Enviro EA800 owner manual Adding Wired Sensors, Adding a Wired Temperature Sensor

Page 47
Adding Wired Sensors

Installation

Adding Wired Sensors

Low temperature sensors - Blue Thermistor Probes: See “Adding a Wired Temperature Sensor” on page 43.

High temperature sensors - Red Thermistor Probes: See “Adding a Wired Temperature Sensor” on page 43.

Ultra Low temperature sensors - White Thermistor Probes: See “Adding a Wired Temperature Sensor” on page 43.

HA-III+ humidity sensor: See “Adding a Wired HA-III+ Humidity Sensor” on page 44.

WaterBug sensor: See “Adding a Wired WaterBug Sensor” on page 45.

N.O. Contact: See “Adding a Wired Contact Closure Sensor” on page 46.

N.C. Contact: See “Adding a Wired Contact Closure Sensor” on page 46.

4-20 mA: See “Adding a 4-20mA Sensor” on page 47.

Adding a Wired Temperature Sensor

The procedure shown below adds a wired Blue temperature sensor, but is applicable to the wired Red and White temperature sensors as well.

The Hysteresis setting helps prevent alarms from being set and reset continually if the environment is at or near the alarm set point by providing an acceptable variance. For example, if HYSTERESIS is set at 1 and the sensor High Alarm Limit is set at +158, the sensor reading must decrease to +157 (+157 minus 1) in order for the temperature alarm to reset to a no-alarm condition.

When setting numeric values, use the arrow keys to change the value. Use the PREV and NEXT soft keys to move the cursor to the next or previous digit. Press the ENTER key to enter the value.

NOTE: Select the sensor number that matches the input number used by the sensor, or an alarm may result.

Example values are shown, Set all limit values as appropriate for your system.

 

 

 

 

 

 

 

 

This is the start screen for the next

 

 

 

 

F3

 

 

 

sensor to be added, if any.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D-011-0152

43

Image 47
Contents D-011-0152 Limitations of the Alarm System or Device Preparation Table of ContentsInstallation General InformationOperation Overview General InformationHow to Use This Manual D-011-0152 Block DiagramsGeneral Information Symbols on the Product or Manual Labeling D-011-0152 Monitoring ScreensGeneral Information Keys Base Unit Connections Access Control and Passwords selected System Configuration Parameterswill sound when an alarm occurs if DISABLE is Temperature Sensors SensorsTheory of Operation Humidity Sensors4-20mASensors Power Supply / Sensor Voltage Selection Contact Closure Sensors Water SensorsMulti-FunctionSensors High Scaled Value Sensor Parameter DescriptionsResolution Maximum AllowedRelay Operation D-011-0152 Relay OperationPreparation D-011-0152 From 11-26VDC power supply From 11-26VDC power supplyTo alarm-on-closed loop circuit power supplied via loopD-011-0152 Mounting the EA800 Rear Plate InstallationPower Requirements Tools and Supplies RequiredInstall the Wireless Sensors Install the Wired SensorsEA800 Base Unit Power Connections SENSOR MODEL NO RESET BUTTONJ6 Input 1 Input 2 Input 3 Input RESET BUTTONSENSOR MODEL NO D-011-0152Connecting Wired HA-III+Humidity Sensors Connecting Wired 4-20mASensors Programming Connecting the EA800 Alarm OutputsConfiguring System Parameter Settings Accessing the MAIN MENU for Programming3.Enter the SYSTEM menu and then select the CONFIGURATION menu as shown below DISABLED is selected Setting the Current Date D-011-0152 Setting the TimeAdding a Wireless Temperature Sensor Adding Wireless SensorsD-011-0152 Adding Wireless SensorsD-011-0152 InstallationD-011-0152 D-011-0152 Adding a Wireless Humidity SensorInstallation D-011-0152 D-011-0152 InstallationD-011-0152 D-011-0152 InstallationSelect N.O. Contact or N.C. Contact D-011-0152 Verify Wireless Signal StrengthAdding a Wired Temperature Sensor Adding Wired SensorsD-011-0152 Adding a Wired HA-III+Humidity SensorAdding Wired Sensors Note A supervised WaterBug sensor must be used Adding a Wired WaterBug SensorD-011-0152 Adding a Wired Contact Closure SensorSelect N.O. Contact or N.C. Contact Adding a 4-20mASensor Configuring the Relays Monitoring Environmental Conditions OperationViewing Active Alarms Viewing Sensor SettingsViewing Pending Alarm Information Viewing the Alarm LogViewing the Event Log Viewing Limit SettingsD-011-0152 Viewing the Sensor LogViewing Firmware Information OperationViewing RF Information Viewing RF InformationLocking and Unlocking the EA800 MaintenancePausing Monitoring and Cancelling Pause Replacing a Sensor Adding a SensorSENSORS screen Editing Sensor ParametersF3 F3 Reprogramming a RelayDeleting a Sensor Changing the Time Format Changing the Date FormatChanging Sensor Data Collection Frequency Changing the Date or Time SettingChanging the Buzzer Setting Changing the Buzzer SettingD-011-0152 Changing the PasswordMaintenance Clearing the Alarm Log Clearing the Alarm LogClearing the Sensor Log D-011-0152 Updating the FirmwareMaintenance F3 LOAD/SAVE CONFIG screen Saving Configuration SettingsCONFIG screen Loading Configuration SettingsExporting the Stored Logs Exported Alarm DataSensor deleted Exported Event DataExported Sensor Data 12/24/2007 07 06 03 PMD-011-0152 Exporting the Stored LogsACTIVE ALARMS screen TroubleshootingViewing Signal Strength for a Wireless Sensor Verifying RF Signal StrengthBase Unit and Sensor Specifications SpecificationsAccessories Figure 17. Locked Screen Map Appendix A Screen MapsD-011-0152 Figure 18. Unlocked Screen Map - Top LevelD-011-0152 Appendix A Screen MapsFigure 19. Sensors Screen Map D-011-0152 Figure 20. Add New Sensor Screen MapD-011-0152 Appendix A Screen MapsFigure 21. Edit Sensor Screen Map Figure 22. Relay Screen MapD-011-0152 Figure 23. Data Log Screen MapD-011-0152 Appendix A Screen MapsFigure 24. System Screen Map D-011-0152 Figure 25. Configuration Screen MapAppendix B Planning Worksheet Appendix B Planning WorksheetInstallation Alarm ConditionD-011-0152 Appendix C Wiring DiagramD-011-0152 Appendix D System Configuration Record Unit of Measure Appendix D System Configuration Record Sensor 6 Settings wireless Appendix D System Configuration Record D-011-0152 Warranty and Service Information Phone Fax Manufactured in the U.S.A byWinland Electronics 1950 Excel Drive, Mankato, MN, Outside MN Phone