Enviro EA800 owner manual Operation, Monitoring Environmental Conditions

Page 53
Operation

Operation

This chapter provides instructions for doing the following:

“Monitoring Environmental Conditions” on page 49

“Viewing Sensor Settings” on page 50

“Viewing Active Alarms” on page 50

“Viewing the Alarm Log” on page 51

“Viewing Pending Alarm Information” on page 51

“Viewing Limit Settings” on page 52

“Viewing the Event Log” on page 52

“Viewing the Sensor Log” on page 53

“Viewing Firmware Information” on page 53

“Viewing RF Information” on page 54

Monitoring Environmental Conditions

The current environmental conditions measured by each sensor connected to the EA800 base unit are shown on the home screen. Depending on the current sensor status the home screen may be one of the following screens:

MONITORING screen: This screen is shown when there are no active alarms or pending alarms. This screen displays the current readings from all programmed sensors as shown in the example below.

Note: Dashes indicate that a sensor has not been programmed yet.

Current Date

This column shows

environmental readingsMonitoring Environmental Conditions for wired sensors 1-4. Manual background

Sensor 1

Sensor 2

Sensor 3

Sensor 4 Manual backgroundManual background

Current Time

This column shows

Manual background environmental readings

for wireless sensors 5-8.

Manual backgroundManual background Sensor 5

Sensor 6

Manual background Sensor 7 (not installed) Manual backgroundManual background Sensor 8 (not installed)

MONITORING screen with pending alarm. A pending alarm indicates that a sensor has exceeded the low or high limits but that the condition has not exceeded the programmed delay (0 to 120 minutes). When an alarm is pending, the sensor’s reading is displayed in reverse text as shown in the example for wired sensor 2.

If conditions in the sensor’s area return to the non-alarm state within the alarm delay time, the text returns to normal. If conditions remain

outside the programmed sensor alarm limits for longer than the delay

Pending alarm

time, the screen changes to the ACTIVE ALARMS screen below.

 

.ACTIVE ALARMS Screen: This screen is displayed when conditions monitored by any programmed sensor exceed one of its programmed limits for longer than the programmed delay period. Only the active alarm(s) is displayed as shown in the example below. See “Viewing Active Alarms” on page 50 for the procedure to access alarm information

D-011-0152

49

Image 53
Contents D-011-0152 Limitations of the Alarm System or Device Installation Table of ContentsGeneral Information PreparationOperation Overview General InformationHow to Use This Manual D-011-0152 Block DiagramsGeneral Information Symbols on the Product or Manual Labeling D-011-0152 Monitoring ScreensGeneral Information Keys Base Unit Connections Access Control and Passwords selected System Configuration Parameterswill sound when an alarm occurs if DISABLE is Temperature Sensors SensorsTheory of Operation Humidity Sensors4-20mASensors Power Supply / Sensor Voltage Selection Contact Closure Sensors Water SensorsMulti-FunctionSensors Resolution Sensor Parameter DescriptionsMaximum Allowed High Scaled ValueRelay Operation D-011-0152 Relay OperationPreparation D-011-0152 To alarm-on-closed From 11-26VDC power supplyloop circuit power supplied via loop From 11-26VDC power supplyD-011-0152 Power Requirements InstallationTools and Supplies Required Mounting the EA800 Rear PlateInstall the Wireless Sensors Install the Wired SensorsEA800 Base Unit Power Connections SENSOR MODEL NO RESET BUTTONSENSOR MODEL NO RESET BUTTOND-011-0152 J6 Input 1 Input 2 Input 3 InputConnecting Wired HA-III+Humidity Sensors Connecting Wired 4-20mASensors Programming Connecting the EA800 Alarm OutputsConfiguring System Parameter Settings Accessing the MAIN MENU for Programming3.Enter the SYSTEM menu and then select the CONFIGURATION menu as shown below DISABLED is selected Setting the Current Date D-011-0152 Setting the TimeAdding a Wireless Temperature Sensor Adding Wireless SensorsD-011-0152 Adding Wireless SensorsD-011-0152 InstallationD-011-0152 D-011-0152 Adding a Wireless Humidity SensorInstallation D-011-0152 D-011-0152 InstallationD-011-0152 D-011-0152 InstallationSelect N.O. Contact or N.C. Contact D-011-0152 Verify Wireless Signal StrengthAdding a Wired Temperature Sensor Adding Wired SensorsD-011-0152 Adding a Wired HA-III+Humidity SensorAdding Wired Sensors Note A supervised WaterBug sensor must be used Adding a Wired WaterBug SensorD-011-0152 Adding a Wired Contact Closure SensorSelect N.O. Contact or N.C. Contact Adding a 4-20mASensor Configuring the Relays Monitoring Environmental Conditions OperationViewing Active Alarms Viewing Sensor SettingsViewing Pending Alarm Information Viewing the Alarm LogViewing the Event Log Viewing Limit SettingsViewing Firmware Information Viewing the Sensor LogOperation D-011-0152Viewing RF Information Viewing RF InformationLocking and Unlocking the EA800 MaintenancePausing Monitoring and Cancelling Pause Replacing a Sensor Adding a SensorSENSORS screen Editing Sensor ParametersF3 F3 Reprogramming a RelayDeleting a Sensor Changing the Time Format Changing the Date FormatChanging Sensor Data Collection Frequency Changing the Date or Time SettingChanging the Buzzer Setting Changing the Buzzer SettingD-011-0152 Changing the PasswordMaintenance Clearing the Alarm Log Clearing the Alarm LogClearing the Sensor Log D-011-0152 Updating the FirmwareMaintenance F3 LOAD/SAVE CONFIG screen Saving Configuration SettingsCONFIG screen Loading Configuration SettingsExporting the Stored Logs Exported Alarm DataExported Sensor Data Exported Event Data12/24/2007 07 06 03 PM Sensor deletedD-011-0152 Exporting the Stored LogsACTIVE ALARMS screen TroubleshootingViewing Signal Strength for a Wireless Sensor Verifying RF Signal StrengthBase Unit and Sensor Specifications SpecificationsAccessories Figure 17. Locked Screen Map Appendix A Screen MapsD-011-0152 Figure 18. Unlocked Screen Map - Top LevelD-011-0152 Appendix A Screen MapsFigure 19. Sensors Screen Map D-011-0152 Figure 20. Add New Sensor Screen MapFigure 21. Edit Sensor Screen Map Appendix A Screen MapsFigure 22. Relay Screen Map D-011-0152D-011-0152 Figure 23. Data Log Screen MapD-011-0152 Appendix A Screen MapsFigure 24. System Screen Map D-011-0152 Figure 25. Configuration Screen MapInstallation Appendix B Planning WorksheetAlarm Condition Appendix B Planning WorksheetD-011-0152 Appendix C Wiring DiagramD-011-0152 Appendix D System Configuration Record Unit of Measure Appendix D System Configuration Record Sensor 6 Settings wireless Appendix D System Configuration Record D-011-0152 Warranty and Service Information Winland Electronics Manufactured in the U.S.A by1950 Excel Drive, Mankato, MN, Outside MN Phone Phone Fax