APC manual Install the adapter in a drop ceiling, NetworkAIR ACPA4000

Page 17
Install the adapter in a drop ceiling

Install the adapter in a drop ceiling

Use the ceiling adapter to provide an intake and exhaust outlet for the condenser.

Note: Allow at least 305 mm (12 in) of open space above the ceiling adapter opening so exhaust air is not blocked.

1. Determine a location to install the ceiling adapter.

2. Remove the ceiling tile in the chosen location and save it for a future step.

3. Place the ceiling adapter into the ceiling tile grid.

na0373a

4.Secure the ceiling adapter to the building structural

support (not the drop ceiling), using 10-gauge (minimum) steel wire.

na0397aManual backgroundManual backgroundManual backgroundManual backgroundManual background

5.When using 2 x 4 ft ceiling tiles, insert a cross member (not provided) for added support.

na0394a

NetworkAIR ACPA4000

9

Image 17
Contents NetworkAIR Portable Air Conditioning Unit ACPA4000Installation, Operation, and Maintenance Page American Power Conversion Legal Disclaimer Page Contents InstallationGeneral Information Operation Maintenance and Troubleshooting Page Overview General InformationManual updates About the NetworkAIR ACPA4000Cross-referencesymbol used in this manual Safety symbols that may be used in this manualInspecting the Equipment Storing the Equipment Before InstallationSafety Filing a claimThe equipment ships with the items shown below Tools RequiredInventory Rear view Component IdentificationFront view Dimensions are shown in mm in Dimensions and WeightsNet Weight Shipping WeightLock the rolling casters InstallationWhere to locate the equipment Assemble the ceiling adapter Intake and Exhaust VentsHose connections NetworkAIR ACPA4000 Install the adapter in a drop ceilingAssemble the ducts Attach the drain line. Attach Drain LineConnect the fitting to the drain line Temperature/humidity sensor AccessoriesOutput relays Relays and ContactsOverview To connect an input contact Input contactsTo connect an output relay How to apply power to the equipment Start-UpStart-upchecklist Display interface identification OperationOverview Scrolling status screens How to Use the InterfaceTurn on the equipment Navigating the interface Main menu screenDate 18-Jun-2007 Time Date 18-Jun-2007 TimeTurn off the equipment Change settingsPassword entry Default schedule Set Environmental ControlsSchedule 1 of Operating schedulesSchedule On/Off ModeSet the alarm delay Set Up AlarmsTemperature and humidity alarms Password and time-out Set Up the DisplaySet the date and time Display interface optionsResetting to default settings Device settingsPath Main Menu Setup System Device Path Main Menu Setup Factory DefaultsHow to download firmware Input contacts Set Up Contacts and RelaysUser input contacts User outputsDefault schedule status Checking Equipment StatusScrolling status screens System and environmental status screensManufacturer data Viewing alarm statusSilencing the alarm beeper Responding to AlarmsSilence Active Alarm Warning or alarm LEDResolving alarm conditions Active alarm screenAlarm and event log Action Required Alarm messagesAlarm Message Remote temperature Alarm MessageAction Required Setup Display Interface Reference ChartsScrolling status screens Monitoring informationSetup Programmable settingsStatus Control EnvironmentSystem SetupReplace the air filter Maintenance and TroubleshootingMaintenance Update the main control board firmware Clean the condenser filter and test the LCDI plugClean the cabinet Problem TroubleshootingPossible cause Corrective actionTerms of warranty One-YearFactory WarrantyNon-transferablewarranty ExclusionsWarranty claims Parts Warranty ProceduresClaims Electrical SpecificationsPhysical Component TypePage APC Worldwide Customer Support 990-0412D990-0412D 03/2008