Hunter Fan R410A manual Utes, Error display e39 Defective discharge pipe thermistor, 100, 80 C

Page 31

8

Error display : e38

[Defective outdoor air temperature thermistor]

 

Indoor unit

 

Outdoor unit

Red LED

 

Stays OFF

Red LED

 

1 time flash

Green LED

 

Keeps flashing

Green LED

 

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Is the outdoor

YES

Is the outdoor

air temperature thermistor

air temperature thermistor

connector connection

 

 

 

characteristics OK, is there

 

 

 

no broken wire?

OK?

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defective outdoor air

Repairtemperature thermistor Replacement

Display conditions

If the temperature sensed by the thermistor is –30ºC or lower continu- ously for 5 seconds between 2 minutes and 2 minutes 20 seconds after the compressor goes ON, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected 3 times in 40 (60) min-

utes.

Note (1) Values in ( ) show for the case of the 301~601 models.

YES

Defective outdoor unit control PCB

 

Replacement (Defective outdoor air

 

 

 

temperature thermistor input circuit)

Temperature-resistance characteristics of outdoor air temperature thermistor (ThO-A)

 

400

 

 

40

 

°C]

 

 

 

 

°C]

(k)[T<0

300

 

 

30

(k)[T>0

 

 

 

 

resistance

200

T < 0°C

 

20

resistance

 

 

T > 0°C

 

Thermistor

 

 

 

Thermistor

100

 

 

10

 

 

 

 

 

0

0

50

0

 

 

---50

 

 

 

 

Temperature [T](°C)

 

 

9

Error display : e39 [Defective discharge pipe thermistor]

 

Indoor unit

Outdoor unit

Red LED

 

Stays OFF

Red LED

1 time flash

Green LED

 

Keeps flashing

Green LED

Keeps flashing

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Is the discharge

YES

Are the discharge

YES

Defective outdoor unit control

pipe thermistor

pipe thermistor characteristics

PCB

 

Replacement (Defective

 

connector connection

 

OK, is there no

 

discharge pipe thermistor

OK?

 

broken wire?

 

input circuit)

 

NO

 

 

NO

 

 

 

Temperature-resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

characteristics of discharge

 

 

 

 

 

 

 

 

pipe thermistor (ThO-D)

Repair

Defective discharge pipe

°C]

100

 

 

 

 

10

°C]

thermistor

Replacement

 

 

 

 

 

 

 

80

 

 

 

 

 

 

80

 

 

 

<

 

 

T< 80°C

 

 

 

>

 

 

 

)[T

 

 

 

 

T> 80°C

)[T

 

 

 

(k

 

 

 

 

 

 

(k

Display conditions

 

resistance

50

 

 

 

 

5

resistance

 

 

 

 

 

 

 

If the temperature sensed by the thermistor is –10ºC or lower con-

 

 

 

 

 

 

 

 

tinuously for 5 seconds between 10 minutes and 10 minutes 20

Thermistor

0

 

 

 

 

0

Thermistor

goes ON, the compressor stops. After a 3 minute delay, the com-

 

 

 

 

seconds (2minutes and 2minutes 20seconds) after the compressor

 

 

 

 

 

 

 

 

pressor restarts. If this state is detected 3 times in 40 (60) minutes.

 

0

20

50

80

100

120

 

Note (1) Values in (

) show for the case of the 301~601 models.

 

 

 

Temperature [T] (°C)

 

 

 

 

 

 

 

 

 

- 29 -

Image 31
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation Evacuation procedureCation Circuit Refrigerant chargingHigh side Low side IndiE10 E16 E28 Indoor unit LED Outdoor unit LED Selfdiagnosis function Check Indicator TableIndoor unit side No-indicationOutdoor unit side Timing of error detection Display sequence of error, inspection display lampWait Indoor unit Outdoor unit Recording and reset of errorProcedures of trouble diagnosis Error diagnosis procedures at the indoor unit sideControl change switch SW5, SW9, SW10 Change by the jumper wireParts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Drain motor Model Fdur seriesIndoor unit Outdoor unit Check method when the error code is displayApproximately Remote controller wire Is removedReplacement indoor Unit control PCB Red LED Time flash Stays OFF Green LED Keeps flashingRed LED 151~251301~601 Green LED Stays OFF or Lights Only case of FDTCases of other than FDT Red LED Stays OFFError display Detective return air thermistor Error display e6Defective indoor unit heat exchanger thermistor Indoor unit heat exchanger temp. ˚C Error display Heating overloadAbnormal Temperature Detection Error display Drain troubleOnly case of FDTA501, 601 types Error displayError display e16 Fan motor abnormalities E10Only case of 301 type Only case of Fdkn Only case of 151~251 typesDisplay conditions Within a period of 1 hourRemote controller therm Replacement Detective re Error display e28 Directive remote controller thermistorAre characteristics Detectivie remote controller PCBError diagnosis procedures at the outdoor units side Change by the JA3 Change by the jumper wireFunction of DIP switches SW5 Usually all turned OFF Parts layout on the outdoor unit PCB FDCVA151~251 typeFDCA301~601 type Overcurrent SettingPower transistor module Power supply phases reversed Only case of 301~601 type Error display Communications error during operationE32 Inverter primary current abnormal Only case of 151~251 type E33Compressor overcurrent trouble Only case of 301~601 type E34 Error display e35 Cooling overload operationAbnormal Temperature Detection Error display e36 Discharge temperature errorPressor is stopped 80 C Error display e39 Defective discharge pipe thermistorUtes 100Open phase at L3-phase of 52C primary side Error display e40 63H1 operation Only case of 301~601 typeError display e42 Current cut Only case of 151~251 type Inverter over-voltage trouble Only case of 151~251 type Error display e52 52C Abnormal Only case of 301~601 typeE47 E48E57 Insufficient refrigerant volumeMalfunction. If Did it improve? Replacement CompressorCould be causing Refrigerant circuitIs the power Power transistor module including drive circuit check methodCheck abnormal operation data with the remote controller Pull the cover downward to open it Remote controller Wired remote controllerIndoor unit functions I/U Function Remote controller unit functionsWhen Function is selected Function setting methodPress the ON/OFF button When I/U Function is selectedChanging the remote controller’s temperature setting range Checking Operation Data Cooling Test Operation ProcedureCanceling the Cooling Test Operation Starting the Cooling Test OperationHeating Setting SW5-1, SW5-2 on-siteTest run Test run method Checking the state of the unit in operationFdkn Series Indication board Fden SeriesWireless remote controller Page NATIONAL, State and Local Codes Installation of this equipment must comply with all