Model: FDKN series
This diagram shows the PCB for the 151~251. The component layout on the 301 PCB is different, but the functions are the same.
J31
| Heat exchanger thermistor, |
|
Heat exchanger thermistor | Return air thermistor | Remote controller |
| ||
| ||
|
| |
|
| TB,3 |
| R16 |
|
Dip switch (SW5)
J9~J11
(SW10)
Dip switch (SW9)
J5~J8
(SW8)
J1~J4(SW7)
CNZ
SW10 SW5
J9 | J10 | J11 |
SW8 SW9
J5 | J6 | J7 | J8 |
J4 J3 J2 J1 | SW7 |
CNE
CNN1 |
| CNH | R17 |
| CNB | L1 | L2 |
|
|
| |
J31 |
|
|
|
|
|
| CNW1 |
|
| IC11 |
|
| L4 |
|
|
R151
TB,2
TB,1
G
PCB power supply connector
(Primary side)
Adress switch (SW2)
SW2
IC9IC10
| C92 |
LED1 | CNG |
| |
CNL | CNY |
| C2 |
| R62 |
| IC8 |
| BZ |
| CNT |
CNJ | CNM |
C104
PCB power supply connector
(Secondary side)
Louver motor | Connector | Fan motor |
(CNT) |
| |
|
|
●Change by the jumper wire
| Name | Function | |
J1 |
| With | Input signal - Reverse invalid |
| None (1) | Input signal - Rus stop | |
|
| ||
J2 |
| With | Heating thermostat |
| None (1) | Heating thermostat | |
|
| ||
J3 |
| With | Normal operation operable |
| None (1) | Operation permission prohibited | |
|
| ||
J4 |
| With | Normal |
| None (1) | Heating temp. +3 | |
|
| ||
J5 |
| With | Louver free stop control - Invalid |
| None (1) | Louver free stop control - Effective | |
|
| ||
J6 |
| With | Freeze prevention fan control activated. |
| None (1) | Freeze prevention fan control deactivated. | |
|
| ||
J8 |
| With | Model 151~251 |
| None (1) | Model 301 | |
|
|
Note (1) “None” means that jumper wire is not provided on the PCB or the connection is cut
(2)The replacement board is not equipped with jumpers J1 ~ J8. Instead, SW7 and 8, with the same functions as jumpers J1~J8, are used in the position where the jumpers were previously. Set SW7 and 8 locally in accordance with the above table.
●Control change switch (SW5, SW9, SW10)
Function of DIP switch SW5 (Usually all turned OFF)
| Switch |
| Function | ||
| ON |
| ON | Setting time : 1000hrs. (Unit stop) | |
OFF | Setting time : 1000hrs. (Display) | ||||
| |||||
OFF | ON | Setting time : 600hrs. (Display) | |||
|
| ||||
|
| OFF | Setting time : 180hrs. (when shipped from factory) | ||
|
|
|
Function of DIP switch SW9 (Usually all turned OFF)
| Switch | Function | |
| OFF | Custom code - Change | |
| ON | Custom code - Normal | |
|
| ||
| OFF | Power failure security - Effective | |
| ON | Power failure security - Invalid | |
|
| ||
| ON | Emergency operation | |
| OFF | Normal | |
|
| ||
| ON | Fan control : Powerful mode | |
| OFF | Fan control : Mild mode | |
|
|
Note (1) It is normally ON only in the case of
Function of DIP switch SW10 (Usually all turned OFF)
| Switch |
| Function | |||
OFF | Auto swing fanction - None |
| ||||
ON | Auto swing function - With |
| ||||
|
|
|
| |||
| OFF |
| OFF | Remote controller air flow | – | |
ON | Remote controller air flow | 1 speed | ||||
| ||||||
(J10) | ON | (J11) | OFF | Remote controller air flow | 2 speed | |
ON | Remote controller air flow | 3 speed | ||||
|
|
|
- 10 -