Enviro EA800 owner manual D-011-0152

Page 22
Manual background

5.Complete the copy of Appendix B: Planning Worksheet for the facility in which the EA800 system is to be installed. This must include all monitored areas for the total security system so that you know how many EA800 base units are needed.

6.Determine the sensors required from the Planning Worksheet you completed and the information provided for each sensor type in “System Configuration”. Enter these in the copy of the System Configuration Record you made.

Note: When water sensors are required, you must use at least one supervised water sensor and may add up to five additional unsupervised water sensors, all in parallel. Thus, an alarm on any sensor will result in an alarm with no way to determine which sensor is the source.

7.Enter the sensor information in the copy of the EA800 Wiring Diagram you made. It is a good idea to name each sensor on this diagram and use that name in both the EA800 Wiring Diagram and the System Configuration Record. This helps ensure proper programming of the system after you have physically installed the system.

!WARNING

!CAUTION

EA800 relay outputs are intended only for use as low-voltage, low-current alarm connections, and not for direct switching or control of AC-mains powered loads. Additionally, local codes may further dictate or limit the types of loads and associated wiring to be used with the low-current Form C relay outputs used with the EA800. Connecting AC-mains type circuits to the EA800 may result in an electric shock and/or fire hazard.

Do not connect a load to the AUX OUT or OUTPUT 1 through OUTPUT 8 relay outputs that exceeds limitations stated in the Specifications section of this manual. Loads exceeding the specified limitations may damage the EA800, or result in improper or unreliable operation.

8.Using the floor plan you created, identify the specific locations for each sensor and verify that their locations meet the specifications. See Specifications for operational parameters such as cable length.

Note: For 4-20mA sensors: See 4-20mA Sensors for a discussion of determining the constraints for your 4-20mA sensor to ensure accuracy over its rated range.

9.Determine the channel to use for the wireless sensors. If more than one EA800 is being installed on-site, it is recommended that they be configured to use different channels.

10.The wireless sensor must be located so that the wireless signal strength is adequate as outlined in Winland Application Note AN00101. You must verify that the wireless sensors can communicate with the base unit before you permanently mount them.

Note: Certain environments may present conditions that intermittently cause interference with wireless sensor to base unit communications. You should understand the environment in which the EA800 is to operate to minimize their affects on system performance.

11.Decide the loop design you will use. Figure 9 shows an alarm loop where alarm power is derived from the alarm loop. Figure 10 shows an alarm loop where alarm power is derived from the power supply feeding the EA800.

Note: if using a self-powered loop, ensure the power supply can provide power for all loading conditions.

18

D-011-0152

Image 22
Contents D-011-0152 Limitations of the Alarm System or Device General Information Table of ContentsInstallation PreparationOperation General Information OverviewHow to Use This Manual General Information Block DiagramsD-011-0152 Symbols on the Product or Manual Labeling General Information Monitoring ScreensD-011-0152 Keys Base Unit Connections Access Control and Passwords will sound when an alarm occurs if DISABLE is System Configuration Parametersselected Sensors Temperature Sensors4-20mASensors Humidity SensorsTheory of Operation Power Supply / Sensor Voltage Selection Multi-FunctionSensors Water SensorsContact Closure Sensors Maximum Allowed Sensor Parameter DescriptionsResolution High Scaled ValueRelay Operation Relay Operation D-011-0152Preparation D-011-0152 loop circuit power supplied via loop From 11-26VDC power supplyTo alarm-on-closed From 11-26VDC power supplyD-011-0152 Tools and Supplies Required InstallationPower Requirements Mounting the EA800 Rear PlateEA800 Base Unit Power Connections Install the Wired SensorsInstall the Wireless Sensors RESET BUTTON SENSOR MODEL NOD-011-0152 RESET BUTTONSENSOR MODEL NO J6 Input 1 Input 2 Input 3 InputConnecting Wired HA-III+Humidity Sensors Connecting Wired 4-20mASensors Connecting the EA800 Alarm Outputs ProgrammingAccessing the MAIN MENU for Programming Configuring System Parameter Settings3.Enter the SYSTEM menu and then select the CONFIGURATION menu as shown below DISABLED is selected Setting the Current Date Setting the Time D-011-0152Adding Wireless Sensors Adding a Wireless Temperature SensorAdding Wireless Sensors D-011-0152Installation D-011-0152D-011-0152 Installation Adding a Wireless Humidity SensorD-011-0152 D-011-0152 Installation D-011-0152D-011-0152 Select N.O. Contact or N.C. Contact InstallationD-011-0152 Verify Wireless Signal Strength D-011-0152Adding Wired Sensors Adding a Wired Temperature SensorAdding Wired Sensors Adding a Wired HA-III+Humidity SensorD-011-0152 Adding a Wired WaterBug Sensor Note A supervised WaterBug sensor must be usedSelect N.O. Contact or N.C. Contact Adding a Wired Contact Closure SensorD-011-0152 Adding a 4-20mASensor Configuring the Relays Operation Monitoring Environmental ConditionsViewing Sensor Settings Viewing Active AlarmsViewing the Alarm Log Viewing Pending Alarm InformationViewing Limit Settings Viewing the Event LogOperation Viewing the Sensor LogViewing Firmware Information D-011-0152Viewing RF Information Viewing RF InformationMaintenance Locking and Unlocking the EA800Pausing Monitoring and Cancelling Pause Adding a Sensor Replacing a SensorEditing Sensor Parameters SENSORS screenDeleting a Sensor Reprogramming a RelayF3 F3 Changing the Date Format Changing the Time FormatChanging the Date or Time Setting Changing Sensor Data Collection FrequencyChanging the Buzzer Setting Changing the Buzzer SettingMaintenance Changing the PasswordD-011-0152 Clearing the Sensor Log Clearing the Alarm LogClearing the Alarm Log Maintenance Updating the FirmwareD-011-0152 Saving Configuration Settings F3 LOAD/SAVE CONFIG screenLoading Configuration Settings CONFIG screenExported Alarm Data Exporting the Stored Logs12/24/2007 07 06 03 PM Exported Event DataExported Sensor Data Sensor deletedExporting the Stored Logs D-011-0152Troubleshooting ACTIVE ALARMS screenVerifying RF Signal Strength Viewing Signal Strength for a Wireless SensorSpecifications Base Unit and Sensor SpecificationsAccessories Appendix A Screen Maps Figure 17. Locked Screen MapFigure 18. Unlocked Screen Map - Top Level D-011-0152Figure 19. Sensors Screen Map Appendix A Screen MapsD-011-0152 Figure 20. Add New Sensor Screen Map D-011-0152Figure 22. Relay Screen Map Appendix A Screen MapsFigure 21. Edit Sensor Screen Map D-011-0152Figure 23. Data Log Screen Map D-011-0152Figure 24. System Screen Map Appendix A Screen MapsD-011-0152 Figure 25. Configuration Screen Map D-011-0152Alarm Condition Appendix B Planning WorksheetInstallation Appendix B Planning WorksheetD-011-0152 C Wiring Diagram AppendixD-011-0152 Appendix D System Configuration Record Unit of Measure Appendix D System Configuration Record Sensor 6 Settings wireless Appendix D System Configuration Record D-011-0152 Warranty and Service Information 1950 Excel Drive, Mankato, MN, Outside MN Phone Manufactured in the U.S.A byWinland Electronics Phone Fax