Connecting the EA800 Alarm Outputs

Installation

Connecting the EA800 Alarm Outputs

 

 

If the EA800 base unit will be connected to a remote alarm panel, do not connect

!

CAUTION

the base unit to the alarm panel until after sensor connection and configuration

 

 

 

 

is complete. Connecting the remote alarm panel before configuring the EA800

 

 

sensors will result in false alarms at the remote panel.

1.If alarm loops will be controlled by the EA800, install all required wiring from alarm loops to the EA800 mounting location.

2.Connect the alarm loop leads to the terminal block adapter. Attach the adapter to terminals C and either NC or NO on the appropriate circuit board header connector.

3.Repeat the previous step for each alarm loop.

4.Engage the mating tabs on the EA800 main chassis into the mounting plate upper hinges.

5.Pivot the bottom of the EA800 main chassis into closed position while aligning the retainer tabs on the main chassis with the holes in the rear mounting plate and ensure that the wiring is not pinched, stressed, or protruding between the chassis halves.

6.Snap the main chassis closed onto the mounting plate. When properly closed, the main chassis and mounting plate mating surfaces are flush.

Programming

When powered-up, the EA800 is ready for programming. The following is an overview of the general process for programming the EA800:

View the MAIN MENU and unlock the EA800 as described in “Accessing the MAIN MENU for Programming” on page 28.

Set the system configuration as described in “Configuring System Parameter Settings” on page 28.

Set the current date as described in “Setting the Current Date” on page 31.

Set the current time as described in “Setting the Time” on page 32.

Add the wireless sensors. See the appropriate subsection under “Adding Wireless Sensors” on page 33.

Add the wired sensors. See the appropriate subsection under “Adding Wired Sensors” on page 43.

Verify performance of the wireless sensors. See “Verify Wireless Signal Strength” on page 42.

Configure the relays. See “Configuring the Relays” on page 48.

 

 

If the EA800 base unit will be connected to a remote alarm panel, do not connect

!

CAUTION

the base unit to the alarm panel until after sensor connection and configuration

 

 

 

 

is complete. Connecting the remote alarm panel before configuring the EA800

 

 

sensors will result in false alarms at the remote panel.

Note: When no sensors are programmed in the EA800 system, the EA800 base unit boots up with a 30-minute delay before the alarm buzzer sounds. At this time the Alarm screen is displayed with a System Alarm caused by the fact that no sensors have been programmed yet. To prevent the System Alarm from going off, you must program at least 1 connected sensor into the EA800 base unit prior to the end of the

30-minute alarm time-out. If the alarm buzzer sounds press the Alarm Silence key to temporarily silence the alarm buzzer.

D-011-0152

27

Image 31
Contents D-011-0152 Limitations of the Alarm System or Device Preparation Table of ContentsInstallation General InformationOperation Overview General InformationHow to Use This Manual General Information Block DiagramsD-011-0152 Symbols on the Product or Manual Labeling General Information Monitoring ScreensD-011-0152 Keys Base Unit Connections Access Control and Passwords will sound when an alarm occurs if DISABLE is System Configuration Parametersselected Temperature Sensors Sensors4-20mASensors Humidity SensorsTheory of Operation Power Supply / Sensor Voltage Selection Multi-FunctionSensors Water SensorsContact Closure Sensors High Scaled Value Sensor Parameter DescriptionsResolution Maximum AllowedRelay Operation D-011-0152 Relay OperationPreparation D-011-0152 From 11-26VDC power supply From 11-26VDC power supplyTo alarm-on-closed loop circuit power supplied via loopD-011-0152 Mounting the EA800 Rear Plate InstallationPower Requirements Tools and Supplies RequiredEA800 Base Unit Power Connections Install the Wired SensorsInstall the Wireless Sensors SENSOR MODEL NO RESET BUTTONJ6 Input 1 Input 2 Input 3 Input RESET BUTTONSENSOR MODEL NO D-011-0152Connecting Wired HA-III+Humidity Sensors Connecting Wired 4-20mASensors Programming Connecting the EA800 Alarm OutputsConfiguring System Parameter Settings Accessing the MAIN MENU for Programming3.Enter the SYSTEM menu and then select the CONFIGURATION menu as shown below DISABLED is selected Setting the Current Date D-011-0152 Setting the TimeAdding a Wireless Temperature Sensor Adding Wireless SensorsD-011-0152 Adding Wireless SensorsD-011-0152 InstallationD-011-0152 Installation Adding a Wireless Humidity SensorD-011-0152 D-011-0152 D-011-0152 InstallationD-011-0152 Select N.O. Contact or N.C. Contact InstallationD-011-0152 D-011-0152 Verify Wireless Signal StrengthAdding a Wired Temperature Sensor Adding Wired SensorsAdding Wired Sensors Adding a Wired HA-III+Humidity SensorD-011-0152 Note A supervised WaterBug sensor must be used Adding a Wired WaterBug SensorSelect N.O. Contact or N.C. Contact Adding a Wired Contact Closure SensorD-011-0152 Adding a 4-20mASensor Configuring the Relays Monitoring Environmental Conditions OperationViewing Active Alarms Viewing Sensor SettingsViewing Pending Alarm Information Viewing the Alarm LogViewing the Event Log Viewing Limit SettingsD-011-0152 Viewing the Sensor LogViewing Firmware Information OperationViewing RF Information Viewing RF InformationLocking and Unlocking the EA800 MaintenancePausing Monitoring and Cancelling Pause Replacing a Sensor Adding a SensorSENSORS screen Editing Sensor ParametersDeleting a Sensor Reprogramming a RelayF3 F3 Changing the Time Format Changing the Date FormatChanging Sensor Data Collection Frequency Changing the Date or Time SettingChanging the Buzzer Setting Changing the Buzzer SettingMaintenance Changing the PasswordD-011-0152 Clearing the Sensor Log Clearing the Alarm LogClearing the Alarm Log Maintenance Updating the FirmwareD-011-0152 F3 LOAD/SAVE CONFIG screen Saving Configuration SettingsCONFIG screen Loading Configuration SettingsExporting the Stored Logs Exported Alarm DataSensor deleted Exported Event DataExported Sensor Data 12/24/2007 07 06 03 PMD-011-0152 Exporting the Stored LogsACTIVE ALARMS screen TroubleshootingViewing Signal Strength for a Wireless Sensor Verifying RF Signal StrengthBase Unit and Sensor Specifications SpecificationsAccessories Figure 17. Locked Screen Map Appendix A Screen MapsD-011-0152 Figure 18. Unlocked Screen Map - Top LevelFigure 19. Sensors Screen Map Appendix A Screen MapsD-011-0152 D-011-0152 Figure 20. Add New Sensor Screen MapD-011-0152 Appendix A Screen MapsFigure 21. Edit Sensor Screen Map Figure 22. Relay Screen MapD-011-0152 Figure 23. Data Log Screen MapFigure 24. System Screen Map Appendix A Screen MapsD-011-0152 D-011-0152 Figure 25. Configuration Screen MapAppendix B Planning Worksheet Appendix B Planning WorksheetInstallation Alarm ConditionD-011-0152 Appendix C Wiring DiagramD-011-0152 Appendix D System Configuration Record Unit of Measure Appendix D System Configuration Record Sensor 6 Settings wireless Appendix D System Configuration Record D-011-0152 Warranty and Service Information Phone Fax Manufactured in the U.S.A byWinland Electronics 1950 Excel Drive, Mankato, MN, Outside MN Phone