Hunter Fan R410A manual Power transistor module including drive circuit check method, Is the power

Page 36

Power transistor module (including drive circuit) check method

Is the power

transistor module cracked or burnt?

YES

Is there a

short circuit between the power transistor module terminals? 1

YES

Compressor operation

Is the balance between the compressor current phases good?

YES

Normal

NO

NO

NO

If there is a 10% or greater difference in the current in different phases.

(except during acceleration or deceleration)

Replacement control PCB

1 Power transistor module terminal short circuit check procedure

Disconnect the compressor wiring, then conduct a short circuit check. P-U, P-V, P-W

N-U, N-V, N-W

Check between the P-N terminals.

Bring the tester probes in contact with the following places on each terminal.

P: Power transistor P terminal,

U: End of red harness to compressor

N: Power transistor N terminal,

V: End of white harness to compressor

 

W: End of black harness to compressor

- 34 -

Image 36
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation procedure EvacuationRefrigerant charging High side Low sideIndi Cation CircuitSelfdiagnosis function Check Indicator Table Indoor unit sideNo-indication E10 E16 E28 Indoor unit LED Outdoor unit LEDOutdoor unit side Display sequence of error, inspection display lamp Timing of error detectionWait Recording and reset of error Procedures of trouble diagnosisError diagnosis procedures at the indoor unit side Indoor unit Outdoor unitChange by the jumper wire Control change switch SW5, SW9, SW10Parts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Model Fdur series Drain motorCheck method when the error code is display Indoor unit Outdoor unitRemote controller wire Is removed Replacement indoor Unit control PCBRed LED Time flash Stays OFF Green LED Keeps flashing Approximately151~251 Red LED301~601 Only case of FDT Cases of other than FDTRed LED Stays OFF Green LED Stays OFF or LightsError display e6 Error display Detective return air thermistorDefective indoor unit heat exchanger thermistor Error display Heating overload Abnormal Temperature DetectionError display Drain trouble Indoor unit heat exchanger temp. ˚CError display Error display e16 Fan motor abnormalitiesE10 Only case of FDTA501, 601 typesOnly case of Fdkn Only case of 151~251 types Display conditionsWithin a period of 1 hour Only case of 301 typeError display e28 Directive remote controller thermistor Are characteristicsDetectivie remote controller PCB Remote controller therm Replacement Detective reError diagnosis procedures at the outdoor units side Change by the jumper wire Function of DIP switches SW5 Usually all turned OFFParts layout on the outdoor unit PCB FDCVA151~251 type Change by the JA3Overcurrent Setting FDCA301~601 typePower transistor module Error display Communications error during operation Power supply phases reversed Only case of 301~601 typeE32 E33 Inverter primary current abnormal Only case of 151~251 typeCompressor overcurrent trouble Only case of 301~601 type Error display e35 Cooling overload operation E34Error display e36 Discharge temperature error Abnormal Temperature DetectionPressor is stopped Error display e39 Defective discharge pipe thermistor Utes100 80 CError display e40 63H1 operation Only case of 301~601 type Open phase at L3-phase of 52C primary sideError display e42 Current cut Only case of 151~251 type Error display e52 52C Abnormal Only case of 301~601 type E47E48 Inverter over-voltage trouble Only case of 151~251 typeInsufficient refrigerant volume E57Did it improve? Replacement Compressor Could be causingRefrigerant circuit Malfunction. IfPower transistor module including drive circuit check method Is the powerCheck abnormal operation data with the remote controller Remote controller Wired remote controller Pull the cover downward to open itRemote controller unit functions Indoor unit functions I/U FunctionFunction setting method When Function is selectedWhen I/U Function is selected Press the ON/OFF buttonChanging the remote controller’s temperature setting range Cooling Test Operation Procedure Canceling the Cooling Test OperationStarting the Cooling Test Operation Checking Operation DataSetting SW5-1, SW5-2 on-site Test run Test run methodChecking the state of the unit in operation HeatingIndication board Fden Series Fdkn SeriesWireless remote controller Page Installation of this equipment must comply with all NATIONAL, State and Local Codes