Hunter Fan R410A manual Error diagnosis procedures at the outdoor units side

Page 23

(4)Error diagnosis procedures at the outdoor units side

At the error diagnosis related to the outdoor unit, check at first the error code of remote controller and the illumination patterns of norma1 and inspection display lamps in the same manner as the case of indoor unit.

Then estimate the outline, the cause and the location of error based on the pattern and proceed to the inspcetion and repair. Since the self diagnosis function by means of the microcomputers of indoor/outdoor units provide the judgement of error of microcomputers them selves irregularity power supply line, overload, etc. caused by the installation space, inadequate volume of refrigerant etc., the location and cause of trouble will be discovered without difficulty.

In addition, the display lamps error code of indoor/outdoor unit is kept flashing, (except when the power supply is iterrupted) after the irregularity is automatically recovered to give irregularity information to the service presonnel. If any mode of higher priority than the error retained in memory occurs after the reset of error, it is switched to that mode and saved in the memory.

(a)Replacement parts assembly related to the outdoor unit controller

Outdoor unit PCB, power transistor module, capacitor, noise filter, thermistor, (heat exchanger, discharge pipe, outdoor temperature, power transistor), fuse, transformer, etc.

(b)Replacement procedure of outdoor unit microcomputer printed circuit board.

Microcomputer printed circuit board can replaced with following procedure.

1)Confirm the parts numbers. (Refer to the following parts layout drawing for the location of parts number.)

Parts No.

Applicable Model

PCA505A080Z

FDCVA151HEN, 201HEN, 251HEN

PCA505A065ZN

FDCA301HEN, 401HEN

PCA505A065ZS

FDCA301HES, 401HES, 501HES, 601HES

2)Set the model using the model setting switch (SW6). (In the case of the 151~251 only). Switch Setting Table (All switches are set in the OFF position when shipped from the factory.)

Model

Switch Setting Table

Set the switches ON or OFF for each switch No.

( ON, OFF)

151

 

 

 

4

 

 

 

 

 

3

 

 

 

 

 

 

 

 

2

ON

 

 

 

 

 

1

 

 

 

 

201

 

 

 

4

 

 

 

 

3

 

 

 

2

 

 

 

 

 

 

ON

 

 

 

 

 

1

 

 

 

 

251

 

 

 

4

 

 

 

3

 

 

 

 

 

 

 

2

ON

 

 

 

 

1

 

 

 

 

3)Set the overcurrent value using the overcurrent setting switch for CM (SW3). (In the case of the 301~601 only) Switch Setting Table (All switches are set in the OFF position when shipped from the factory.)

Model

Setting Value (A)

Switch Setting Table

Set the switches ON or OFF for each switch No.

( ON, OFF)

301HEN 301HES 401HEN 401HES 501HES 601HES

 

17

 

 

10

 

 

27

 

 

11

 

 

12

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

6

 

 

6

 

 

6

 

 

6

 

 

6

 

5

 

 

5

 

 

5

 

 

5

 

 

5

 

 

5

 

4

 

 

4

 

 

4

 

 

4

 

 

4

 

 

4

 

3

 

 

3

 

 

3

 

 

3

 

 

3

 

 

3

 

2

 

 

2

 

 

2

 

 

2

 

 

2

 

 

2

ON

1

 

ON

1

 

ON

1

 

ON

 

 

ON

 

1

 

ON

 

1

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4)Set the control select switch to match the previously set settings on the previous board.

If the previously set settings were set with jumper wires, the control select switch should be set in the ON position if there was a jumper wire and in the OFF position if there wasn’t a jumper wire.

5)Connect the faston terminals and connectors to the control board.

When connecting the wires to the faston terminals, connect each wire to the terminal printed with the same color on the

board.

Note (1) When connecting the faston terminals to the control board, connect them so that there is no deformation of the far end of the circuit board.

- 21 -

Image 23
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation Evacuation procedureCation Circuit Refrigerant chargingHigh side Low side IndiE10 E16 E28 Indoor unit LED Outdoor unit LED Selfdiagnosis function Check Indicator TableIndoor unit side No-indicationOutdoor unit side Wait Display sequence of error, inspection display lampTiming of error detection Indoor unit Outdoor unit Recording and reset of errorProcedures of trouble diagnosis Error diagnosis procedures at the indoor unit sideParts layout on the indoor unit PCB Model FDT series Change by the jumper wireControl change switch SW5, SW9, SW10 Model Fden series Model Fdkn series Drain motor Model Fdur seriesIndoor unit Outdoor unit Check method when the error code is displayApproximately Remote controller wire Is removedReplacement indoor Unit control PCB Red LED Time flash Stays OFF Green LED Keeps flashing301~601 151~251Red LED Green LED Stays OFF or Lights Only case of FDTCases of other than FDT Red LED Stays OFFDefective indoor unit heat exchanger thermistor Error display e6Error display Detective return air thermistor Indoor unit heat exchanger temp. ˚C Error display Heating overloadAbnormal Temperature Detection Error display Drain troubleOnly case of FDTA501, 601 types Error displayError display e16 Fan motor abnormalities E10Only case of 301 type Only case of Fdkn Only case of 151~251 typesDisplay conditions Within a period of 1 hourRemote controller therm Replacement Detective re Error display e28 Directive remote controller thermistorAre characteristics Detectivie remote controller PCBError diagnosis procedures at the outdoor units side Change by the JA3 Change by the jumper wireFunction of DIP switches SW5 Usually all turned OFF Parts layout on the outdoor unit PCB FDCVA151~251 typeFDCA301~601 type Overcurrent SettingPower transistor module E32 Error display Communications error during operationPower supply phases reversed Only case of 301~601 type Compressor overcurrent trouble Only case of 301~601 type E33Inverter primary current abnormal Only case of 151~251 type E34 Error display e35 Cooling overload operationPressor is stopped Error display e36 Discharge temperature errorAbnormal Temperature Detection 80 C Error display e39 Defective discharge pipe thermistorUtes 100Error display e42 Current cut Only case of 151~251 type Error display e40 63H1 operation Only case of 301~601 typeOpen phase at L3-phase of 52C primary side Inverter over-voltage trouble Only case of 151~251 type Error display e52 52C Abnormal Only case of 301~601 typeE47 E48E57 Insufficient refrigerant volumeMalfunction. If Did it improve? Replacement CompressorCould be causing Refrigerant circuitIs the power Power transistor module including drive circuit check methodCheck abnormal operation data with the remote controller Pull the cover downward to open it Remote controller Wired remote controllerIndoor unit functions I/U Function Remote controller unit functionsWhen Function is selected Function setting methodPress the ON/OFF button When I/U Function is selectedChanging the remote controller’s temperature setting range Checking Operation Data Cooling Test Operation ProcedureCanceling the Cooling Test Operation Starting the Cooling Test OperationHeating Setting SW5-1, SW5-2 on-siteTest run Test run method Checking the state of the unit in operationFdkn Series Indication board Fden SeriesWireless remote controller Page NATIONAL, State and Local Codes Installation of this equipment must comply with all