Quadra-Fire QV32-A, QV36-A manual Constructing the Fireplace Chase, Locating the Fireplace

Page 12

Installing the Fireplace

Constructing the Fireplace Chase

A chase is a vertical box-like structure built to enclose the gas fireplace and/or its vent system. Vertical vents that run on the outside of a building may be, but are not required to be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND CONSTRUCTION OF THE CHASE MAY VARY WITH THE TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES. THEREFORE, YOUR LOCAL BUILD- ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner.

This means that the walls, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltra- tion barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, Aladdin Hearth Products recommends that the inside surfaces be sheet- rocked and taped for maximum air tightness.

To further prevent drafts, the firestops should be caulked to seal gaps. Gas line holes and other openings should be caulked or stuffed with insulation. If the unit is being in- stalled on a cement slab, we recommend that a layer of plywood be placed underneath to prevent conducting cold up into the room. Be sure to include spark arrestors for woodburning units if they are required.

THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL CLEARANCES TO THE FIREPLACE ARE MAINTAINED AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

Step 1. Locating the Fireplace

The following diagram shows space and clearance require- ments for locating a fireplace within a room.

Clearance Requirements

The top and back of the fireplace are defined by stand-offs. The minimum clearance to a perpendicular wall extending past the face of the fireplace is 3 inches (76mm). The back of the fireplace may be recessed 16 1/4 inches (413mm) into combustible construction.

3” MIN. (76mm)

B

A

E

D

C

1/2 “ MIN. (13mm)

 

A

B

C

D

E

QV36-A

42”

16 1/4”

31 7/8”

45”

63 3/4”

QV32-A

37”

16 1/4”

29 3/8”

41 1/2”

58 3/4”

Figure 4. Fireplace Dimensions, Locations, and Space Requirements

Minimum Clearances

from the Fireplace to Combustible Materials

 

Inches

mm

Glass Front

...................................... 36

914

Floor

0

0

Rear

1/2

13

Sides

1/2

13

Top (QV-36)

.................................... 3 1/4

83

(QV-32)

................................... 1 1/2

38

Ceiling*

31

787

*The clearance to the ceiling is measured from the top of the unit, excluding the standoffs (see Figure 38).

The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the com- bustible construction, NOT from the screw heads that se- cure the unit together.

Minimum Clearances

from the Vent Pipe to Combustible Materials

 

Inches

mm

Vertical Sections

1

25

Horizontal......................................Sections

3

75

Top

Bottom

1

25

Sides

1

25

At Wall...................................Firestops

2 1/2

63.7

Top

Bottom

1/2

13

Sides

1

25

For minimum clearances, see the direct vent termination clearance in Figures 30 and 31.

12

Image 12
Contents Installers Guide What to do if you smell gasSafety and Warning Information Table of Contents Service Parts Accessories / Accessoires Standing Pilot Ignition / D’ALLUMAGE PAR VeilleuseLog Set Assembly DF-36TS-BK Installation Codes High Altitude InstallationsAppliance Certification CertificationPre-install Preparation Introducing the Village Collection Gas FireplacesANY Such Action MAY Possibly Cause a Fire Hazard Diagram of the QV36-A Diagram of the QV-32-A Constructing the Fireplace Chase Locating the FireplaceClearance Requirements Framing Dimensions Framing the FireplaceDV-FLEX-10 47 3/4 Installing the Vent System Identifying Vent ComponentsVent System Approvals Straight UP Vertical Venting Use SL D-Series components onlyUse D-Series components only Use SL D-Series components only Venting with Two 90 Elbows Natural GAS MAX. = 16 FT 4.8m V + V1 + H MAX. = 40 FT 12.2m Venting with Three 90 elbows Venting with Three 3 90 o Elbows + H 1 MAX. = 16 FT 4.8m + V 1 + H + H Venting with Four 90 elbows SET of Collars YOU are Using could Cause a Fire Adding Venting Components Install Support Brackets Continue Adding Vent ComponentsCeiling Firestop Ceiling Side Vent Termination Positioned SO That the Arrow is Pointing UP191mm Minimum Trapezoid CAP TerminationVent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Positioning, Leveling, and Securing the Fireplace Gas Control SystemStanding Pilot Ignition System Gas Supply Line Gas Pressure RequirementsTo Check for GAS Leaks PressureWiring the Fireplace For Standing Pilot Ignition Wiring Appliance RequirementsOptional Accessories Wall SwitchRefractory Kit Placement BRICK-291, BRICK-293 FinishingInstalling Trim, Logs Ember Material Glass SpecificationsDouble-check for faulty components Before Lighting the FireplaceAfter the Installation Lighting the ApplianceStanding Pilot Ignition What to do if YOU Smell GASFireplace Maintenance Important Turn OFF the GAS Before Servicing Your FireplaceTroubleshooting Be Placed in this Opening Lifetime Warranty