Hunter Fan R410A Selfdiagnosis function Check Indicator Table, Indoor unit side, No-indication

Page 6

(1)Selfdiagnosis function

(a)Check Indicator Table

Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote controller eroor code, indoor/outdoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).

1) Indoor unit side

1.3

- 4 -

Remote controller error code

No-indication

LCD flashes continuously or is off.

E1

E5

E6

E7

E8

E9

E10

E16

E28

Indoor unit LED

Outdoor unit LED

Green

Red

Green

Red

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Stays OFF

Stays OFF

Stays OFF

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

*3 time flash

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

2 time flash

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Stay OFF or Lights

Stay OFF

Keeps flashing

Stays OFF

continously

 

 

 

Keeps flashing

Stay OFF

Keeps flashing

Stays OFF

Keeps flashing

2 time flash

Keeps flashing

2 time flash

Keeps flashing

2 time flash

Stays OFF

Stays OFF

Keeps flashing

2 time flash

Keeps flashing

Stays OFF

Keeps flashing

1 time flash

Keeps flashing

Stays OFF

Keeps flashing

1 time flash

Keeps flashing

Stays OFF

Keeps flashing

1 time flash

Keeps flashing

Stays OFF

Keeps flashing

1 time flash

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Keeps flashing

Stays OFF

Cause

Normal

Power OFF, L phase wiring is open, power source failure

Indoor unit microcomputer failure

Remote controller wires X and Y are reversely connected. *For wire breaking at power ON, the LED is OFF. Remote controller wire is open. (X wire breaking : A beep is produced and no indication is made. Z wire breaking : No beep and no indication) The remote controller wires Y and Z are reversely connected.

Poor connection or disconnection in wires connecting the indoor and outdoor units.

When multiple remote controllers are used for control, the power supply to some indoor units is OFF.

Indoor unit PCB fault

The remote controller wire Y is open. The remote controller wires X and Y are reversely connected. Noise is penetrating the remote control lines. The remote controller or indoor control PCB is faulty. (The communications circuit is faulty.)

Indoor / outdoor transmission error.

Outdoor unit control PCB is faulty when the power is turned on, or the inverter parts are faulty (FDCVA 151~251 type).

Outdoor unit microcomputer failure

Indoor unit heat exchanger thermistor failure

Indoor unit return air thermistor failure

Heating overload (indoor heat exchanger temperature is abnormally high) and indoor heat exchanger thermistor is faulty.

The float SW operates (with FS only). Drain up kit wiring fault.

When multi-unit control by remote controller is performed, the number of units is over (more than 17 units). Two remote controller are provided for one controller is performed.

Fan motor is faulty (FDTA 501, 601 type, FDKN type).

Remote controller thermistor failure

Diagnosing of microcomputer circuit

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.

Image 6
Contents FDA Series Split Systems FDA Series Multi Systems Page Index Evacuation procedure EvacuationIndi Refrigerant chargingHigh side Low side Cation CircuitNo-indication Selfdiagnosis function Check Indicator TableIndoor unit side E10 E16 E28 Indoor unit LED Outdoor unit LEDOutdoor unit side Display sequence of error, inspection display lamp Timing of error detectionWait Error diagnosis procedures at the indoor unit side Recording and reset of errorProcedures of trouble diagnosis Indoor unit Outdoor unitChange by the jumper wire Control change switch SW5, SW9, SW10Parts layout on the indoor unit PCB Model FDT series Model Fden series Model Fdkn series Model Fdur series Drain motorCheck method when the error code is display Indoor unit Outdoor unitRed LED Time flash Stays OFF Green LED Keeps flashing Remote controller wire Is removedReplacement indoor Unit control PCB Approximately151~251 Red LED301~601 Red LED Stays OFF Only case of FDTCases of other than FDT Green LED Stays OFF or LightsError display e6 Error display Detective return air thermistorDefective indoor unit heat exchanger thermistor Error display Drain trouble Error display Heating overloadAbnormal Temperature Detection Indoor unit heat exchanger temp. ˚CE10 Error displayError display e16 Fan motor abnormalities Only case of FDTA501, 601 typesWithin a period of 1 hour Only case of Fdkn Only case of 151~251 typesDisplay conditions Only case of 301 typeDetectivie remote controller PCB Error display e28 Directive remote controller thermistorAre characteristics Remote controller therm Replacement Detective reError diagnosis procedures at the outdoor units side Parts layout on the outdoor unit PCB FDCVA151~251 type Change by the jumper wireFunction of DIP switches SW5 Usually all turned OFF Change by the JA3Overcurrent Setting FDCA301~601 typePower transistor module Error display Communications error during operation Power supply phases reversed Only case of 301~601 typeE32 E33 Inverter primary current abnormal Only case of 151~251 typeCompressor overcurrent trouble Only case of 301~601 type Error display e35 Cooling overload operation E34Error display e36 Discharge temperature error Abnormal Temperature DetectionPressor is stopped 100 Error display e39 Defective discharge pipe thermistorUtes 80 CError display e40 63H1 operation Only case of 301~601 type Open phase at L3-phase of 52C primary sideError display e42 Current cut Only case of 151~251 type E48 Error display e52 52C Abnormal Only case of 301~601 typeE47 Inverter over-voltage trouble Only case of 151~251 typeInsufficient refrigerant volume E57Refrigerant circuit Did it improve? Replacement CompressorCould be causing Malfunction. IfPower transistor module including drive circuit check method Is the powerCheck abnormal operation data with the remote controller Remote controller Wired remote controller Pull the cover downward to open itRemote controller unit functions Indoor unit functions I/U FunctionFunction setting method When Function is selectedWhen I/U Function is selected Press the ON/OFF buttonChanging the remote controller’s temperature setting range Starting the Cooling Test Operation Cooling Test Operation ProcedureCanceling the Cooling Test Operation Checking Operation DataChecking the state of the unit in operation Setting SW5-1, SW5-2 on-siteTest run Test run method HeatingIndication board Fden Series Fdkn SeriesWireless remote controller Page Installation of this equipment must comply with all NATIONAL, State and Local Codes