Hunter Fan R410A manual Outdoor unit side

Page 7

2) Outdoor unit side

- 5 -

Remote

Indoor

controller

Green

error code

E32

Keeps flashing

E33

Keeps flashing

E34

Keeps flashing

E35

Keeps flashing

E36

Keeps flashing

E37

Keeps flashing

E38

Keeps flashing

E39

Keeps flashing

E40

Keeps flashing

E42

Keeps flashing

E47

Keeps flashing

E48

Keeps flashing

E52

Keeps flashing

E56

Keeps flashing

E57

Keeps flashing

E59

Keeps flashing

E60

Keeps flashing

unit LED

Outdoor unit LED

Red

Green

Red

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

Keeps flashing

1 time flash

Stays OFF

 

1 time flash

Stays OFF

 

1 time flash

Stays OFF

 

1 time flash

Stays OFF

Keeps flashing

Lights contiously

Stays OFF

 

1 time flash

Stays OFF

Keeps flashing

1 time flash

 

 

1 time flash

Stays OFF

 

2 time flash

 

 

3 time flash

Stays OFF

 

1 time flash

Cause

Wiring is open or reversal phase (FDCA 301~601 type) Inverter primary side current is abnormal. (FDCVA151~251 type) Abnormal current cut of compressor (FDCA 301~601 type) 52C secondary side L3-phase wiring is open. (FDCA 301~601 type)

Outdoor heat exchanger temperature is high or outdoor heat exchanger thermistor is faulty.

Discharge temperature abnormality.

Outdoor unit heat exchanger thermistor failure

Outdoor air temperature thermistor failure Discharge pipe thermistor failure 63H1 operation (FDCA 301~601 type) Current (Abnormalities in a compressor over current) Inverter Over-voltage Trouble. (FDCVA 151~251 type) DC fan motor abnormal. (FDCVA 151~251 type) 52C abnormal. (FDCA 301~601 type)

Power transistor thermistor is faulty or disconnection or connector connections are poor. (FDCVA 151~251 type)

Insufficient refrigerant.

Compressor startup error (FDCVA 151~251 type)

Compressor loader position detection error. (FDCVA 151~251 type)

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Image 7
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation Evacuation procedureCation Circuit Refrigerant chargingHigh side Low side IndiE10 E16 E28 Indoor unit LED Outdoor unit LED Selfdiagnosis function Check Indicator TableIndoor unit side No-indicationOutdoor unit side Timing of error detection Display sequence of error, inspection display lampWait Indoor unit Outdoor unit Recording and reset of errorProcedures of trouble diagnosis Error diagnosis procedures at the indoor unit sideControl change switch SW5, SW9, SW10 Change by the jumper wireParts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Drain motor Model Fdur seriesIndoor unit Outdoor unit Check method when the error code is displayApproximately Remote controller wire Is removedReplacement indoor Unit control PCB Red LED Time flash Stays OFF Green LED Keeps flashingRed LED 151~251301~601 Green LED Stays OFF or Lights Only case of FDTCases of other than FDT Red LED Stays OFFError display Detective return air thermistor Error display e6Defective indoor unit heat exchanger thermistor Indoor unit heat exchanger temp. ˚C Error display Heating overloadAbnormal Temperature Detection Error display Drain troubleOnly case of FDTA501, 601 types Error displayError display e16 Fan motor abnormalities E10Only case of 301 type Only case of Fdkn Only case of 151~251 typesDisplay conditions Within a period of 1 hourRemote controller therm Replacement Detective re Error display e28 Directive remote controller thermistorAre characteristics Detectivie remote controller PCBError diagnosis procedures at the outdoor units side Change by the JA3 Change by the jumper wireFunction of DIP switches SW5 Usually all turned OFF Parts layout on the outdoor unit PCB FDCVA151~251 typeFDCA301~601 type Overcurrent SettingPower transistor module Power supply phases reversed Only case of 301~601 type Error display Communications error during operationE32 Inverter primary current abnormal Only case of 151~251 type E33Compressor overcurrent trouble Only case of 301~601 type E34 Error display e35 Cooling overload operationAbnormal Temperature Detection Error display e36 Discharge temperature errorPressor is stopped 80 C Error display e39 Defective discharge pipe thermistorUtes 100Open phase at L3-phase of 52C primary side Error display e40 63H1 operation Only case of 301~601 typeError display e42 Current cut Only case of 151~251 type Inverter over-voltage trouble Only case of 151~251 type Error display e52 52C Abnormal Only case of 301~601 typeE47 E48E57 Insufficient refrigerant volumeMalfunction. If Did it improve? Replacement CompressorCould be causing Refrigerant circuitIs the power Power transistor module including drive circuit check methodCheck abnormal operation data with the remote controller Pull the cover downward to open it Remote controller Wired remote controllerIndoor unit functions I/U Function Remote controller unit functionsWhen Function is selected Function setting methodPress the ON/OFF button When I/U Function is selectedChanging the remote controller’s temperature setting range Checking Operation Data Cooling Test Operation ProcedureCanceling the Cooling Test Operation Starting the Cooling Test OperationHeating Setting SW5-1, SW5-2 on-siteTest run Test run method Checking the state of the unit in operationFdkn Series Indication board Fden SeriesWireless remote controller Page NATIONAL, State and Local Codes Installation of this equipment must comply with all