Hunter Fan R410A Display sequence of error, inspection display lamp, Timing of error detection

Page 8

(b)Display sequence of error, inspection display lamp

1)One kind error

Display corresponding to the error is shown.

2)More than one errors.

Section

 

Display section

 

 

Error code of remote controller

• Displays the error of higher priority (When plural errors are persisting)

 

···········

···········

Inspection LED (red) of indoor unit PCB

 

 

 

• Displays the present errors.

 

Inspection LED (red) of outdoor unit PCB

 

(When a new error has occurred after the former error was reset.)

 

 

 

3)Timing of error detection

Indoor unit side.

Error detail

 

 

 

Error code

 

Timing of error detection

 

 

 

 

 

 

 

 

 

 

 

 

Drain error (float switch motion)

 

 

 

 

 

 

 

 

 

Normally, 30 seconds after the power is turned ON.

 

 

 

 

 

 

 

 

 

 

 

 

Wrong connection between the indoor and

 

 

 

Wait

 

 

 

No communications even once with the outdoor unit.

outdoor units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transmission error of remote controller

 

 

 

 

 

 

 

 

 

After 1 or more communications of the indoor unit with the remote controller

indoor unit

 

 

 

 

 

 

 

 

 

following power on, transmission errors cause an interruption for 2 minutes.

 

 

 

 

 

 

 

 

 

 

 

Transmission error between indoor/outdoor

 

 

 

 

 

 

 

 

 

After communications with the outdoor unit 1 or more times, communications

units

 

 

 

 

 

 

 

 

 

are abnormal continuously for 2 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

The number of connected indoor units

 

 

 

 

 

 

 

 

 

 

 

exceeds the connection limit (when

 

 

 

 

 

 

 

 

 

Normally after the power is turned ON (during communications).

multiple units are control by a single remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Broken wire of indoor unit return air

 

 

 

 

 

 

 

 

 

When an input temperature of –50°C or lower is measured by the return air

 

 

 

 

 

 

 

 

 

thermistor is measured for 5 seconds or longer within 60 minutes after the

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

first detection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Broken wire of heat exchanger thermistor

 

 

 

 

 

 

 

 

 

When an input temperature of –50°C or lower is measured by the heat

 

 

 

 

 

 

 

 

 

exchanger thermistor is measured for 5 seconds or longer within 60 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

after the first detection.

Outdoor unit side.

Error detail

Error code

Timing of error detection

 

 

 

 

 

When a thermistor input temperature of –30°C or lower is measured for 5

Broken wire of outdoor air temperature

 

seconds or longer 3 times within 40 (60) minutes after the 1st detection

thermistor

 

between 2 minutes and 2 minutes 20 seconds after compressor operation

 

 

starts.

 

 

 

Broken wire of heat exchanger thermister

 

When a thermistor input temperature of –30°C or lower is measured for 5

 

seconds or longer 3 times within 40 (60) minutes after the 1st detection

 

 

between 2 minutes and 2 minutes 20 seconds after compressor operation

 

 

starts.

Broken wire of discharge pipe thermistor

 

When a thermistor input temperature of –10°C or lower is measured for 5

 

seconds or longer 3 times within 40 (60) minutes after the 1st detection

 

 

 

 

between 10 minutes and 10 minutes 20 seconds (between 2 minutes and 2

 

 

minutes 20 seconds) after compressor operation starts.

 

 

 

Broken wire of power transistor

 

When the under-dome thermistor input temperature of –10°C is measured for

 

5 seconds or longer 3 times within 40 minutes after the 1st detection between

thermistor

 

10 minutes and 10 minutes 20 seconds after compressor operation starts.

 

 

 

Notes (1) Values in ( ) show for the FDCA301~601 models.

(2) The power transistor temperature sensor is used in the FDCVA151~251 models only.

- 6 -

Image 8
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation procedure EvacuationRefrigerant charging High side Low sideIndi Cation CircuitSelfdiagnosis function Check Indicator Table Indoor unit sideNo-indication E10 E16 E28 Indoor unit LED Outdoor unit LEDOutdoor unit side Wait Display sequence of error, inspection display lampTiming of error detection Recording and reset of error Procedures of trouble diagnosisError diagnosis procedures at the indoor unit side Indoor unit Outdoor unitParts layout on the indoor unit PCB Model FDT series Change by the jumper wireControl change switch SW5, SW9, SW10 Model Fden series Model Fdkn series Model Fdur series Drain motorCheck method when the error code is display Indoor unit Outdoor unitRemote controller wire Is removed Replacement indoor Unit control PCBRed LED Time flash Stays OFF Green LED Keeps flashing Approximately301~601 151~251Red LED Only case of FDT Cases of other than FDTRed LED Stays OFF Green LED Stays OFF or LightsDefective indoor unit heat exchanger thermistor Error display e6Error display Detective return air thermistor Error display Heating overload Abnormal Temperature DetectionError display Drain trouble Indoor unit heat exchanger temp. ˚CError display Error display e16 Fan motor abnormalitiesE10 Only case of FDTA501, 601 typesOnly case of Fdkn Only case of 151~251 types Display conditionsWithin a period of 1 hour Only case of 301 typeError display e28 Directive remote controller thermistor Are characteristicsDetectivie remote controller PCB Remote controller therm Replacement Detective reError diagnosis procedures at the outdoor units side Change by the jumper wire Function of DIP switches SW5 Usually all turned OFFParts layout on the outdoor unit PCB FDCVA151~251 type Change by the JA3Overcurrent Setting FDCA301~601 typePower transistor module E32 Error display Communications error during operationPower supply phases reversed Only case of 301~601 type Compressor overcurrent trouble Only case of 301~601 type E33Inverter primary current abnormal Only case of 151~251 type Error display e35 Cooling overload operation E34Pressor is stopped Error display e36 Discharge temperature errorAbnormal Temperature Detection Error display e39 Defective discharge pipe thermistor Utes100 80 CError display e42 Current cut Only case of 151~251 type Error display e40 63H1 operation Only case of 301~601 typeOpen phase at L3-phase of 52C primary side Error display e52 52C Abnormal Only case of 301~601 type E47E48 Inverter over-voltage trouble Only case of 151~251 typeInsufficient refrigerant volume E57Did it improve? Replacement Compressor Could be causingRefrigerant circuit Malfunction. IfPower transistor module including drive circuit check method Is the powerCheck abnormal operation data with the remote controller Remote controller Wired remote controller Pull the cover downward to open itRemote controller unit functions Indoor unit functions I/U FunctionFunction setting method When Function is selectedWhen I/U Function is selected Press the ON/OFF buttonChanging the remote controller’s temperature setting range Cooling Test Operation Procedure Canceling the Cooling Test OperationStarting the Cooling Test Operation Checking Operation DataSetting SW5-1, SW5-2 on-site Test run Test run methodChecking the state of the unit in operation HeatingIndication board Fden Series Fdkn SeriesWireless remote controller Page Installation of this equipment must comply with all NATIONAL, State and Local Codes