Hunter Fan R410A manual Remote controller unit functions, Indoor unit functions I/U Function

Page 39

(2) Setting functions using the remote controller

(a)The factory settings of this unit's functions are as follows: If you want to charge a setting, follow the procedure found in the installation manual and set to your desired setting.

For the method of setting, please refer to the installation manual of a remote control unit.

1 Remote controller unit functions (

 

 

 

FUNCTION )

2 Indoor unit functions (I/U FUNCTION )

 

 

 

Function

 

 

 

Function description B

 

 

 

 

Setting C

 

Factory

number A

 

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRILLE SET (panelGrillesettinglift

)

 

 

INVALID

 

 

 

 

 

 

 

 

 

 

01

50Hz AREA ONLY

 

 

 

60Hz AREA ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

 

AUTO RUN SET

 

AUTO RUN ON

*

 

 

 

 

 

 

 

AUTO RUN OFF

 

 

 

 

 

 

 

03

 

 

 

TEMP S/W

 

 

 

 

VALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

 

 

 

MODE S/W

 

 

 

 

VALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALID

 

 

 

 

 

 

 

 

 

 

ON/OFF

 

 

05

 

ON/OFF

ON/OFF S/W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON/OFF

INVALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

 

 

 

FANSPEED S/W

 

 

 

 

VALID

 

 

 

 

 

 

 

 

 

INVALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07

 

 

 

LOUVER S/W

 

 

 

 

VALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVALID

*

 

 

 

 

 

 

 

 

 

 

08

 

 

 

TIMER S/W

 

 

 

 

VALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVALID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote control

 

 

INSENSOR OFF (Invalid)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09

 

 

 

SENSOR S/W(sensor setting

)

 

 

 

 

 

 

 

 

SENSOR ON (Valid)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

POWER FAILURE

 

INVALID

 

 

 

 

 

 

 

 

 

COMPENSATION SET

 

VALID

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO VENTI

 

 

11

 

VENTI SET

 

 

 

 

 

 

 

 

 

VENTI LINK SET

 

 

 

 

 

 

 

 

 

NO VENTI LINK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

TEMP RANGE SET

 

DISP CHARGE

 

 

 

 

 

 

 

 

 

 

 

NO DISP CHARGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

3 FAN SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

I/U FA SPEED (fan speed setting)

2 FAN SPEED

*

 

1 FAN SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

MODEL TYPE

 

HEAT PUMP

 

 

 

 

COOLING ONLY

*

 

 

 

 

 

 

 

15

 

EXTERNAL CONTROL SET

INDIVIDUAL OPERATION

 

 

 

 

 

 

 

 

 

SAME OPERATION FOR ALL UNITS

 

 

 

 

 

 

 

 

 

 

 

16

 

ERROR DISP SET

 

ERROR DISP

 

 

 

 

 

 

 

 

 

 

 

NO ERROR DISP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

 

POSITION (controlLouver setting)

FIX (1 OF 4) (4 position stop)

 

 

IN MOTION (Free stop)

 

 

 

 

 

 

 

 

 

 

 

18

 

°C/°F SET

 

°C

 

 

 

 

 

 

 

 

 

 

 

 

°F

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

Function description B

Setting C

 

Factory

number A

 

setting

 

 

 

 

 

 

 

 

01

Hi CEILING SET

STANDARD (Mild mode)

 

 

 

 

 

Hi CEILING 1 (Powerful mode)

*

 

 

 

 

NO DISPLAY

 

 

 

 

 

 

 

 

 

AFTER 180H

 

 

03

FILTER SIGN SET

 

*

AFTER 600H

 

 

 

 

AFTER 1000H

 

 

 

 

 

 

 

 

 

1000HSTOP

 

 

 

 

 

 

 

04

POSITION (settingLouver control)

FIX (1 OF 4) (4 positiion stop)

 

 

 

 

 

IN MOTION (Free stop)

 

 

 

 

 

 

 

05

EXTERNAL INPUT SET

LEVEL INPUT

 

 

 

 

 

PULSE INPUT

 

 

 

 

 

 

 

 

 

 

 

06

OPERATION PERMISSION

NORMAL OPERATION

 

 

PROHIBITED

VALID

 

 

 

 

 

 

 

 

 

 

07

ROOM TEMP OFF SET

NORMAL OPERATION

 

 

 

 

 

(Heating room temperature off set)

TEMP SHIFT +3˚C

 

 

 

 

 

 

 

 

 

 

 

Heating

LOW FAN

 

 

08

FAN CONTROL (fan control)

 

 

*

STOPLOW FAN (Intermittent operation)

 

09

FREEZE PREVENT TEMP

TEMP Hi

 

 

 

 

 

TEMP Lo

 

 

 

 

 

 

10

FREEZE PREVENT CONTROL

FAN CONTROL ON

 

 

 

 

 

FAN CONTROL OFF

 

 

 

 

 

 

Notes(1) Setting marked with [] are the default setting.

(2)Setting marked with [*] are those that are set automatically according to an indoor unit or an outdoor unit connected.

Please check default settings with the indoor unit's installation manual.

Notes(1) Setting marked with [] are the default setting.

(2)Setting marked with [*] are those that are set automatically according to an indoor unit or an outdoor unit connected. Please check default settings with the indoor unit's installation manual.

(3)When Item 17 : “ POSITION” is changed, please also

change Item 04 “ POSITION” setting found in “Indoor unit functions”.

- 37 -

Image 39
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation Evacuation procedureCation Circuit Refrigerant chargingHigh side Low side IndiE10 E16 E28 Indoor unit LED Outdoor unit LED Selfdiagnosis function Check Indicator TableIndoor unit side No-indicationOutdoor unit side Display sequence of error, inspection display lamp Timing of error detectionWait Indoor unit Outdoor unit Recording and reset of errorProcedures of trouble diagnosis Error diagnosis procedures at the indoor unit sideChange by the jumper wire Control change switch SW5, SW9, SW10Parts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Drain motor Model Fdur seriesIndoor unit Outdoor unit Check method when the error code is displayApproximately Remote controller wire Is removedReplacement indoor Unit control PCB Red LED Time flash Stays OFF Green LED Keeps flashing151~251 Red LED301~601 Green LED Stays OFF or Lights Only case of FDTCases of other than FDT Red LED Stays OFFError display e6 Error display Detective return air thermistorDefective indoor unit heat exchanger thermistor Indoor unit heat exchanger temp. ˚C Error display Heating overloadAbnormal Temperature Detection Error display Drain troubleOnly case of FDTA501, 601 types Error displayError display e16 Fan motor abnormalities E10Only case of 301 type Only case of Fdkn Only case of 151~251 typesDisplay conditions Within a period of 1 hourRemote controller therm Replacement Detective re Error display e28 Directive remote controller thermistorAre characteristics Detectivie remote controller PCBError diagnosis procedures at the outdoor units side Change by the JA3 Change by the jumper wireFunction of DIP switches SW5 Usually all turned OFF Parts layout on the outdoor unit PCB FDCVA151~251 typeFDCA301~601 type Overcurrent SettingPower transistor module Error display Communications error during operation Power supply phases reversed Only case of 301~601 typeE32 E33 Inverter primary current abnormal Only case of 151~251 typeCompressor overcurrent trouble Only case of 301~601 type E34 Error display e35 Cooling overload operationError display e36 Discharge temperature error Abnormal Temperature DetectionPressor is stopped 80 C Error display e39 Defective discharge pipe thermistorUtes 100Error display e40 63H1 operation Only case of 301~601 type Open phase at L3-phase of 52C primary sideError display e42 Current cut Only case of 151~251 type Inverter over-voltage trouble Only case of 151~251 type Error display e52 52C Abnormal Only case of 301~601 typeE47 E48E57 Insufficient refrigerant volumeMalfunction. If Did it improve? Replacement CompressorCould be causing Refrigerant circuitIs the power Power transistor module including drive circuit check methodCheck abnormal operation data with the remote controller Pull the cover downward to open it Remote controller Wired remote controllerIndoor unit functions I/U Function Remote controller unit functionsWhen Function is selected Function setting methodPress the ON/OFF button When I/U Function is selectedChanging the remote controller’s temperature setting range Checking Operation Data Cooling Test Operation ProcedureCanceling the Cooling Test Operation Starting the Cooling Test OperationHeating Setting SW5-1, SW5-2 on-siteTest run Test run method Checking the state of the unit in operationFdkn Series Indication board Fden SeriesWireless remote controller Page NATIONAL, State and Local Codes Installation of this equipment must comply with all