Base Unit Connections

General Information

Base Unit Connections

Figure 5 shows the EA800 base unit's connections and Table 3 describes the functions of each connection.

Note: The base unit has four wired sensor inputs and four wireless RF sensor inputs.

J5

Power Aux

In Power

Out

J6

Input 1 Input 2 Input 3 Input 4

J13 J14

J2

Output 1

Output 2

Output 3

Output 4

Output 5

Output 6

Output 7

Output 8

Aux

NO COM NC NO COM NC

NO COM NC NO COM NC

NO COM NC

NO COM NC NO COM NC NO COM NC NO COM NC

J8

J9

J10

 

 

 

 

Figure 5 EA800 Base Unit Connections

 

Table 3

EA800 Base Unit Connector Functions

 

 

 

 

 

 

Connector

Designation

 

Function

 

 

 

 

 

 

J2

 

USB

USB Type A connection used to program firmware, export logs, and export

 

 

 

 

and import configuration files. www.winland.com lists compatible USB sticks.

 

 

 

 

 

 

J5

 

Power In

11-26 VDC input power connection for EA800 base unit (from accessory

 

 

 

 

power supply or alarm panel).

 

 

 

 

!

CAUTION

 

 

 

 

CAUTION

 

 

 

 

 

Observe (+) and (-) polarity markings screened on circuit board. EA800

 

 

 

 

can be damaged if power polarity is reversed.

 

 

 

 

 

 

 

 

Aux Power Out

11-26 VDC power out connection for EA800 accessories requiring power

 

 

 

 

(such as HA-III+ Humid Alert). This output voltage equals that of Power In and

 

 

 

 

is current-limited to a maximum of 500 mA.

 

 

 

 

!

CAUTION

 

 

 

 

CAUTION

 

 

 

 

 

Connect only accessories specified in this manual to the Aux Power Out

 

 

 

 

connection. Connection of unsuitable loads to this connection may

 

 

 

 

damage the power supply and EA800, or result in improper or unreliable

 

 

 

 

operation.

 

 

 

 

 

Note: Accuracy for the HA-III+ sensor is stated at +12VDC input.

 

 

 

 

 

If Aux Power Out is used to power the HA-III+ and is not

 

 

 

 

 

+12VDC, then the accuracy of the HA-III+ is compromised.

 

 

 

 

 

 

 

 

 

 

 

 

D-011-0152

7

Image 11
Contents D-011-0152 Limitations of the Alarm System or Device Preparation Table of ContentsInstallation General InformationOperation Overview General InformationHow to Use This Manual D-011-0152 Block DiagramsGeneral Information Symbols on the Product or Manual Labeling D-011-0152 Monitoring ScreensGeneral Information Keys Base Unit Connections Access Control and Passwords selected System Configuration Parameterswill sound when an alarm occurs if DISABLE is Temperature Sensors SensorsTheory of Operation Humidity Sensors4-20mASensors Power Supply / Sensor Voltage Selection Contact Closure Sensors Water SensorsMulti-FunctionSensors High Scaled Value Sensor Parameter DescriptionsResolution Maximum AllowedRelay Operation D-011-0152 Relay OperationPreparation D-011-0152 From 11-26VDC power supply From 11-26VDC power supplyTo alarm-on-closed loop circuit power supplied via loopD-011-0152 Mounting the EA800 Rear Plate InstallationPower Requirements Tools and Supplies RequiredInstall the Wireless Sensors Install the Wired SensorsEA800 Base Unit Power Connections SENSOR MODEL NO RESET BUTTONJ6 Input 1 Input 2 Input 3 Input RESET BUTTONSENSOR MODEL NO D-011-0152Connecting Wired HA-III+Humidity Sensors Connecting Wired 4-20mASensors Programming Connecting the EA800 Alarm OutputsConfiguring System Parameter Settings Accessing the MAIN MENU for Programming3.Enter the SYSTEM menu and then select the CONFIGURATION menu as shown below DISABLED is selected Setting the Current Date D-011-0152 Setting the TimeAdding a Wireless Temperature Sensor Adding Wireless SensorsD-011-0152 Adding Wireless SensorsD-011-0152 InstallationD-011-0152 D-011-0152 Adding a Wireless Humidity SensorInstallation D-011-0152 D-011-0152 InstallationD-011-0152 D-011-0152 InstallationSelect N.O. Contact or N.C. Contact D-011-0152 Verify Wireless Signal StrengthAdding a Wired Temperature Sensor Adding Wired SensorsD-011-0152 Adding a Wired HA-III+Humidity SensorAdding Wired Sensors Note A supervised WaterBug sensor must be used Adding a Wired WaterBug SensorD-011-0152 Adding a Wired Contact Closure SensorSelect N.O. Contact or N.C. Contact Adding a 4-20mASensor Configuring the Relays Monitoring Environmental Conditions OperationViewing Active Alarms Viewing Sensor SettingsViewing Pending Alarm Information Viewing the Alarm LogViewing the Event Log Viewing Limit SettingsD-011-0152 Viewing the Sensor LogViewing Firmware Information OperationViewing RF Information Viewing RF InformationLocking and Unlocking the EA800 MaintenancePausing Monitoring and Cancelling Pause Replacing a Sensor Adding a SensorSENSORS screen Editing Sensor ParametersF3 F3 Reprogramming a RelayDeleting a Sensor Changing the Time Format Changing the Date FormatChanging Sensor Data Collection Frequency Changing the Date or Time SettingChanging the Buzzer Setting Changing the Buzzer SettingD-011-0152 Changing the PasswordMaintenance Clearing the Alarm Log Clearing the Alarm LogClearing the Sensor Log D-011-0152 Updating the FirmwareMaintenance F3 LOAD/SAVE CONFIG screen Saving Configuration SettingsCONFIG screen Loading Configuration SettingsExporting the Stored Logs Exported Alarm DataSensor deleted Exported Event DataExported Sensor Data 12/24/2007 07 06 03 PMD-011-0152 Exporting the Stored LogsACTIVE ALARMS screen TroubleshootingViewing Signal Strength for a Wireless Sensor Verifying RF Signal StrengthBase Unit and Sensor Specifications SpecificationsAccessories Figure 17. Locked Screen Map Appendix A Screen MapsD-011-0152 Figure 18. Unlocked Screen Map - Top LevelD-011-0152 Appendix A Screen MapsFigure 19. Sensors Screen Map D-011-0152 Figure 20. Add New Sensor Screen MapD-011-0152 Appendix A Screen MapsFigure 21. Edit Sensor Screen Map Figure 22. Relay Screen MapD-011-0152 Figure 23. Data Log Screen MapD-011-0152 Appendix A Screen MapsFigure 24. System Screen Map D-011-0152 Figure 25. Configuration Screen MapAppendix B Planning Worksheet Appendix B Planning WorksheetInstallation Alarm ConditionD-011-0152 Appendix C Wiring DiagramD-011-0152 Appendix D System Configuration Record Unit of Measure Appendix D System Configuration Record Sensor 6 Settings wireless Appendix D System Configuration Record D-011-0152 Warranty and Service Information Phone Fax Manufactured in the U.S.A byWinland Electronics 1950 Excel Drive, Mankato, MN, Outside MN Phone