B. Installing Vent Components

After determining which set of starting collars will be used (top or rear), follow venting instructions accordingly.

Venting Out the Rear Vent (See Figure 21)

Remove the installed rear seal cap from the rear starting collars by cutting the strap at each end. Remove the insulation inside the 5” collar. Follow the vent configuration tables accordingly.

Remove the 5” diameter heat shield from the 5” diameter collar by sliding it out.

!WARNING: THE TOP HEAT SHIELD (INSIDE THE FIREBOX) MUST REMAIN ATTACHED IF THE VENT SYSTEM IS ATTACHED TO THE REAR STARTING COLLARS. SEE FIGURE 21.

Venting Out the Top Vent

Remove the top vent collar seal cap by removing the two screws from the upper heat shield. Remove the insulation inside BOTH the 4” diameter and 6 5/8” diameter collars. (See Figure 21).

Remove the 4” diameter heat shield from the 4” diameter collar by sliding it out.

You have to take the glass off for positioning the logs when the unit is finally installed in place and finished around it. Attach vent system to the top starting collars.

WARNING: THE REAR VENT COLLAR SEAL ! CAP MUST REMAIN ATTACHED TO THE REAR VENT COLLARS IF THE VENT SYSTEM IS ATTACHED TO THE TOP STARTING COLLARS. SEE FIGURE 21.

WARNING: FAILURE TO REMOVE INSULATION

!IN THE SET OF COLLARS YOU ARE USING COULD CAUSE A FIRE.

!WARNING: YOU MUST LEAVE THE INSULA- TION IN PLACE IN THE SET OF COLLARS YOU ARE NOT USING.

1.Attach the First Vent Component to the Starting Collars

To attach the first vent component to the starting collars of the fireplace:

Apply a 3/8 inch (9.5mm) bead of stove cement around the fireplace inner vent starting collar.

Lock the vent components into place by sliding the con- centric pipe sections with four (4) equally spaced interior beads into the fireplace collar or previously installed com- ponent end with four (4) equally spaced indented sections.

When the internal beads of each outer pipe line up, ro- tate the pipe section clockwise about one-quarter (1/4) turn. The vent pipe is now locked together.

Slide the ceramic fiber pad over the first vent section and place it flush to the fireplace. Continue to add vent com- ponents.

STARTING

COLLAR

3/8”

(9.5mm)

STOVE

SEALANT

BEAD

FIRST VENT

COMPONENT

1 INCH (25.4mm)

Figure 22. Attaching the First Vent Component

to the Starting Collars

Insert screwdriver

Venting

or similar object

Out Rear

here to remove cap.

 

 

Venting

 

 

Out Top

SEAL

SEAL

INSULATION,

!WARNING: A 3/8 INCH (9.5 MM) BEAD OF STOVE CEMENT MUST BE PLACED AROUND

CUT HERE

Figure 21

HEAT

SHIELD

DISCARD

INSULATION

CAP

CAP

DISCARD

 

BOTH

 

 

 

 

PIECES

 

HEAT

 

 

SHIELD

 

THE FIREPLACE INNER VENT STARTING COLLAR BEFORE ATTACHING THE FIRST VENT COMPO- NENT. FAILURE TO SEAL THIS JOINT MAY CAUSE THE FIREPLACE TO OPERATE IMPROPERLY. SEE THE DIAGRAM .

If the installation is for a termination cap attached directly to the fireplace, skip to the sections, Install Firestops and Vent Termination.

26

Image 26
Contents Installers Guide What to do if you smell gasSafety and Warning Information Table of Contents Service Parts Accessories / Accessoires Standing Pilot Ignition / D’ALLUMAGE PAR VeilleuseLog Set Assembly DF-36TS-BK Appliance Certification Installation CodesHigh Altitude Installations CertificationANY Such Action MAY Possibly Cause a Fire Hazard Pre-install PreparationIntroducing the Village Collection Gas Fireplaces Diagram of the QV36-A Diagram of the QV-32-A Clearance Requirements Constructing the Fireplace ChaseLocating the Fireplace Framing Dimensions Framing the FireplaceDV-FLEX-10 47 3/4 Vent System Approvals Installing the Vent SystemIdentifying Vent Components Use D-Series components only Straight UP Vertical VentingUse SL D-Series components only Use SL D-Series components only Venting with Two 90 Elbows Natural GAS MAX. = 16 FT 4.8m V + V1 + H MAX. = 40 FT 12.2m Venting with Three 90 elbows Venting with Three 3 90 o Elbows + H 1 MAX. = 16 FT 4.8m + V 1 + H + H Venting with Four 90 elbows SET of Collars YOU are Using could Cause a Fire Adding Venting Components Install Support Brackets Continue Adding Vent ComponentsCeiling Firestop Ceiling Side 191mm Vent TerminationPositioned SO That the Arrow is Pointing UP Minimum Trapezoid CAP TerminationVent Termination Minimum Clearances Minimum Height from Roof to Lowest Discharge Opening Standing Pilot Ignition System Positioning, Leveling, and Securing the FireplaceGas Control System To Check for GAS Leaks Gas Supply LineGas Pressure Requirements PressureOptional Accessories Wiring the FireplaceFor Standing Pilot Ignition Wiring Appliance Requirements Wall SwitchRefractory Kit Placement BRICK-291, BRICK-293 FinishingInstalling Trim, Logs Ember Material Glass SpecificationsDouble-check for faulty components Before Lighting the FireplaceStanding Pilot Ignition After the InstallationLighting the Appliance What to do if YOU Smell GASFireplace Maintenance Important Turn OFF the GAS Before Servicing Your FireplaceTroubleshooting Be Placed in this Opening Lifetime Warranty