Hunter Fan R410A manual Recording and reset of error, Indoor unit Outdoor unit, Model Parts number

Page 9

4) Recording and reset of error

Error display

Memory

Reset

 

 

 

Error code of remote

• Saves in memory the mode (1) of higher

• Stop the unit operation by pressing the ON/OFF switch of remote

controller

priority

controller.

 

 

• Operation can be started again if the error has been reset.

Indoor unit inspection lamp

• Cannot save in memory

 

(red)

 

 

Outdoor unit inspection lamp

• Saves in memory the mode (1) of higher

 

(red)

priority

 

 

 

 

Notes (1) Priority is in the order of E1 > ... > E10 > ... > E60.

Indoor unit

Outdoor unit

:Press the ON/OFF button on the remote controller. Or disconnect and reconnect the power supply connector (CNW1 or CNW0) on the indoor unit control PCB or turn the main power supply OFF.

:Turn the main power supply OFF.

(2)Procedures of trouble diagnosis

When any error occurs, inspect in following sequence. Detailed explanation on each step is given later in this text.

Error

 

Power supply check

 

(indoor/outdoor unit)

 

 

 

 

 

Replacement or repair of defective parts Test run/adjustment

Check of inspection display [In-

 

 

 

door/outdoor unit PCB, remote

 

 

Power supply reset (1)

controller or Indication board]

 

 

 

 

 

 

 

 

 

 

 

 

 

Check of unit

 

 

Check of inspection display [In-

 

 

door/outdoor unit PCB, remote

controller

 

 

 

 

controller or Indication board]

 

 

 

 

 

 

 

 

 

Note (1) It means the operation to turn off the power and back on again more than 1 min. later in order to reset the malfunction of microcomputer due to the

effect of power supply conditions or accidental noise.

(3)Error diagnosis procedures at the indoor unit side

To diagnose the error, measure the voltage (AC, DC), resistance, etc. at each connector around the circuit board of indoor unit based on the inspection display or the operation state of unit (no operation of compressor or blower, no switching of 4-way valve, etc.) If any defective parts are discoverd, replace with the assembly of parts as shown below.

(a)Single-unit replacement parts for circuit board of indoor unit. (Peripheral electric parts for circuit board.) Indoor unit printed circuit board, thermistor (return, heat exchanger), operating switches, limit switches, transformers, fuses.

Note (1) Use normal inspection methods to determine the condition of strong electrical circuits and frozen cycle parts.

(b)Replacement procedure of indoor unit microcomputer printed circuit board

Microcomputer printed circuit board can be replaced with following procedure.

(i) Confirm the parts numbers. (Refer to the following parts layout drawing for the location of parts number.)

Model

Parts number

Model

Parts number

FDTA 151~401

PJA505A122ZD

FDKA 151~251

PHA505A018ZF

 

 

 

 

FDTA 501, 601

PJA505A122ZC

FDKA 301

PHA505A018ZG

 

 

 

 

FDE

PJA505A128ZF

FDUR

PJA505A131ZC

 

 

 

 

- 7 -

Image 9
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation Evacuation procedureHigh side Low side Refrigerant chargingIndi Cation CircuitIndoor unit side Selfdiagnosis function Check Indicator TableNo-indication E10 E16 E28 Indoor unit LED Outdoor unit LEDOutdoor unit side Display sequence of error, inspection display lamp Timing of error detectionWait Procedures of trouble diagnosis Recording and reset of errorError diagnosis procedures at the indoor unit side Indoor unit Outdoor unitChange by the jumper wire Control change switch SW5, SW9, SW10Parts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Drain motor Model Fdur seriesIndoor unit Outdoor unit Check method when the error code is displayReplacement indoor Unit control PCB Remote controller wire Is removedRed LED Time flash Stays OFF Green LED Keeps flashing Approximately151~251 Red LED301~601 Cases of other than FDT Only case of FDTRed LED Stays OFF Green LED Stays OFF or LightsError display e6 Error display Detective return air thermistorDefective indoor unit heat exchanger thermistor Abnormal Temperature Detection Error display Heating overloadError display Drain trouble Indoor unit heat exchanger temp. ˚CError display e16 Fan motor abnormalities Error displayE10 Only case of FDTA501, 601 typesDisplay conditions Only case of Fdkn Only case of 151~251 typesWithin a period of 1 hour Only case of 301 typeAre characteristics Error display e28 Directive remote controller thermistorDetectivie remote controller PCB Remote controller therm Replacement Detective reError diagnosis procedures at the outdoor units side Function of DIP switches SW5 Usually all turned OFF Change by the jumper wireParts layout on the outdoor unit PCB FDCVA151~251 type Change by the JA3FDCA301~601 type Overcurrent SettingPower transistor module Error display Communications error during operation Power supply phases reversed Only case of 301~601 typeE32 E33 Inverter primary current abnormal Only case of 151~251 typeCompressor overcurrent trouble Only case of 301~601 type E34 Error display e35 Cooling overload operationError display e36 Discharge temperature error Abnormal Temperature DetectionPressor is stopped Utes Error display e39 Defective discharge pipe thermistor100 80 CError display e40 63H1 operation Only case of 301~601 type Open phase at L3-phase of 52C primary sideError display e42 Current cut Only case of 151~251 type E47 Error display e52 52C Abnormal Only case of 301~601 typeE48 Inverter over-voltage trouble Only case of 151~251 typeE57 Insufficient refrigerant volumeCould be causing Did it improve? Replacement CompressorRefrigerant circuit Malfunction. IfIs the power Power transistor module including drive circuit check methodCheck abnormal operation data with the remote controller Pull the cover downward to open it Remote controller Wired remote controllerIndoor unit functions I/U Function Remote controller unit functionsWhen Function is selected Function setting methodPress the ON/OFF button When I/U Function is selectedChanging the remote controller’s temperature setting range Canceling the Cooling Test Operation Cooling Test Operation ProcedureStarting the Cooling Test Operation Checking Operation DataTest run Test run method Setting SW5-1, SW5-2 on-siteChecking the state of the unit in operation HeatingFdkn Series Indication board Fden SeriesWireless remote controller Page NATIONAL, State and Local Codes Installation of this equipment must comply with all