Error display : e1
[Communication error between remote controller~Indoor unit]
| Indoor unit |
| Outdoor unit |
Red LED | Stays OFF | Red LED | Stays OFF |
|
|
|
|
Green LED | Keeps flashing | Green LED | Keeps flashing |
|
|
|
|
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Voltage | YES |
|
|
| ||
between X and Z | Replacement remote | |||||
|
| |||||
approximately |
|
| controller | |||
10~11 V? |
|
|
|
|
| |
NO |
|
|
|
|
| |
Voltage | NO |
|
| YES | ||
|
|
| ||||
fluctuates between |
|
|
| |||
5~11 V between |
|
|
|
|
| |
Y and Z. |
|
|
| Power supply OFF | ||
|
|
|
| |||
YES |
|
|
|
|
| |
|
|
|
|
|
Remote controller
wire is removed
Is the
resistance between NO Y~Z on the remote controller
approximately
10kΩ?
Replacement
remote controller
Voltage | NO | |
fluctuates between | ||
5~10 V between |
| |
| ||
Y and Z |
| |
indoors. |
| |
YES |
| |
Voltage | NO | |
fluctuates between | ||
| ||
5~10 V between |
| |
| ||
CNB Y and Z. |
| |
YES |
| |
Indoor unit | NO | |
resets every ❇ |
| |
| ||
4 minutes. |
|
Remote controller wire disconnection
Terminal block CNB harness is defective.
Power supply reset
| Resistance is | NO |
|
|
| |||
| approximately 10kΩ |
|
| Replacement indoor | ||||
| between indoor |
|
| unit control PCB | ||||
| Y~Z. |
|
|
|
| |||
|
|
|
| |||||
|
| YES |
|
|
|
| ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| Remote controller |
|
|
|
| |||
| wire short circuit |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| YES |
|
|
|
|
| ||
|
| Noise? |
| |||||
Normal? |
|
|
|
| ||||
| ||||||||
|
|
|
|
|
|
|
|
|
YES
Power supply reset
Normal?
NO
Replacement indoor
unit control PCB
❇After the green LED lights up once, it begins flashing again continuously. The louver moves once in the
close direction.
YES
Noise
NO
Replacement remote
controller
| Indoor unit |
| Outdoor unit | |
Red LED | Stays OFF | Red LED | Stays OFF | |
|
|
|
| |
Green LED | Stays OFF or Lights | Green LED | Keeps flashing | |
continuously | ||||
|
|
| ||
|
|
|
|
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
●Only case of FDT
Stays OFF
Is the voltage | NO | Check the CNW5- |
|
between CNW8 |
| ||
| CNW8 harness. |
| |
|
| ||
|
|
|
Lighting YES
Power supply reset
YES
Disconnection ?
NO
Is the
voltage at the transfomer's NO secondary side
or higher?
YES
Replacement indoor unit
power supply PCB
Harness exchange
Transformer
exchange
Normal | NO | Replacement indoor |
| unit control PCB | |
|
| |
|
|
|
YES
The unit is normal.
(The malfunction is due to noise, etc.)
●Cases of other than FDT
|
|
|
|
|
|
| YES | Unit is normal. | ||||
|
|
|
| Is it normalized? |
| (Runaway of indoor | ||||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| unit CPU due to | ||
|
|
|
|
| NO |
|
|
| noise, etc. |
|
| |
|
|
|
|
|
|
|
| Transient trouble) | ||||
|
|
|
|
|
|
|
|
|
| |||
|
| Defective indoor unit control PCB |
|
|
|
|
|
| ||||
Power supply |
|
|
|
|
|
| ||||||
|
|
|
|
|
| |||||||
reset |
|
| Replace. (Defective CPU) |
|
|
|
|
|
|
- 15 -