Hunter Fan R410A manual E32, Error display Communications error during operation

Page 27

1

Error display

: e5

[Communications error during operation]

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

 

Red LED

 

2 time flash

Red LED

 

2 time flash

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

 

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

(1)

 

(2)

 

Is the connection

NO

Is the connection

NO

of the signal wires at the

of the signal wires at the

 

 

outdoor unit poor?

 

indoor unit poor?

 

 

YES

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair

 

 

 

Repair

 

 

 

 

 

 

 

 

 

 

 

Reset power

supply.

Did the remote

 

WAIT

 

 

 

controller’s LCD return

 

 

to normal?

 

 

 

 

 

YES

The unit is normal. Malfunction was due to transient noise, etc.

WAIT

Go to display diagnosis (page 140).

Notes (1) Check for poor connections (disconnection, looseness) on the outdoor unit’s terminal block.

(2) Check for poor connections or disconnection of the signal lines between the indoor and outdoor units.

 

Indoor unit

 

Outdoor unit

Red LED

2 time flash

Red LED

 

Stays OFF

Green LED

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Reset power supply.

Malfunction is due to noise, etc.

Did it return to normal? YES (The outdoor unit’s CPU went out of control due to noise during

power on.)

NO

Outdoor unit’s control PCB is faulty. (Network communications

circuit is faulty.) Replace

2

Error display

: e32

 

[Power supply phases reversed] [Only case of 301~601 type]

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

 

Red LED

 

Stays OFF

 

Red LED

 

1 time flash

 

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

 

Are the power supply phases reversed?

NO

Are the connections

to the reverse phase detection circuit lines correct?

YES

YES

NO

Repair

Repair

Outdoor unit’s control PCB is faulty.

Replace

(Reverse phase detection circuit is faulty.)

- 25 -

Image 27
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation Evacuation procedureCation Circuit Refrigerant chargingHigh side Low side IndiE10 E16 E28 Indoor unit LED Outdoor unit LED Selfdiagnosis function Check Indicator TableIndoor unit side No-indicationOutdoor unit side Display sequence of error, inspection display lamp Timing of error detectionWait Indoor unit Outdoor unit Recording and reset of errorProcedures of trouble diagnosis Error diagnosis procedures at the indoor unit sideChange by the jumper wire Control change switch SW5, SW9, SW10Parts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Drain motor Model Fdur seriesIndoor unit Outdoor unit Check method when the error code is displayApproximately Remote controller wire Is removedReplacement indoor Unit control PCB Red LED Time flash Stays OFF Green LED Keeps flashing151~251 Red LED301~601 Green LED Stays OFF or Lights Only case of FDTCases of other than FDT Red LED Stays OFFError display e6 Error display Detective return air thermistorDefective indoor unit heat exchanger thermistor Indoor unit heat exchanger temp. ˚C Error display Heating overloadAbnormal Temperature Detection Error display Drain troubleOnly case of FDTA501, 601 types Error displayError display e16 Fan motor abnormalities E10Only case of 301 type Only case of Fdkn Only case of 151~251 typesDisplay conditions Within a period of 1 hourRemote controller therm Replacement Detective re Error display e28 Directive remote controller thermistorAre characteristics Detectivie remote controller PCBError diagnosis procedures at the outdoor units side Change by the JA3 Change by the jumper wireFunction of DIP switches SW5 Usually all turned OFF Parts layout on the outdoor unit PCB FDCVA151~251 typeFDCA301~601 type Overcurrent SettingPower transistor module Error display Communications error during operation Power supply phases reversed Only case of 301~601 typeE32 E33 Inverter primary current abnormal Only case of 151~251 typeCompressor overcurrent trouble Only case of 301~601 type E34 Error display e35 Cooling overload operationError display e36 Discharge temperature error Abnormal Temperature DetectionPressor is stopped 80 C Error display e39 Defective discharge pipe thermistorUtes 100Error display e40 63H1 operation Only case of 301~601 type Open phase at L3-phase of 52C primary sideError display e42 Current cut Only case of 151~251 type Inverter over-voltage trouble Only case of 151~251 type Error display e52 52C Abnormal Only case of 301~601 typeE47 E48E57 Insufficient refrigerant volumeMalfunction. If Did it improve? Replacement CompressorCould be causing Refrigerant circuitIs the power Power transistor module including drive circuit check methodCheck abnormal operation data with the remote controller Pull the cover downward to open it Remote controller Wired remote controllerIndoor unit functions I/U Function Remote controller unit functionsWhen Function is selected Function setting methodPress the ON/OFF button When I/U Function is selectedChanging the remote controller’s temperature setting range Checking Operation Data Cooling Test Operation ProcedureCanceling the Cooling Test Operation Starting the Cooling Test OperationHeating Setting SW5-1, SW5-2 on-siteTest run Test run method Checking the state of the unit in operationFdkn Series Indication board Fden SeriesWireless remote controller Page NATIONAL, State and Local Codes Installation of this equipment must comply with all