Customer Support 990-0412D990-0412D 03/2008