Hunter Fan R410A manual Error display e36 Discharge temperature error, Pressor is stopped

Page 30

6

Error display : e36

[Discharge temperature error]

 

Indoor unit

 

Outdoor unit

 

Red LED

 

Stays OFF

Red LED

 

1 time flash

 

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Check the unit side.

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

 

During cooling: Is FM0 operating?

 

 

 

 

 

During heating: Is FM1 operating?

Is the

 

Discharge

Check the unit side.

 

Are

service

valves

(both liquid,

 

 

gas)

fully

opened

during both

discharge pipe ther-

YES

temperature error?

 

 

Insufficient refrigerant

 

cooling and heating.

 

mistror characteristics

 

(At cooling/heating

 

 

normal?

 

operation)

Charge the refrigerant (measure)

Is the installation space of indoor/

 

outdoor unit adequate?

 

 

 

Is it the oveload operation?

NO

 

 

Is there any short circuit air flow

 

 

 

 

 

 

 

 

for indoor/outdoor units?

Discharge pipe thermis-

 

Is discharge temperature

 

 

 

 

 

 

 

 

tor replacement

 

control normal?

If the discharge pipe temperature exceeds the set value,

 

 

 

 

 

 

 

 

the compressor’s speed (151~251) or the expansion

Is the unit

 

Abnormal temperature sensed

valve’s opening angle (301~601) is controlled to prevent

normalized

 

Is the (actual measurement) normal?

the discharge pipe temperature from rising.

 

NO

 

 

NO

Compressor control

The compressor’s capacity

 

Defective outdoor unit PCB

 

 

 

is lowered (Each minute the

 

 

 

 

 

speed is reduced (151~251).

 

 

Replacement

 

 

 

 

 

Expansion valve control

 

 

 

 

 

Hold

 

 

Display conditions

 

 

 

 

 

 

(301~601)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the discharge temperature is as shown at left 2 (5) times within 60

Release

 

 

 

 

 

minutes, or continuously for 60 minutes, including when the com-

151~251 type

80

 

90

 

 

pressor is stopped.

 

 

 

301~601 type

90

 

100

 

 

 

 

Discharge pipe temperature (°C)

 

 

 

 

 

 

Note (1) Values in ( ) show for the case of the 301~601 models.

Abnormal Temperature Detection

151~251 type

 

 

 

301~601 type

 

 

 

 

 

Error stop

 

 

 

 

Error stop

 

 

 

 

 

 

 

 

 

 

 

 

 

Operoble

 

 

 

 

 

Operoble

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

105

 

80

121

 

Discharge pipe temp. (°C)

 

Discharge pipe temp. (°C)

Thermistor resistance

151~251 type

 

 

 

 

 

301~601 type

 

 

 

 

Temperature-resistance characteristics

C]80°

 

Temperature-resistance characteristics

of discharge pipe thermistor (Tho-D)

 

of discharge pipe thermistor (Tho-D)

 

C]80°

100

 

 

 

 

 

 

 

 

100

 

 

 

 

10

 

 

 

 

 

 

 

 

 

<

 

 

T< 80˚C

 

 

 

>

 

 

 

 

 

 

 

 

)(k[T

 

 

 

T >80˚C

 

)(k[T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

resistance

50

 

 

 

 

5

resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

20

40

60

80

100

120

140

Thermistor

0

0

50

80

100

0

Thermistor

 

 

 

 

 

 

Temperature [T] (°C)

 

 

 

 

Temperature [T] (°C)

 

 

7

Error display : e37 [Defective outdoor unit heat exchanger thermistor]

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time flash

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Is the outdoor

YES

Are the outdoor unit

unit heat exchanger

heat exchanger thermistor

thermistor connector

 

characteristics OK, is there

OK?

 

any broken wire?

 

NO

 

NO

 

 

 

 

 

 

Defective outdoor unit

Repairheat exchanger thermistor Replacement

Display conditions

If the temperature sensed by the thermistor is –30ºC or lower con- tinuously for 5 seconds between 2 minutes and 2 minutes 20 seconds after the compressor goes ON, the compressor stops. After a 3 minute

delay, the compressor restarts. If this state is detected 3 times in 40 (60) minutes.

Note (1) Values in ( ) show for the case of the 301~601 models.

- 28 -

Defective outdoor unit control YES PCB Replacement (Defective

outdoor unit heat exchanger thermistor input circuit)

Outdoor unit heat exchanger thermistor (ThO-R)

Resistance temperature characteristics

 

15

 

 

(k)

10

 

 

Resistance

 

 

 

5

5kat 25°

C

 

 

 

 

0

10

20

30

40

50

Temperature (°C)

Image 30
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation procedure EvacuationIndi Refrigerant chargingHigh side Low side Cation CircuitNo-indication Selfdiagnosis function Check Indicator TableIndoor unit side E10 E16 E28 Indoor unit LED Outdoor unit LEDOutdoor unit side Display sequence of error, inspection display lamp Timing of error detectionWait Error diagnosis procedures at the indoor unit side Recording and reset of errorProcedures of trouble diagnosis Indoor unit Outdoor unitChange by the jumper wire Control change switch SW5, SW9, SW10Parts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Model Fdur series Drain motorCheck method when the error code is display Indoor unit Outdoor unitRed LED Time flash Stays OFF Green LED Keeps flashing Remote controller wire Is removedReplacement indoor Unit control PCB Approximately151~251 Red LED301~601 Red LED Stays OFF Only case of FDTCases of other than FDT Green LED Stays OFF or LightsError display e6 Error display Detective return air thermistorDefective indoor unit heat exchanger thermistor Error display Drain trouble Error display Heating overloadAbnormal Temperature Detection Indoor unit heat exchanger temp. ˚CE10 Error displayError display e16 Fan motor abnormalities Only case of FDTA501, 601 typesWithin a period of 1 hour Only case of Fdkn Only case of 151~251 typesDisplay conditions Only case of 301 typeDetectivie remote controller PCB Error display e28 Directive remote controller thermistorAre characteristics Remote controller therm Replacement Detective reError diagnosis procedures at the outdoor units side Parts layout on the outdoor unit PCB FDCVA151~251 type Change by the jumper wireFunction of DIP switches SW5 Usually all turned OFF Change by the JA3Overcurrent Setting FDCA301~601 typePower transistor module Error display Communications error during operation Power supply phases reversed Only case of 301~601 typeE32 E33 Inverter primary current abnormal Only case of 151~251 typeCompressor overcurrent trouble Only case of 301~601 type Error display e35 Cooling overload operation E34Error display e36 Discharge temperature error Abnormal Temperature DetectionPressor is stopped 100 Error display e39 Defective discharge pipe thermistorUtes 80 CError display e40 63H1 operation Only case of 301~601 type Open phase at L3-phase of 52C primary sideError display e42 Current cut Only case of 151~251 type E48 Error display e52 52C Abnormal Only case of 301~601 typeE47 Inverter over-voltage trouble Only case of 151~251 typeInsufficient refrigerant volume E57Refrigerant circuit Did it improve? Replacement CompressorCould be causing Malfunction. IfPower transistor module including drive circuit check method Is the powerCheck abnormal operation data with the remote controller Remote controller Wired remote controller Pull the cover downward to open itRemote controller unit functions Indoor unit functions I/U FunctionFunction setting method When Function is selectedWhen I/U Function is selected Press the ON/OFF buttonChanging the remote controller’s temperature setting range Starting the Cooling Test Operation Cooling Test Operation ProcedureCanceling the Cooling Test Operation Checking Operation DataChecking the state of the unit in operation Setting SW5-1, SW5-2 on-siteTest run Test run method HeatingIndication board Fden Series Fdkn SeriesWireless remote controller Page Installation of this equipment must comply with all NATIONAL, State and Local Codes