Hunter Fan R410A manual E33, Inverter primary current abnormal Only case of 151~251 type

Page 28

3

Error display

: e33

 

[Inverter primary current abnormal] [Only case of 151~251 type]

 

 

 

 

 

 

 

 

Indoor unit

 

 

Outdoor unit

 

Red LED

 

Stays OFF

 

Red LED

 

1 time flash

Green LED

 

Keeps flashing

 

 

 

 

Is the power supply normal? NO

YES

Is the voltage within

NO

the specified range?

 

 

YES

 

 

 

 

 

 

Is there any foreign matter

NO

such as dust or dirt on the control

 

 

PCB soldered surfaces?

 

 

YES

 

 

 

 

Restore it to the

normal state.

Restore it to the

normal state.

Remove any foreign matter

such as dust or dirt.

Display Conditions

If the inverter’s primary current exceeds the set value for 3 sec- onds, the compressor stops. After a 3 minute delay, it restarts, but when this occurs 5 times within 60 minutes.

Replace the control PCB.

[Compressor overcurrent trouble] [Only case of 301~601 type]

 

Indoor unit

 

Outdoor unit

Red LED

Stays OFF

Red LED

 

1 time flash

Green LED

Keeps flashing

Green LED

 

Keeps flashing

Is the voltage

AC220/240V between the NO L1 and L3 phases and between the L2

and L3 phases on the 52C

secondary side?

YES

 

 

• 52C is faulty.

Out of phase between the

 

• There is a disconnection between

L1 and L2 phases.

 

52C and CM or in the L1 and L2

 

 

 

 

phases between TB1 and 52C.

 

 

Check the unit side.

 

(1)

Is there overcurrent

YES

at the compressor?

 

NO

 

Outdoor unit control PCB is

faulty. Replace

(The CT input circuit is faulty.)

Is the power supply voltage proper? (Isn’t it too low?)

Are the power lines proper? (Aren’t they too thin?)

Is the overcurrent setting correct? (SW3 setting)

Is the compressor running with an overload?

Is the compressor locked?

During cooling: Is FMo turning?

During heating: Is FMI turning?

Is the service valve (gas side) fully open?

Is the filter clogged?

Is there an overcharge?

Is the installation space for the indoor and outdoor units proper?

Is there a short circuit in the indoor or outdoor units?

Compressor is faulty. Replace

Notes (1) Measure the overcurrent value to make sure.

Also make sure the overcurrent setting set with SW3 and SW4-1 on the outdoor unit control PCB

is not incorrect.

- 26 -

Image 28
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation procedure EvacuationRefrigerant charging High side Low sideIndi Cation CircuitSelfdiagnosis function Check Indicator Table Indoor unit sideNo-indication E10 E16 E28 Indoor unit LED Outdoor unit LEDOutdoor unit side Timing of error detection Display sequence of error, inspection display lampWait Recording and reset of error Procedures of trouble diagnosisError diagnosis procedures at the indoor unit side Indoor unit Outdoor unitControl change switch SW5, SW9, SW10 Change by the jumper wireParts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Model Fdur series Drain motorCheck method when the error code is display Indoor unit Outdoor unitRemote controller wire Is removed Replacement indoor Unit control PCBRed LED Time flash Stays OFF Green LED Keeps flashing ApproximatelyRed LED 151~251301~601 Only case of FDT Cases of other than FDTRed LED Stays OFF Green LED Stays OFF or LightsError display Detective return air thermistor Error display e6Defective indoor unit heat exchanger thermistor Error display Heating overload Abnormal Temperature DetectionError display Drain trouble Indoor unit heat exchanger temp. ˚CError display Error display e16 Fan motor abnormalitiesE10 Only case of FDTA501, 601 typesOnly case of Fdkn Only case of 151~251 types Display conditionsWithin a period of 1 hour Only case of 301 typeError display e28 Directive remote controller thermistor Are characteristicsDetectivie remote controller PCB Remote controller therm Replacement Detective reError diagnosis procedures at the outdoor units side Change by the jumper wire Function of DIP switches SW5 Usually all turned OFFParts layout on the outdoor unit PCB FDCVA151~251 type Change by the JA3Overcurrent Setting FDCA301~601 typePower transistor module Power supply phases reversed Only case of 301~601 type Error display Communications error during operationE32 Inverter primary current abnormal Only case of 151~251 type E33Compressor overcurrent trouble Only case of 301~601 type Error display e35 Cooling overload operation E34Abnormal Temperature Detection Error display e36 Discharge temperature errorPressor is stopped Error display e39 Defective discharge pipe thermistor Utes100 80 COpen phase at L3-phase of 52C primary side Error display e40 63H1 operation Only case of 301~601 typeError display e42 Current cut Only case of 151~251 type Error display e52 52C Abnormal Only case of 301~601 type E47E48 Inverter over-voltage trouble Only case of 151~251 typeInsufficient refrigerant volume E57Did it improve? Replacement Compressor Could be causingRefrigerant circuit Malfunction. IfPower transistor module including drive circuit check method Is the powerCheck abnormal operation data with the remote controller Remote controller Wired remote controller Pull the cover downward to open itRemote controller unit functions Indoor unit functions I/U FunctionFunction setting method When Function is selectedWhen I/U Function is selected Press the ON/OFF buttonChanging the remote controller’s temperature setting range Cooling Test Operation Procedure Canceling the Cooling Test OperationStarting the Cooling Test Operation Checking Operation DataSetting SW5-1, SW5-2 on-site Test run Test run methodChecking the state of the unit in operation HeatingIndication board Fden Series Fdkn SeriesWireless remote controller Page Installation of this equipment must comply with all NATIONAL, State and Local Codes