(5) Test run
(a)Test run method
1)A test run can be initiated from an outdoor unit by using SW9 (SW2) and
2)Models FDCVA151~251
When SW9 (press button switch) is pressed for 1 second and then released, the compressor will start operation approxi- mately 5 seconds later.
Models FDCA301~601
Press SW2
3)The unit will start a cooling operation, when
4)When a test run is completed, press SW9 (SW2)
Note (1) Items in ( ) show for the FDCA 301~601.
(b)Checking the state of the unit in operation
Check discharge pressure and suction pressure, using the check joint provided inside the outdoor unit and the gas charge valve charge port. The check joint in the unit is provided on the pipe connecting the
| Check joint in the unit | Gas operation valve charge port |
|
|
|
Cooling | Discharge pressure (high pressure) | Suction pressure (low pressure) |
|
|
|
Heating | Suction pressure (low pressure) | Discharge pressure (high pressure) |
|
|
|
(c)Setting SW5-1, SW5-2 on-site
1)Defrost conteol switching
a)When this switch is turned on, the unit will run in the defrost mode more frequentiy.
b)Please set this switch to ON, when installed in a region where outdoor temperaure falls below zero during the season the unit is run for a heating operation.
2)Snow guard fan control
a)When this switch is turned on, the outdoor unit fan will run for 10 seconds in every 10 minutes, when outdoor tempera- ture falls to 3˚C or lower and the compressor is not running.
b)When the unit is used in a very snowy country, please set this switch to ON.
- 42-