Enviro EA800 System Configuration Parameters, will sound when an alarm occurs if DISABLE is

Page 13
System Configuration Parameters

General Information

System Configuration Parameters

The EA800 base unit requires certain system level information as outlined in Table 4.

Table 4 System Configuration Parameters

Parameter

Selections

Factory Default

 

Description

 

 

 

 

 

 

 

Date Format

• MM/DD/YYYY

MM/DD/YYYY

 

Sets the desired date format for all event time stamps.

 

 

• DD/MM/YYYY

 

 

 

 

 

 

 

 

 

 

Time Format

12-hour

24-hour

 

Sets the desired time format for all event time stamps.

 

 

24-hour

 

 

 

 

 

 

 

 

 

Data Collec-

• 30 seconds

5 minutes

Sets the interval for collecting and recording data from the

 

tion Fre-

• 1 minute

 

 

sensors. The data collection frequency applies to all sen-

 

quency

• 5 minutes

 

 

sors.The EA800 provides approximately 10,000 data

 

 

• 15 minutes

 

 

points to be collected regardless of the frequency

 

 

• 30 minutes

 

 

selected. The estimated time duration covered for each

 

 

 

 

data collection frequency is listed below.

 

 

• 60 minutes

 

 

 

 

 

 

30 seconds = 3.5 days

 

 

 

 

 

 

 

 

 

 

1 minute = 1 week

 

 

 

 

 

5 minutes = 1 month

 

 

 

 

 

15 minutes = 3 months

 

 

 

 

 

30 minutes = 6 months

 

 

 

 

 

60 minutes = 1 year

 

 

 

 

 

 

 

Buzzer

• Enable

Enabled

 

Enables and disables the buzzer when an alarm limit has

 

 

• Disable

 

 

been exceeded or a warning condition exists.

 

 

 

 

 

! WARNING

 

 

 

 

 

Selecting Disable for this parameter turns the audible

 

 

 

 

 

alarm buzzer off completely. No audible alarm tone

 

 

 

 

 

will sound when an alarm occurs if DISABLE is

 

 

 

 

 

selected.

 

 

 

 

 

 

 

RF Channel

11 (2405 MHz)

channel 16

 

Selects the ISM band radio frequency (RF) channel for

 

 

12 (2410 MHz)

 

 

transmission between the wireless sensors and EA800

 

 

13 (2415 MHz)

 

 

base unit.

 

 

 

 

 

 

 

14 (2420 MHz)

 

 

 

 

 

15 (2425 MHz)

 

 

 

 

 

16 (2430 MHz)

 

 

 

 

 

17 (2435 MHz)

 

 

 

 

 

18 (2440 MHz)

 

 

 

 

 

19 (2445 MHz)

 

 

 

 

 

20 (2450 MHz)

 

 

 

 

 

21 (2455 MHz)

 

 

 

 

 

22 (2460 MHz)

 

 

 

 

 

23 (2465 MHz)

 

 

 

 

 

24 (2470 MHz)

 

 

 

 

 

25 (2475 MHz)

 

 

 

 

 

26 (2480 MHz)

 

 

 

 

 

 

 

 

 

 

D-011-0152

9

Image 13
Contents D-011-0152 Limitations of the Alarm System or Device Installation Table of ContentsGeneral Information PreparationOperation Overview General InformationHow to Use This Manual General Information Block DiagramsD-011-0152 Symbols on the Product or Manual Labeling General Information Monitoring ScreensD-011-0152 Keys Base Unit Connections Access Control and Passwords will sound when an alarm occurs if DISABLE is System Configuration Parametersselected Temperature Sensors Sensors4-20mASensors Humidity SensorsTheory of Operation Power Supply / Sensor Voltage Selection Multi-FunctionSensors Water SensorsContact Closure Sensors Resolution Sensor Parameter DescriptionsMaximum Allowed High Scaled ValueRelay Operation D-011-0152 Relay OperationPreparation D-011-0152 To alarm-on-closed From 11-26VDC power supplyloop circuit power supplied via loop From 11-26VDC power supplyD-011-0152 Power Requirements InstallationTools and Supplies Required Mounting the EA800 Rear PlateEA800 Base Unit Power Connections Install the Wired SensorsInstall the Wireless Sensors SENSOR MODEL NO RESET BUTTONSENSOR MODEL NO RESET BUTTOND-011-0152 J6 Input 1 Input 2 Input 3 InputConnecting Wired HA-III+Humidity Sensors Connecting Wired 4-20mASensors Programming Connecting the EA800 Alarm OutputsConfiguring System Parameter Settings Accessing the MAIN MENU for Programming3.Enter the SYSTEM menu and then select the CONFIGURATION menu as shown below DISABLED is selected Setting the Current Date D-011-0152 Setting the TimeAdding a Wireless Temperature Sensor Adding Wireless SensorsD-011-0152 Adding Wireless SensorsD-011-0152 InstallationD-011-0152 Installation Adding a Wireless Humidity SensorD-011-0152 D-011-0152 D-011-0152 InstallationD-011-0152 Select N.O. Contact or N.C. Contact InstallationD-011-0152 D-011-0152 Verify Wireless Signal StrengthAdding a Wired Temperature Sensor Adding Wired SensorsAdding Wired Sensors Adding a Wired HA-III+Humidity SensorD-011-0152 Note A supervised WaterBug sensor must be used Adding a Wired WaterBug SensorSelect N.O. Contact or N.C. Contact Adding a Wired Contact Closure SensorD-011-0152 Adding a 4-20mASensor Configuring the Relays Monitoring Environmental Conditions OperationViewing Active Alarms Viewing Sensor SettingsViewing Pending Alarm Information Viewing the Alarm LogViewing the Event Log Viewing Limit SettingsViewing Firmware Information Viewing the Sensor LogOperation D-011-0152Viewing RF Information Viewing RF InformationLocking and Unlocking the EA800 MaintenancePausing Monitoring and Cancelling Pause Replacing a Sensor Adding a SensorSENSORS screen Editing Sensor ParametersDeleting a Sensor Reprogramming a RelayF3 F3 Changing the Time Format Changing the Date FormatChanging Sensor Data Collection Frequency Changing the Date or Time SettingChanging the Buzzer Setting Changing the Buzzer SettingMaintenance Changing the PasswordD-011-0152 Clearing the Sensor Log Clearing the Alarm LogClearing the Alarm Log Maintenance Updating the FirmwareD-011-0152 F3 LOAD/SAVE CONFIG screen Saving Configuration SettingsCONFIG screen Loading Configuration SettingsExporting the Stored Logs Exported Alarm DataExported Sensor Data Exported Event Data12/24/2007 07 06 03 PM Sensor deletedD-011-0152 Exporting the Stored LogsACTIVE ALARMS screen TroubleshootingViewing Signal Strength for a Wireless Sensor Verifying RF Signal StrengthBase Unit and Sensor Specifications SpecificationsAccessories Figure 17. Locked Screen Map Appendix A Screen MapsD-011-0152 Figure 18. Unlocked Screen Map - Top LevelFigure 19. Sensors Screen Map Appendix A Screen MapsD-011-0152 D-011-0152 Figure 20. Add New Sensor Screen MapFigure 21. Edit Sensor Screen Map Appendix A Screen MapsFigure 22. Relay Screen Map D-011-0152D-011-0152 Figure 23. Data Log Screen MapFigure 24. System Screen Map Appendix A Screen MapsD-011-0152 D-011-0152 Figure 25. Configuration Screen MapInstallation Appendix B Planning WorksheetAlarm Condition Appendix B Planning WorksheetD-011-0152 Appendix C Wiring DiagramD-011-0152 Appendix D System Configuration Record Unit of Measure Appendix D System Configuration Record Sensor 6 Settings wireless Appendix D System Configuration Record D-011-0152 Warranty and Service Information Winland Electronics Manufactured in the U.S.A by1950 Excel Drive, Mankato, MN, Outside MN Phone Phone Fax